Premium multiplexes in Turkey's large shopping malls are the country's flagship cinema venues. An IMAX auditorium holds 400 seats with a 30 m screen and 15 kW laser projection. NFPA 101 treats cinemas as assembly occupancy, requiring aisles of at least 1065 mm where level or ramped with seating on both sides (915 mm if serving 50 seats or fewer) and 1220 mm where stepped with seating on both sides (915 mm if serving 50 seats or fewer), at least two exits (three above 500 occupants, four above 1000), at least 305 mm clear row width (NFPA 101-2024 12.2.5.8.3, 12.2.5.7.2) and sprinklers where the aggregate assembly occupant load exceeds 300 (12.3.5.2; exceptions in 12.3.5.3).

Assembly Occupancy

  • Assembly occupancy: a gathering of 50 or more persons (NFPA 101-2024 6.1.2.1); NFPA 101 defines no subclasses, the A-1…A-5 letter codes belong to the IBC
  • Cinema auditorium: theater-type seating in rows; egress capacity per NFPA 101-2024 Table 12.2.3.2 (12.2.3.1)

Egress Width

  • Stair width per seat: 7.6 mm (NFPA 101-2024 Table 12.2.3.2)
  • Door width per person: 5.6 mm per seat for theater-type seating (NFPA 101-2024 Table 12.2.3.2)
  • Number of exits: at least two; three above 500 occupants, four above 1000 (NFPA 101-2024 7.4.1)
  • Dead-end: Max 6 m
  • Travel distance: 76 m sprinklered

Seat Layout

  • Aisle width: level or ramped with seating on both sides 1065 mm; stepped with seating on both sides 1220 mm (915 mm for either if serving 50 seats or fewer); seating on one side only 915 mm (12.2.5.8.3)
  • Seats per row: max 100 with aisles at both ends; with an aisle at one end only, max 9.1 m travel from any seat to the aisle (NFPA 101-2024 12.2.5.7.5, 12.2.5.7.6)
  • Row clear width: min 305 mm; +7.6 mm per seat over 14 with aisles at both ends (need not exceed 560 mm), +15 mm per seat over 7 with an aisle at one end (NFPA 101-2024 12.2.5.7.2, 12.2.5.7.5.1, 12.2.5.7.6.1)
  • Upholstered seating: newly introduced upholstered furniture must resist cigarette ignition (NFPA 101-2024 10.3.2.1)

Projection Booth

  • Laser 15 kW: IEC 60825 Class 4
  • Film type: where cellulose nitrate film is used, the projection room must comply with NFPA 40 (NFPA 101-2024 12.4.8.2)
  • Ventilation: adequate supply air; lamp exhaust of each projector goes directly outside and is not connected to any other exhaust or return-air system (12.4.8.8, 12.4.8.9)
  • Room: permanent construction consistent with the building construction type; at least 7.4 m² for one machine plus 3.7 m² per additional machine; ceiling at least 2285 mm (12.4.8.4, 12.4.8.5)
  • Projection ports: total area at most 25 percent of the wall between room and auditorium; openings closed with glass or other approved material (12.4.8.7)

Turkey Cinemas

  • Mall multiplex: 12 halls
  • IMAX auditorium: 30 m screen
  • Large mall multiplex: 15 halls
  • Historic cinema building: restoration
  • Pandemic 2020-22: Closures

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 101, NFPA 13, IBC Chapter 10, CAL 133, ADA. NFPA 101 Life Safety Code.