An atrium (internal courtyard, lobby, shopping mall) traps smoke due to its large volume. Long evacuation times let smoke fall into sleeping areas. NFPA 92 (Smoke Control Systems) defines smoke reservoirs, exhaust flow, makeup air, pressurization and CFD simulation requirements.
Smoke Reservoir
- Purpose: separate smoke layer at top from clean air below
- Depth: at least 20 percent of the floor-to-ceiling height, or per engineering analysis (NFPA 92 clause 4.5.1.3)
- Smoke curtain: auto-deploying
- Minimum clear layer: by engineering analysis, the smoke layer interface is kept above the highest unprotected opening to adjoining spaces, or 6 ft (1.83 m) above the highest exit-access floor open to the atrium, for 1.5 times the calculated egress time or 20 minutes, whichever is greater (NFPA 101-2024 8.6.7)
Exhaust Flow Calculation
NFPA 92 clause 5.5.1.1, axisymmetric plume:
- m = 0.071 × Qc^(1/3) × z^(5/3) + 0.0018 × Qc (z > zl); for z ≤ zl, m = 0.032 × Qc^(3/5) × z
- Qc = convective heat release rate (kW), taken as 0.7 times the total HRR (clause 5.5.1.4)
- z = height of the smoke layer interface above the base of the fire (m)
- zl = limiting elevation = 0.166 × Qc^(2/5) (m)
- m = plume mass flow (kg/s)
Example: for a 5 MW fire (Q = 5000 kW), Qc = 0.7 × 5000 = 3500 kW and zl = 0.166 × 3500^(2/5) ≈ 4.3 m. Flow grows with z^(5/3): keeping the smoke layer interface 15 m above the floor of a 25 m atrium (z > zl) gives m = 0.071 × 3500^(1/3) × 15^(5/3) + 0.0018 × 3500 ≈ 105 kg/s. The smoke temperature is Ts = To + Qc/(m·cp) ≈ 20 + 3500/105 ≈ 53 °C (cp = 1.0 kJ/kg·K, To = 20 °C assumed), so the density is about 1.08 kg/m3 and the volume flow about 97 m3/s, roughly 350,000 m3/h of exhaust (clause 5.5.5). At that scale the fan room and shafts must be coordinated with the architect at the earliest stage.
Makeup Air
- Flow: mechanical makeup air must be less than the mechanical exhaust (NFPA 92 clause 4.4.4.1.2)
- Velocity: at most 1.02 m/s (200 ft/min) where makeup air can contact the plume, unless a higher velocity is supported by engineering analysis; supply points below the smoke layer interface (clauses 4.4.4.1.1, 4.4.4.1.4)
- Source: atrium floor level, doors and grilles
- Temperature: conditioned outdoor air
Pressurization
- Smoke barrier: minimum design pressure difference 12.5 Pa (0.05 in. w.g.) in sprinklered spaces; 25 Pa (0.10 in. w.g.) in nonsprinklered spaces at a 2.7 m ceiling, rising with ceiling height (NFPA 92 Table 4.4.2.1.1)
- Test: pressure maintained with doors open
- Control: the pressure difference must hold under the design wind and stack-effect conditions
CFD Validation
- FDS (Fire Dynamics Simulator, NIST) free
- Pathfinder + Pyrosim egress simulation
- Verify the smoke layer interface stays above the highest unprotected opening to adjoining spaces (or 1.83 m above the highest floor level of exit access open to the atrium) for 1.5 times the calculated egress time or 20 min, whichever is greater (NFPA 101-2024 8.6.7(5))
- Sprinkler activation time, smoke spread
- AHJ may request CFD (IBC Sec 909, NFPA 92 Annex C)

Atrium smoke with MEP Calc
MEP Calc runs NFPA 92 plume mass flow, exhaust fan sizing, makeup air and pressurization for atrium smoke control.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.