Design density is the water flow per unit area. In SI it is given in mm/min, numerically identical to L/min/m²: 5 mm/min means 5 litres per square metre per minute.

Why a rainfall unit?

mm/min is in fact a rainfall unit: it states how many millimetres of water are applied to the surface each minute. That notation gives the engineer an intuitive check; 5 mm/min is 300 mm of rainfall an hour, an intensity never seen in nature. That is what a sprinkler does.

Unit conversion

  • 1 mm/min is about 0.0245 gpm/ft²
  • 1 gpm/ft² is about 40.75 mm/min

For example, the 0.20 gpm/ft² (over 1500 ft²) that NFPA 13-2025 Table 19.2.3.1.1 gives for Ordinary Hazard Group 2 corresponds to about 8.1 mm/min (over 140 m²). EN 12845 uses 5.0 mm/min for ordinary hazard; but because the areas differ, the total flows are of the same order: about 8.1 × 140 ≈ 1,130 L/min for NFPA OH2 and 5.0 × 216 = 1,080 L/min for EN OH3.

Density alone is meaningless

If a page states only "5 mm/min", the information is incomplete. Density is always read together with the area of operation, because the total flow is the product of the two:

Q = density × area of operation
OH-3 example: 5.0 mm/min × 216 m² = 1,080 L/min

EN 12845 values by hazard class

ClassDensityArea (wet)Area (dry)
LH2.25 mm/min84 m²Not permitted → OH1
OH15.0 mm/min72 m²90 m²
OH25.0 mm/min144 m²180 m²
OH35.0 mm/min216 m²270 m²
OH45.0 mm/min360 m²Not permitted → HHP1
HHP17.5 mm/min260 m²325 m²
HHP210.0 mm/min260 m²325 m²
HHP312.5 mm/min260 m²325 m²

Note that across the OH groups the density stays fixed and the area changes. Moving from OH1 to OH4 does not mean more water per square metre; it means wetting a larger area at the same density.

Why does the area grow on a dry system?

EN 12845 Table 3 gives a roughly 25 percent larger area of operation for dry and alternate installations (for example OH3 216 → 270 m²). For HHS storage, the notes to Tables 4 and 5 advise avoiding dry and alternate systems and, if that is not possible, increasing the area by 25 percent. The density does not change; because the area grows, the total flow and the tank volume rise.

An error to avoid: treating the density as one average over the whole area. In EN 12845 density is the total flow of the four most closely adjacent sprinklers divided by the area they cover, and it must not fall below the design value for any such group within the area of operation (13.4.1). The most unfavourable sprinkler must also meet the minimum pressure (13.4.4).

The minimum pressure rule

Even where the density calculation gives a low pressure, EN 12845 clause 13.4.4 sets floors: 0.70 bar for LH, 0.35 bar for OH, 0.50 bar for HHP and HHS (except in-rack), and for in-rack sprinklers 1.00 bar for K115 (K8.0) and 2.00 bar for K80 (K5.6). The rule is explicit — the density or that pressure, whichever is higher.

Frequently Asked Questions

What does 5 mm/min mean?

Five litres of water per square metre per minute. The unit mm/min is numerically identical to L/min/m² and is a rainfall unit.

Is density alone sufficient?

No. Density is always read with the area of operation; the total flow is the product of the two. For OH-3: 5.0 mm/min × 216 m² = 1,080 L/min.

Does the density increase on a dry system?

No, the density stays fixed; the area of operation grows. EN 12845 Table 3 gives it about 25 percent larger on dry and alternate systems.

What is the conversion between mm/min and gpm/ft²?

1 mm/min is about 0.0245 gpm/ft²; in reverse, 1 gpm/ft² is about 40.75 mm/min.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

EN 12845:2015+A2:2026 · NFPA 13 (2025) · EN 12259-1 · FM Global Data Sheets. Definitions are for information; the full text of the standard governs in design.