Modern greenhouses use polycarbonate or PE film covers with propane/LPG heaters plus CO₂ enrichment. Heater clearances to the cover and LPG container distances to the structure need separate attention.
Fire Load
- PE film: drips and spreads fast once ignited
- Polycarbonate: tends to self-extinguish
- Glass: non-combustible, but breaks and falls at high temperature
- Wood frame: one of the main fire loads in the greenhouse
- Plants: light, wet load; dry leaves on mature plants raise the risk
Heater Risk
- LPG container: the distance of an aboveground container to buildings and adjoining property depends on water capacity: 3 m (10 ft) for 0.5-1.9 m³, 7.6 m (25 ft) for 1.9-7.6 m³, 15 m (50 ft) for 7.6-114 m³, larger for bigger containers; for containers under 0.5 m³ see the sub-clauses of the table (NFPA 1-2018 Table 69.3.5.1.1)
- Biomass boiler: NFPA 85 applies at a heat input of 3.7 MW (12.5 million Btu/h) or more (Chapter 10 for wood-fired stokers); smaller boilers are outside NFPA 85
- Cogeneration: gas engine exhaust used as CO₂ source, with double checks
CO₂ Enrichment
- Source: flue gas recovery or liquid CO₂
- OSHA TLV: 5,000 ppm TWA

Greenhouses with MEP Calc
MEP Calc sizes greenhouse ventilation 30 percent ridge vent, pad fan 1.2 m/s, CO2 1,500 ppm fertigation and NFPA 1 LPG tank setback 3 m.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.