Turkey's city hospitals are huge complexes with thousands of beds, and facilities of this size still use ethylene oxide (EO) to sterilize surgical instruments. Pure (100%) EO is an explosive gas with a lower explosive limit (LEL) of only 3% (NFPA 497 table). The critical point is that it has practically no upper explosive limit, because the gas can decompose explosively even without oxygen. For this reason NFPA 55 Chapter 14 therefore requires Class I Division 2 Group B electrical classification for the sterilizer room, dispensing area, container storage and aeration rooms (Division 1 inside the sterilizer vessel), automatic sprinklers in facilities using ethylene oxide and an NFPA 16 deluge system in ethylene oxide storage areas (14.7.1, 14.12.1). Ethylene oxide in chambers of 10 scf (0.283 Nm³) or less in volume, or in containers holding 200 g or less, is outside the scope (1.1.2(13)).
Ethylene Oxide Properties
- Flash point: -20 °C; Class IA
- Explosive limits (LEL–UEL): 3–100% — an unusually wide range among gases
- Autoignition temperature: 429 °C
- Molar mass: 44 g/mol; heavier than air
- Exposure limit (TLV): 1 ppm TWA — classified as a carcinogen
NFPA 55 Classification
- Sterilizer room: Class I Division 2 electrical classification
- Container storage area: Class I Division 2 Group B; inside the sterilizer vessel Class I Division 1 (14.7.1)
- Ventilation: continuous mechanical exhaust in the dispensing area of at least 1 scf/min·ft² (about 0.3 Nm³/min·m²) (14.5.1.4)
- Gas detection: sterilizer areas are monitored continuously; an audible and visual warning is given at 25 percent of the lower flammable limit and the supply at the containers is shut off automatically above it (14.6.3)
Sterilization Cycle
- Temperature: 37–63 °C, depending on the load
- Relative humidity: 40–80%
- Gas concentration: 450–1,200 mg/L
- Exposure time: 1–6 h, depending on the load type
- Aeration: 12–24 h to remove residual gas
Fire Protection
- Sprinklers: facilities using ethylene oxide are protected by automatic sprinklers; storage areas need an NFPA 16 deluge system (14.12.1)
- Abatement: Catalytic oxidation unit
- Scrubber: Wet scrubbing for EPA NESHAP compliance
- Nitrogen purge: Removes oxygen from the line during cylinder changes
Incidents and Examples
- Sterigenics Willowbrook 2019: Facility shut down over emissions
- A sterilization facility: Area evacuation after an EO leak
- A city hospital: 2,680 beds, high daily sterilization load
- The largest city hospital in Turkey: 3,711 beds
- FDA approach: Hydrogen peroxide (H2O2) plasma recommended as an alternative to EO

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 55, NFPA 99, ANSI AAMI ST41, EPA NESHAP, FDA 510(k). NFPA 55 Compressed Gases and Cryogenic Fluids.