Turkey's large airports reach annual capacities of 90, 41 and 39 million passengers. At the largest, the terminal covers 1.4 million m², there are 230 passenger boarding bridges, and about 800,000 L of Jet A-1 is held on the apron. At this scale NFPA 415 brings boarding bridge protection and apron drainage to the table; atrium smoke control falls under NFPA 92. The hardest part on these projects is planning from the start that these systems must work as an integrated whole, not independently.

Terminal Hazards

  • Atrium: 30–40 m high, with an unprotected steel roof
  • Baggage conveyors: 15 km long; the rubber belts add fire load
  • Duty-free shops: High fire load from alcohol, perfume and cosmetics
  • Occupant load: 40,000 people at peak hour; the evacuation scenario is critical
  • Jet A-1 hydrant system: Pressurized line beneath the apron

NFPA 415 and Passenger Boarding Bridges

  • Passenger boarding bridge: protection is achieved either by fire-resistant construction design or by fixed suppression (NFPA 415 6.1.2)
  • Fixed suppression: open-head deluge water spray (NFPA 15) or an automatic foam system; at least 5 minutes (NFPA 415 6.5)

Apron Drainage

  • Drainage slope: at least 1% away from structures for the first 15 m (50 ft), then at least 0.5% toward the inlets (NFPA 415 5.1.1)

Atrium Smoke Control

  • NFPA 92: Reference standard for smoke control
  • CFD modeling: Scenario simulation with FDS 6
  • Makeup air: Natural or mechanical inlets
  • Smoke-free height: The smoke layer must stay at least 1.8 m above the egress path

Turkey Airports

  • Largest airport: Annual capacity of 90 million passengers
  • Second-largest hub: 41 million passengers
  • Tourism airport: 39 million passengers; tourism-driven seasonal peaks
  • Another large airport: 17 million passengers
  • Largest terminal: Opened with a 1.4 million m² terminal

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 415, NFPA 92, ICAO Annex 14, FAA AC 150/5210. NFPA 415 Aircraft Fueling Ramp Drainage and Loading Walkways.