With 1,700 MW of installed geothermal capacity, Turkey ranks fourth in the world; the backbone of the sector is two large plants of 242 MW and 162 MW. Geothermal fluid at 200–250 °C carries CO2, H2S and CH4, so what comes out of the wellhead is not just steam but a toxic and flammable mixture. NFPA 850 Chapter 15 gives recommendations for geothermal plants (direct steam, flash and binary); for binary plants the main hazards listed include release of a flammable fluid above its boiling point, pool fires and combustible cooling tower construction (15.4.2).

Geothermal Fluid Composition

  • CO2: 90% of the non-condensable gases
  • H2S: 100–500 ppm — toxic; exposure limits are critical
  • CH4: 1–5% methane
  • Temperature: 180–250 °C at the wellhead
  • Wellhead pressure: 10–25 bar

Flash Separator Safety

  • First-stage flash: 180 °C, 10 bar
  • Second-stage flash: 120 °C, 2 bar
  • Demister: Captures silica particles before they reach the turbine
  • Emergency vent: Upward-discharging flare line

Risks of Pentane ORC Units

  • Binary cycle: Working fluid is n-pentane or isobutane
  • Flash point: -40 °C — Class IA
  • LEL: 1.5% — a low explosive threshold
  • Layout: Components containing flammable working fluid are recommended to be located outdoors or in enclosures ventilated to keep the concentration below 25 percent of the LFL (15.3.2.2)

H2S Abatement

  • LO-CAT: Converts H2S to elemental sulfur (redox process)
  • Stretford: Older-generation technology, not preferred in new plants
  • Reinjection: Non-condensable gas and water are pumped back into the reservoir
  • Monitoring: 1 ppm TLV-TWA threshold (ACGIH)

Field Examples and Lessons Learned

  • Largest plant: 242 MW
  • Second-largest plant: 162 MW
  • A mid-size plant: 47 MW
  • Pentane leak: a binary plant in the US — a reference event for binary cycles
  • The Geysers (California): 1,517 MW, the world’s largest geothermal field

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 850, NFPA 497, API 521, ISO 17776, IEC 60079-10-1. NFPA 850 Fire Protection for Electric Generating Plants.