Short answer: Clause 14.2.3 (TSE p.107 / EN p.104) lists three prohibitions: sidewall sprinklers shall not be installed in HH installations (except for the protection of corridors, cable ducts and columns), in OH storage areas, or above suspended ceilings. In addition they may be installed only under flat ceilings.

Source: TS EN 12845+A2:2026 (EN 12845:2015+A2:2026), Clauses 12.1.2, 12.2, 12.3, 12.4.1, 12.4.3, 14.2.1, 14.2.3 and Tables 20, 37a.

The sidewall sprinkler has no clause of its own in EN 12845; it is regulated from two places. The layout and the area of coverage are in Clause 12.2 with Table 20, and the restrictions on use are in Clause 14.2.3. This article brings the two together and uses only the figures given by the standard.

Which clauses apply

Clause 12.2 (TSE p.73 / EN p.70): the maximum area of coverage per sprinkler shall be determined in accordance with Table 19 for sprinklers other than sidewall, and in accordance with Table 20 for sidewall sprinklers.

Clause 14.2.1 (TSE p.106-107 / EN p.103-104): sprinklers shall be used in accordance with Table 37a for the various hazard classes and as specified in 14.2.2 to 14.2.4. The restrictions concerning sidewall sprinklers are in Clause 14.2.3.

Table 20: the layout rules

Table 20 (TSE p.74 / EN p.71) contains rows for only two hazard classes, because Clause 14.2.3 prohibits general use in HH.

Hazard class Maximum area per sprinkler (m²) Between sprinklers along the wall (m) From sprinkler to end of wall (m) Room width w (m) Room length l (m) Number of sidewall rows Layout
LH 17.0 4.6 2.3 w ≤ 3.7 any 1 single row
LH 17.0 4.6 2.3 3.7 < w ≤ 7.4 ≤ 9.2 2 standard
LH 17.0 4.6 2.3 3.7 < w ≤ 7.4 > 9.2 2 staggered
LH 17.0 4.6 2.3 w > 7.4 any 2 (see NOTE 1) standard
OH 9.0 3.4 (see NOTE 2) 1.8 w ≤ 3.7 any 1 single row
OH 9.0 3.4 (see NOTE 2) 1.8 3.7 < w ≤ 7.4 ≤ 6.8 2 standard
OH 9.0 3.4 (see NOTE 2) 1.8 3.7 < w ≤ 7.4 > 6.8 2 staggered
OH 9.0 3.4 (see NOTE 2) 1.8 w > 7.4 any 2 standard (see NOTE 1)

The four notes to the table are as binding as the table itself:

Clause 14.2.3: three prohibitions and one condition

Clause 14.2.3 (TSE p.107 / EN p.104) is short and clear. Sidewall sprinklers shall not be installed:

And one positive condition: sidewall sprinklers may be installed only under flat ceilings.

This last sentence should be read together with Clause 12.4.3 (TSE p.75 / EN p.72): sprinklers shall be installed with their deflectors parallel to the slope of the roof or ceiling; where the slope is greater than 30° to the horizontal, a row of sprinklers shall be fixed at the ridge, or radially not more than 0.75 m from the ridge. For sidewall sprinklers the "flat ceilings only" condition closes off this flexibility.

The K-factor: Table 37a

Table 37a (TSE p.107 / EN p.104) lists sidewall among the types permitted in two classes:

Hazard class Design density Permitted types Nominal K-factor
LH 2.25 mm/min conventional, spray, ceiling, flush, flat spray, recessed, concealed and sidewall 57
OH 5.0 mm/min conventional, spray, ceiling, flush, flat spray, recessed, concealed and sidewall 80 or 115

The sidewall type is not listed in the HHP, HHS and HHS in-rack rows, which is consistent with the HH prohibition of Clause 14.2.3.

Distance to the wall and to adjacent sprinklers

Clause 12.4.1 (TSE p.75 / EN p.72): the maximum distance from walls and partitions to sprinklers shall be the smallest of the following values:

Where Table 20 is used, the last item produces 4.6/2 = 2.3 m in LH and 3.4/2 = 1.7 m in OH (or 3.7/2 = 1.85 m where NOTE 2 is applied); the smallest of these and the other values is then selected.

Clause 12.3 (TSE p.75 / EN p.72): sprinklers shall not be installed at intervals of less than 2 m. The exceptions are: where arrangements are made to prevent adjacent sprinklers from wetting each other (using baffles of approximately 200 mm × 150 mm or intervening constructional features), intermediate sprinklers in racks (12.5.3), and escalators and stair wells (12.4.11).

Clause 12.1.2 (TSE p.73 / EN p.70): in LH and OH a clear space of 0.3 m below the deflector shall be maintained for flat spray sprinklers and 0.5 m in all other cases.

A corridor example: how the figures tie together

The calculation below is only the arithmetic of the figures in Table 20 itself; there is no such example in the standard.

Take an LH corridor 24.0 m long and 2.0 m wide, to be protected with a single row of sidewall sprinklers (since w = 2.0 m ≤ 3.7 m, Table 20 permits a single row).

If 5 sprinklers were chosen, 4 intervals × 4.6 m = 18.4 m would be covered, and dividing the remaining 5.6 m between the two ends would give an end distance of 2.8 m, exceeding the 2.3 m limit of Table 20.

Sidewall sprinklers in the spares stock

The spare parts provision of Clause 20.1 (TSE p.122 / EN p.119) carries one detail: where installations include high temperature sprinklers, sidewall or other variants of the sprinkler pattern, or multiple controls, a sufficient number of spares of these shall also be kept. After spares have been used, the stock shall be replenished without delay.

Frequently Asked Questions

Where may sidewall sprinklers not be used?

Clause 14.2.3 (TSE p.107 / EN p.104) lists three prohibitions: sidewall sprinklers shall not be installed in HH installations (except for the protection of corridors, cable ducts and columns), in OH storage areas, or above suspended ceilings. In addition they may be installed only under flat ceilings.

What is the maximum area of coverage per sidewall sprinkler?

Table 20 (Clause 12.2, TSE p.74 / EN p.71): 17.0 m2 per sprinkler for LH and 9.0 m2 for OH. The maximum distance between sprinklers along the wall is 4.6 m in LH and 3.4 m in OH; the maximum distance from a sprinkler to the end of the wall is 2.3 m in LH and 1.8 m in OH.

Can the 3.4 m limit along the wall be increased in OH?

Table 20 NOTE 2: this distance may be increased to 3.7 m provided that the fire resistance of the ceiling is not less than 120 min.

Where is the deflector of a sidewall sprinkler positioned?

Table 20 NOTE 3: the sprinkler deflectors shall be positioned between 0.1 m and 0.15 m below the ceiling and between 0.05 m and 0.15 m horizontally from the wall.

Above what room width are two rows of sidewall sprinklers required?

Table 20: where the room width w does not exceed 3.7 m, a single row is sufficient. For 3.7 < w of 7.4 m, two rows are required; where the room length exceeds 9.2 m in LH or 6.8 m in OH, the layout shall be staggered. Where w exceeds 7.4 m, two rows are again used and, under NOTE 1, one or more additional rows of roof or ceiling sprinklers are required.

References


SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.