Malls of 85,000-175,000 m2 host Turkey's biggest mall atriums. A 4-storey 25 m atrium sees 80,000 daily visitors. NFPA 92 sets the framework for atrium smoke management design: design fire, plume and layer calculation, exhaust fans and makeup air. The level at which the smoke layer interface must be held in an atrium, and for how long, is set in NFPA 101, 8.6.7.

Atrium Geometry

  • Height: 20-40 m typical
  • Open balcony: 4-6 storeys
  • Shop opening: Open to atrium
  • Glass roof: Skylight smoke vent
  • Foot traffic: 80,000/day peak

NFPA 92 Calc

  • Smoke layer: z = height of the smoke layer interface
  • Plume mass flow (sizes the exhaust): above the flame height m = 0.071 Qc^1/3 z^5/3 + 0.0018 Qc (kg/s; Qc convective heat release rate in kW; z in m) (NFPA 92-2018, 5.5.1.1)
  • Makeup air: velocity must not exceed 1.02 m/s (200 ft/min) where it could contact the plume, unless a higher velocity is supported by engineering analysis (NFPA 92-2018, 4.4.4.1.4)
  • Egress time: the smoke layer interface must stay above the highest unprotected opening to adjoining spaces, or 1.8 m above the highest floor level of exit access open to the atrium, for 1.5 times the calculated egress time or 20 minutes, whichever is greater (NFPA 101-2024, 8.6.7(5))

CFD FDS

  • Fire Dynamics Simulator: NIST's open-source CFD tool
  • Design HRR: 5 MW retail
  • Steady state: 20 min run
  • ASET vs RSET: Safe egress

Exhaust Fan

  • Temperature rating: fans and equipment suitable for the temperatures they may be exposed to (NFPA 92-2018, 6.6.3)
  • Motor out of flow: Heat isolation
  • Control: FSCS (firefighter's smoke control station)

Turkey Malls

  • Largest examples: 155,000-175,000 m2
  • Mid-to-large malls: 85,000-103,000 m2
  • A mall project: smoke control design reference

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 92, NFPA 101, IBC 909, NIST FDS 6. NFPA 92 Smoke Control Systems.