With 1,700 MW of installed geothermal capacity, Turkey ranks fourth in the world; the backbone of the sector is two large plants of 242 MW and 162 MW. Geothermal fluid at 200–250 °C carries CO2, H2S and CH4, so what comes out of the wellhead is not just steam but a toxic and flammable mixture. NFPA 850 Chapter 15 gives recommendations for geothermal plants (direct steam, flash and binary); for binary plants the main hazards listed include release of a flammable fluid above its boiling point, pool fires and combustible cooling tower construction (15.4.2).
Geothermal Fluid Composition
- CO2: 90% of the non-condensable gases
- H2S: 100–500 ppm — toxic; exposure limits are critical
- CH4: 1–5% methane
- Temperature: 180–250 °C at the wellhead
- Wellhead pressure: 10–25 bar
Flash Separator Safety
- First-stage flash: 180 °C, 10 bar
- Second-stage flash: 120 °C, 2 bar
- Demister: Captures silica particles before they reach the turbine
- Emergency vent: Upward-discharging flare line
Risks of Pentane ORC Units
- Binary cycle: Working fluid is n-pentane or isobutane
- Flash point: -40 °C — Class IA
- LEL: 1.5% — a low explosive threshold
- Layout: Components containing flammable working fluid are recommended to be located outdoors or in enclosures ventilated to keep the concentration below 25 percent of the LFL (15.3.2.2)
H2S Abatement
- LO-CAT: Converts H2S to elemental sulfur (redox process)
- Stretford: Older-generation technology, not preferred in new plants
- Reinjection: Non-condensable gas and water are pumped back into the reservoir
- Monitoring: 1 ppm TLV-TWA threshold (ACGIH)
Field Examples and Lessons Learned
- Largest plant: 242 MW
- Second-largest plant: 162 MW
- A mid-size plant: 47 MW
- Pentane leak: a binary plant in the US — a reference event for binary cycles
- The Geysers (California): 1,517 MW, the world’s largest geothermal field

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 850, NFPA 497, API 521, ISO 17776, IEC 60079-10-1. NFPA 850 Fire Protection for Electric Generating Plants.