For decades, AFFF (Aqueous Film Forming Foam) was the default for hydrocarbon fires; it is now being phased out because of its PFAS (forever chemicals) content. US, EU, Australia, and Turkey are transitioning to fluorine-free F3 (Fluorine-Free Foam). NFPA 11 updates performance and system requirements. This article combines technical, environmental, and operational perspectives.

The PFAS Problem

  • AFFF contains PFOA/PFOS and short-chain PFAS
  • Non-biodegradable (forever chemicals)
  • Groundwater contamination: thousands of hectares impacted
  • Health: cancer, immune, developmental effects
  • EPA, EU REACH: phased ban 2023-2026

What Is F3?

F3 (Fluorine-Free Foam) appears in NFPA 11 as SFFF (synthetic fluorine-free foam): a foam concentrate based on a mixture of hydrocarbon surface active agents that is not formulated to contain PFAS (NFPA 11-2024, 3.3.11.8).

  • Hydrocarbon surfactants and polymer additives instead of fluorosurfactants
  • UL 162 and EN 1568 compliant
  • Does not form an aqueous film (unlike AFFF); extinguishes by foam blanket
  • AR-F3 (alcohol-resistant) for polar solvents

Performance Comparison

F3 vs AFFF lab and field tests:

  • Gasoline: NFPA 11-2024 Table 5.8.1.2 requires at least 6.5 L/min/m2 for SFFF (F3) versus 4.1 L/min/m2 for AFFF on nondiked spill fires
  • Jet fuel: F3 comparable
  • Polar solvents (ethanol, methanol): AR-F3 compatible; the proportioning rate follows the product listing
  • Burnback: F3 slightly weaker; more frequent re-application
  • Fire size: Small-medium OK; very large tank fires debated

Conversion Steps

  1. Rinsing: Drain the old AFFF tank and piping, collect the AFFF solution, then rinse several times with PFAS-free water — residual PFAS must not mix with the new foam. Dispose of the rinsate per regulations (NFPA 11-2024 Annex E)
  2. Proportioner update: F3 viscosity differs; re-calibrate or replace
  3. Foam chamber/monitor: F3 flow pattern differs; nozzle may change
  4. Tank capacity: if the rate changes, recalculate the concentrate tank and stock
  5. UL-listed combo: Concentrate + proportioner + discharge device in one listing
  6. AFFF waste: Dispose as hazardous waste (high-temperature incineration)

Economics

  • System conversion: cost depends on facility size
  • AFFF disposal: added per-liter cost
  • Long-term: avoid PFAS cleanup + health liability

Situation in Turkey

Turkey's Ministry of Environment, Urbanization and Climate Change is working on PFAS guidance. Large refineries, petrochemical plants, major airports and aviation facilities have already started conversion. Smaller sites are mostly using up their AFFF stock — the market expects the transition to be complete by 2027. Local F3 production is limited; imports dominate.

Common Mistakes

  1. Adding F3 on top of AFFF: Contamination, unpredictable performance.
  2. Proportioner not re-set: F3 run at the old setting instead of the rate in the product listing → underdose.
  3. Dumping AFFF waste to environment: Fine + cleanup cost.
  4. Non-UL-listed combo: Outside tested system, insurance dispute.

Conclusion

PFAS bans are rewriting the fire suppression industry. F3 can be used with a correctly listed product; correct system conversion is critical. Turkey will transition quickly once EU-aligned regulation lands. Facility managers must plan now; last-minute conversion is expensive and risky.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

Core references: NFPA 11, NFPA 11 Chapter 6 (foam-water) (a separate standard, NFPA 16, until 2021), UL 162, EN 1568, EPA PFAS Regulation. Original NFPA post: NFPA Today - PFAS Foam Transition.