A cement plant fires clinker kiln at 1,450 °C on coal, petcoke or RDF. Coal mill, clinker cooler and by-pass dust collectors hold combustible dust. NFPA 664 (written for wood processing, but its dust explosion methodology is shared), NFPA 652 dust hazard analysis (DHA) and NFPA 68 explosion venting should be applied together.

Risk Points

  • Coal mill: 70-90 °C internal - self-ignition risk
  • Coal bin: 20 t stock - CO monitoring
  • Clinker cooler dust filter: 450 °C dust buildup; periodic cleaning required
  • By-pass dust silo: alkali salts + dust-laden air
  • RDF bunker: mixed plastics/textile alternative fuel

Coal Mill Dust Properties

  • Kst (coal): 50-150 bar m/s (St1)
  • Pmax: 6-8 bar
  • MEC: 60 g/m3
  • MIE: 50-100 mJ
  • Petcoke: in the NFPA 68 Table F.1(b) sample KSt 47 bar m/s and minimum flammable concentration 125 g/m3 (bituminous coal sample: 129 bar m/s, 60 g/m3); values are sample-specific, use measured values for design

NFPA 68 Venting

Coal mill 50 m3:

  • The required area comes from NFPA 68-2018 Equation 8.2.1.1 using Pmax, KSt, volume, Pstat and Pred
  • Example inputs: V = 50 m3, KSt 150 bar m/s; the result follows from the equation with measured Pmax, Pstat and Pred
  • Panel must vent outdoors - no personnel
  • A vent duct behind the panel changes the required area; the effect is calculated with the equations of NFPA 68 Section 8.5

CO Monitoring and Inerting

  • Coal bin CO: 50 ppm alarm, 200 ppm N2 inert
  • N2 inerting: maintain O2 <8 percent
  • CO2 inerting: alternative, lower cost
  • Temperature: bunker thermocouples
  • Bearing monitoring: coal mill bearing temp >70 °C alarm

Coal mill venting with MEP Calc

MEP Calc sizes NFPA 68 venting Av, N2 inerting flow and CO monitoring setpoints for coal mills.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 652, NFPA 68, NFPA 69, NFPA 664, CEMBUREAU Technical Report, ACerS. NFPA 664 Wood Processing standard.