Bearings, gears, small arms and jet engines require grinding, polishing, plating and laser cutting. The resulting metal dust cloud is combustible and explosible; aluminum, magnesium and titanium dusts release hydrogen (H₂) on contact with water, so firefighting with water can increase the explosion risk. NFPA 484 governs combustible-metal safety.
Metal Dust Properties
- Aluminum dust: Kst 400–600 bar·m/s (Class ST3)
- Magnesium dust: Kst about 508 bar·m/s (28 µm sample; NFPA 652 Table A.5.2.2(e)); keeps burning in contact with water
- Titanium dust: can be pyrophoric; cloud ignition temperature is about 330-450 °C depending on the sample (NFPA 652 Table A.5.2.2(h))
- Steel/iron dust: Kst 100–200 (ST1)
- Minimum ignition energy (MIE): varies with metal and particle size; NFPA 652 Table A.5.2.2(h) shows cloud MIE of about 5 mJ for zirconium, 25 mJ for titanium, 40 mJ for magnesium and 50 mJ for aluminum; a static spark can be enough, so never take grounding lightly
Collection Systems
- Wet collector: The required choice for aluminum/magnesium (dust captured by a water curtain)
- Dry baghouse: OK for steel
- Spark detection: IR + water mist
- Grounding: bonding and grounding resistance below 1×106 Ω (NFPA 654 7.6.3, NFPA 652 9.4.7.1.3)
- Central vacuum: All machines tied in
NFPA 484 Ventilation
- Duct velocity: enough to keep dust from settling in the duct (NFPA 484 11.2.3.4); the NFPA 654 annex usually cites 4000 fpm (about 20 m/s) or higher
- Deflagration venting: Av/V ratio calculated per NFPA 68
- Explosion relief: vent closure weight must not exceed 12.2 kg/m² (2.5 lb/ft²) of free vent area (NFPA 68 9.2.6)
Field Practice
- Grinder: Water tank beneath
- Anodizing: Separate room + acid vent
- Electrical: Zone 21 Ex tD motor
- Cleaning: bulk dust is removed with conductive, nonsparking scoops and soft brooms or natural-fiber brushes (NFPA 484 9.4.3, 9.5.1); vacuums only for the small residual amount and, if portable, only if listed for the material (9.5.2, 9.6.4); compressed-air cleaning only under 9.7, at no more than 206 kPa (30 psi)
- Fire gear: Class D metal extinguisher
Turkish Industry
- Bearing plants: Steel grinding dust
- Defense plants: Aluminum dust
- Aerospace plants: Jet engine Ti dust
- Integrated steel mills: Iron dust
- Incidents: an aluminum-dust blast

Metal Dust with MEP Calc
MEP Calc sizes metal-dust plants: capture velocity flow, deflagration vent area and NFPA 484 wet collector.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 484, NFPA 654, NFPA 68, OSHA 1910, VDI 2263. NFPA 484 Combustible Metals.