The fire pump matters — but the controller matters just as much. A badly configured control sequence leads to unnecessary pump runs, pressure fluctuation or, in the worst case, no start at all during a fire. NFPA 20 Chapter 10 defines controller requirements in detail. This article outlines the typical architecture of electric, diesel, and jockey controllers.

Three Controller Types

  • Electric fire pump controller: starts the electric main pump and manages the generator connection through the ATS.
  • Diesel fire pump controller: cranks the diesel engine and supervises two separate battery banks (FM DS 3-7 2.4.24.1 also requires two separate starting batteries per engine).
  • Jockey pump controller: starts and stops the jockey pump automatically.

Pressure Sensing

Controllers read system pressure via a pressure sensor or pressure switch. FM DS 3-7 2.4.11.1 requires each pump (including the jockey) to have its own sensing line. NFPA 20 expects:

  • Adjustable start/stop setpoints
  • Audible and visual signal on an electronic pressure sensor signal fault (10.5.2.1.3.2)
  • Pressure recording for at least 7 days (NFPA 20-2025 10.5.2.1.8.4)

Start Sequence

A typical staged start works like this:

  1. Pressure normal, system idle; pumps on standby.
  2. At a 10 psi (0.7 bar) drop the jockey starts and makes up small leaks.
  3. When pressure falls 10 psi (0.7 bar) below the jockey start point, the main pump starts (NFPA 20 Annex A.14.2.6, fire pump settings). FM DS 3-7 2.4.11.6 recommends that the fire pump starts 5–10 psi below the jockey start point.
  4. Electric pump first; if it cannot restore pressure, the diesel pump starts at its own setpoint 10 psi lower (10 psi decrements for each additional pump, FM DS 3-7 2.4.11.6). The ATS does not switch between pumps — it switches the electric pump's power sources.
  5. Stop: primarily manual. NFPA 20-2025 permits automatic shutdown only during automatic testing or where approved by the AHJ (10.5.4.2); FM DS 3-7 2.4.10.1 calls for manual stopping.

ATS (Automatic Transfer Switch)

On electric pumps, the ATS transfers automatically between two power sources:

  • Primary: utility power
  • Secondary: generator or a second utility feed

Each fire pump must have its own dedicated transfer switch (NFPA 20 10.8.2.3); the building's general ATS does not serve this purpose. In the arrangement with an individually listed transfer switch, a delayed-transition switch has a maximum delay time of 3 seconds (10.8.2.2(7)).

Monitoring Signals

Where the fire pump must be monitored, the controller sends the following signals to the fire alarm panel (NFPA 72 23.8.5.9: pump running may be an alarm or supervisory signal, the others are supervisory):

  • Pump running (run)
  • Pump fail (supervisory)
  • Power loss (supervisory)
  • Controller switch in manual (supervisory)
  • Phase reversal (electric only)

Diesel-Specific Rules

  • Two separate battery banks; if one is out of service, the controller must raise a supervisory alarm.
  • Fuel level below 67% triggers a supervisory alarm.
  • Weekly automatic run test, with the diesel pump running at least 30 minutes (NFPA 25-2026 8.3.2.4); FM DS 3-7 2.4.9.1 requires personnel to attend it.
  • Engine coolant temperature is monitored continuously.

Common Issues (Turkey)

  1. Jockey runs constantly: a small system leak goes unnoticed by maintenance and the jockey eventually burns out.
  2. Main pump set to auto-stop: NFPA 20-2025 permits automatic shutdown only during automatic testing or where approved by the AHJ (10.5.4.2); FM DS 3-7 2.4.10.1 calls for manual stopping.
  3. ATS never tested: NFPA 25-2026 8.3.6.2 requires transfer switches to be tested and exercised routinely; if that is skipped, the first serious outage reveals that the pump does not start.
  4. Phase reversal alarm disabled: with phases swapped the pump runs backwards; some sites disable this alarm "to stop the noise", which is a very dangerous habit.

Conclusion

The controller is as critical as the pump. Even with flawless mechanical work, one mistake on the electrical side means the system does not run in a fire. NFPA 20 Chapter 10 rules on start-stop, ATS, and monitoring are minimums; don't skip them in design.

Pump controller schedule in MEP Calc

Weekly test calendar, ATS check, alarm setpoints, and log book.

View on App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

Core reference: NFPA 20 Chapter 10 - Controllers, FM Global DS 3-7 Fire Protection Pumps (2.4.9–2.4.11, 2.4.24). Original NFPA post: NFPA Today - Fire Pump Controllers.