Biogas plants ferment agricultural waste, manure and sewage sludge. The biogas is 55-70 percent CH4, 30-45 percent CO2 and 100-3000 ppm H2S. NFPA 820 is the reference for sewage-sludge digesters at wastewater plants; agricultural-waste and manure biogas plants are not in its scope list (1.1.2). It labels the digester interior and the envelope around its cover Class I Div 1.

Biogas Chemistry

  • CH4: 55-70 percent, LEL 5 percent
  • CO2: 30-45 percent
  • H2S: 100-3000 ppm (very toxic)
  • Humidity: 100 percent RH
  • Calorific: 20-25 MJ/m3

NFPA 820 Classification

  • Inside digester: Class I Div 1 Zone 0
  • Digester cover envelope (open air): Class I Div 1 up to 3 m above the cover and 1.5 m from the walls; Div 2 beyond that, up to 4.6 m above the Div 1 area and 1.5 m further out around the walls (Table 6.2.2(a))
  • Gas holder: Div 1 Zone 1
  • Holding/buffer room: Div 2 Zone 2
  • Flare stack: 3 m hot zone

NFPA 820 Ventilation

  • Digester room: 12 ACH
  • Pump room: 6 ACH and Zone 2
  • CH4 detection: alarm set at 10 percent LEL (or 0.5 LEL-m); the AHJ may permit a higher value where spurious alarms occur (7.4.6)
  • H2S detection: personnel protection from toxic gas is outside NFPA 820 (1.1.3)

CHP and Flare

  • CHP engine: 500 kW-5 MW typical
  • Gas treatment: Fe2O3 H2S scrubbing
  • Flare: Emergency 1200 °C
  • Scrubber: Biogas upgrade to RNG
  • Grid injection: 97+ percent CH4 biomethane

Turkish Biogas Examples

  • Large-scale plant: 18 MW biogas
  • Municipal plants: Municipal waste
  • Sugar industry: sugar-beet pulp fermentation
  • Poultry sector: Chicken manure
  • EPDK: 400+ licensed biogas plants

Biogas with MEP Calc

MEP Calc sizes biogas digester-room 12 ACH, CH4 10 percent LEL alarm, H2S detection, Zone 1 electrical and NFPA 820 zoning.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 820, NFPA 30, EPA 40 CFR 503, ATEX 137, EPDK regulation. NFPA 820 Wastewater Treatment.