Hypermarkets and large retail chains come with rack warehouses in addition to 10,000–20,000 m² of sales floor. NFPA 13 ESFR (early suppression fast-response) sprinklers are one option: within the table limits, K25.2 (K360) sprinklers largely eliminate the need for in-rack sprinklers. For Class I–IV commodities, however, ESFR is limited to 12.2 m (40 ft) of storage under a 13.7 m (45 ft) ceiling; racks taller than 12.2 m need a different solution.

Commodity Classes (NFPA 13 Section 20.4)

  • Class I: Noncombustible products such as metal and glass, on pallets, in single-layer corrugated cartons or shrink-wrapped
  • Class II: Noncombustible products in wooden crates/boxes or multiple-layered corrugated cartons
  • Class III: Products of wood, paper, natural fibers (textiles) and Group C plastics
  • Class IV: Products made of Group B plastics or containing roughly 5–15% by weight of Group A plastics
  • Group A plastics: For example expanded polystyrene (EPS); high fire load

ESFR Design

  • K25.2 (K360): From Q = K√P, 150 gpm (570 L/min) is reached at about 36 psi (2.5 bar); the actual minimum pressure is read from Table 23.3.1
  • K14.0 (K200) pendent: For Class I–IV, 50 psi (3.4 bar) minimum operating pressure up to a 30 ft (9.1 m) ceiling and 75 psi (5.2 bar) at a 35 ft (10.7 m) ceiling; Table 23.3.1 gives no K14.0 option at 40 ft (12.2 m) or higher ceilings
  • Maximum storage height: 40 ft (12.2 m) for Class I–IV and cartoned nonexpanded Group A plastics; 35 ft (10.7 m) for the other Group A plastics with ceiling-only options
  • Ceiling height: 45 ft (13.7 m) maximum
  • 12 sprinklers: Calculated over the 12 hydraulically most demanding sprinklers

Pump Calculation

  • Total flow: 12 × 570 L/min ≈ 6,800 L/min (1,800 gpm)
  • Hose allowance: 250 gpm (950 L/min) per NFPA 13 Table 20.15.2.6
  • Duration: 60 min
  • Tank: (6,800 + 950) × 60 ≈ 465 m³ (122,800 gal)
  • Pump: 7,750 L/min (2,000 gpm), 15 bar (218 psi)

In-Rack Alternative

  • Face sprinklers: In-rack design criteria are read from the NFPA 13 Chapter 25 tables; face sprinklers sit at least 75 mm from rack uprights and no more than 450 mm from the aisle face of storage (25.1.7.8)
  • Transverse flue: Nominal 6 in (150 mm) between loads and at rack uprights (NFPA 13 20.6.2.2)
  • Longitudinal flue: Not required in double-row racks up to 25 ft (7.6 m); nominal 6 in (150 mm) above 25 ft (NFPA 13 20.6.2.1.1–20.6.2.1.2)
  • Plastic commodities: Face and longitudinal in-rack sprinklers may be required
  • Class I–III: Ceiling-only ESFR is sufficient; no in-rack sprinklers needed

Examples from Turkey

  • Hypermarket chains: ESFR installed in many stores
  • Wholesale retail logistics: An 80,000 m² warehouse
  • Chain-store regional warehouses: ESFR K25.2 (K360) as the standard solution
  • E-commerce logistics centers: Warehouses on the scale of 50,000 m²

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 13, FM DS 8-9, UL 199. NFPA 13 Standard for Sprinkler Systems.