Biogas plants ferment agricultural waste, manure and sewage sludge. The biogas is 55-70 percent CH4, 30-45 percent CO2 and 100-3000 ppm H2S. NFPA 820 is the reference for sewage-sludge digesters at wastewater plants; agricultural-waste and manure biogas plants are not in its scope list (1.1.2). It labels the digester interior and the envelope around its cover Class I Div 1.
Biogas Chemistry
- CH4: 55-70 percent, LEL 5 percent
- CO2: 30-45 percent
- H2S: 100-3000 ppm (very toxic)
- Humidity: 100 percent RH
- Calorific: 20-25 MJ/m3
NFPA 820 Classification
- Inside digester: Class I Div 1 Zone 0
- Digester cover envelope (open air): Class I Div 1 up to 3 m above the cover and 1.5 m from the walls; Div 2 beyond that, up to 4.6 m above the Div 1 area and 1.5 m further out around the walls (Table 6.2.2(a))
- Gas holder: Div 1 Zone 1
- Holding/buffer room: Div 2 Zone 2
- Flare stack: 3 m hot zone
NFPA 820 Ventilation
- Digester room: 12 ACH
- Pump room: 6 ACH and Zone 2
- CH4 detection: alarm set at 10 percent LEL (or 0.5 LEL-m); the AHJ may permit a higher value where spurious alarms occur (7.4.6)
- H2S detection: personnel protection from toxic gas is outside NFPA 820 (1.1.3)
CHP and Flare
- CHP engine: 500 kW-5 MW typical
- Gas treatment: Fe2O3 H2S scrubbing
- Flare: Emergency 1200 °C
- Scrubber: Biogas upgrade to RNG
- Grid injection: 97+ percent CH4 biomethane
Turkish Biogas Examples
- Large-scale plant: 18 MW biogas
- Municipal plants: Municipal waste
- Sugar industry: sugar-beet pulp fermentation
- Poultry sector: Chicken manure
- EPDK: 400+ licensed biogas plants

Biogas with MEP Calc
MEP Calc sizes biogas digester-room 12 ACH, CH4 10 percent LEL alarm, H2S detection, Zone 1 electrical and NFPA 820 zoning.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.