Short answer: Two. Clause I.2 (TS p.159 / EN p.156): signals from water flow alarms and alarm valves are indicated as a fire alarm, which is level A in Table I.1. Technical faults such as a power failure, which could prevent the system from operating correctly in a fire, are indicated as a fault alarm, which is level B. The standard contains no four step alarm scheme numbered 1 to 4.

If nobody hears that a sprinkler system has operated, the outcome is close to the system never having operated at all. That is why TS EN 12845+A2:2026 moves alarm transmission into a separate and normative annex, Annex I. Source: TS EN 12845+A2:2026, Annex I (TS p.158-159 / EN p.155-156), Clause 16 and Annex H.

Annex I is normative

The word "(normative)" appears immediately under the title of Annex I, which means it is a requirement and not a recommendation. The annex consists of two short clauses: I.1 Functions to be monitored and I.2 Alarm levels. The whole annex rests on a single table, Table I.1.

Clause I.1: the alarms specified in this standard shall be connected to an alarm panel in the sprinkler control room or the pump room and shall be transmitted onwards depending on the importance of the alarm. The alarms shall be transmitted to a permanently manned location inside or outside the premises. Type B alarms (technical alarms) may in addition be transmitted to a responsible person (see Clause 20.1) so that immediate corrective action can be taken. Where a direct connection to the fire service exists, it is recommended that the alarm transmission procedure be agreed with the authorities.

There are only two alarm levels: A and B

Clause I.2 (TS p.159 / EN p.156) settles the classification in two lines:

The standard contains no four step (Level 1-4) alarm scheme; the only distinction Annex I recognises is A and B.

Table I.1: alarm types to be transmitted

Table I.1 (TS p.158-159 / EN p.155-156) lists each alarm with both its source clause and its type:

Alarm Clause Type
Water flow alarm 16.1.1 A
Low pressure in the town main 9.2 B
Water flow detector in the pump room 10.3.2 A
Priming tank low level 10.6.2.4 B
Electric pump set: on demand 10.8.5.1 B
Electric pump set: start failure 10.8.5.1 B
Electric pump set: running 10.8.5.1 A
Electric pump set: power not available 10.8.5.1 B
Diesel pump set: automatic mode off 10.9.2 B
Diesel pump set: start failure 10.9.2 B
Diesel pump set: running 10.9.2 A
Diesel pump set: common fault 10.9.2 B
Trace heating circuits 11.1.2.3 B
Low pressure: type A pre-action system 11.4.1.2 B
Low pressure: dry pipe and pre-action systems 16.2.3 B
Zoned systems: open control valve D.3.7 B
Zoned systems: partly closed control valve D.3.7 B
Zoned systems: partly open subsidiary valve D.3.7 B
Zoned systems: low main pressure D.3.7 B
Zoned systems: water flow in the installation D.3.7 A
Zoned systems: water flow in the zone D.3.7 A
Monitored sprinkler systems: partly closed stop valves Annex H B
Monitored sprinkler systems: liquid levels Annex H B
Monitored sprinkler systems: low pressure Annex H B
Monitored sprinkler systems: power failure Annex H B
Monitored sprinkler systems: low temperature in the pump room Annex H B

The point to watch in the table is the correct clause numbers for the pump alarms: 10.8.5.1 for the electric pump set and 10.9.2 for the diesel pump set. Clause 10.8.5.1 (TS p.68 / EN p.65) lists four conditions to be monitored: power available to the motor (on all three phases where alternating current is used), pump on demand, pump running, and start failure. On the diesel side, Clause 10.9.2 (TS p.69 / EN p.66) lists four indicator lights: pump running, start failure, common faults, and automatic mode off; these shall be indicated both locally and at a location permanently attended by responsible personnel.

The equipment producing the alarm: Clause 16

Annex I governs transmission; Clause 16 defines the equipment producing the alarm:

The fire service connection: Clause 16.3

Clause 16.3 (TS p.114 / EN p.111) is directly on point: equipment providing automatic transmission of alarm signals from the sprinkler installation to the fire service or a remote manned centre shall be checkable for:

Where there is a direct connection to the fire service, it is recommended that the test procedure be agreed with the authorities in order to avoid false calls.

On the marking side, Clause 18.2.6.1 (TS p.119 / EN p.116) requires a notice stating the fact to be placed adjacent to the alarm test valve wherever water flow into an installation initiates an automatic alarm to the fire service.

Its relationship with Annex H: what are we monitoring?

The last five rows of Annex I refer to Annex H. Annex H (normative, TS p.156-157 / EN p.153-154) sets the general framework for monitoring: all devices used for monitoring shall have a protection of at least IP 54 to EN 60529, and no more than 15 non-addressable supervisory devices shall be connected to a common indicator. All signal and alarm circuits shall be fully supervised and shall give a fault alarm in the event of a short circuit or an open circuit.

The thresholds for the monitored quantities are quantified in Annex H:

For the pump room, Clause 10.3.3 (TS p.61 / EN p.58) gives the minimum temperatures: 4 °C for electrically driven pump sets and 10 °C for diesel driven pump sets.

Maintenance: how often is the alarm chain tested?

Field note: using Table I.1 as a wiring schedule is the habit that saves the most time at commissioning; every row in the table is one contact, and every type letter tells you what colour that contact will show on the panel.

Frequently Asked Questions

How many alarm levels does EN 12845 Annex I define?

Two. Clause I.2 (TS p.159 / EN p.156): signals from water flow alarms and alarm valves are indicated as a fire alarm, which is level A in Table I.1. Technical faults such as a power failure, which could prevent the system from operating correctly in a fire, are indicated as a fault alarm, which is level B. The standard contains no four step alarm scheme numbered 1 to 4.

Which clauses do the electric and diesel pump alarms in Table I.1 refer to?

Table I.1 (TS p.158 / EN p.155): Clause 10.8.5.1 for the electric pump set and Clause 10.9.2 for the diesel pump set. For the electric pump, demand, start failure and power not available are type B, while pump running is type A. For the diesel pump, automatic mode off, start failure and common fault are type B, while pump running is type A.

Where are the alarms transmitted?

Clause I.1 (TS p.158 / EN p.155): the alarms are connected to an alarm panel in the sprinkler control room or the pump room and are transmitted onwards according to their importance. The alarms shall be transmitted to a permanently manned location inside or outside the premises. Type B (technical) alarms may in addition be transmitted to a responsible person so that immediate corrective action can be taken. Where there is a direct connection to the fire service, the alarm transmission procedure should be agreed with the authorities.

Which continuities have to be checkable on a fire service connection?

Clause 16.3 (TS p.114 / EN p.111): equipment providing automatic transmission of alarm signals from the sprinkler installation to the fire service or a remote manned centre shall be checkable for the continuity of the connection and for the continuity of the connection between the alarm switch and the control unit. Where there is a direct connection to the fire service, the test procedure should be agreed with the authorities in order to avoid false calls.

How often is this alarm installation inspected?

Clause 20.3.3.3 (TS p.124 / EN p.121): the electrical installation of the fire service and remote centre alarm is checked at intervals not exceeding 6 months. In addition, Clause 20.2.2.3 requires every water motor alarm to be sounded for at least 30 seconds weekly, and Clause 20.3.2.8 requires the correct operation of the flow alarms to be checked in the quarterly routine.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.