Marinas have high fuel loads from fiberglass boats, gasoline/diesel fueling stations and wooden piers. NFPA 303 (Marinas and Boatyards) defines pier sprinkler design, fuel dispenser separation, and yacht-interior detection. A burning fiberglass boat can sink in 20 minutes — the response window is tight.
Pier Sprinkler
- NFPA 303 4.4: Overhead sprinkler required for piers >8 m or 8 boats
- Design density: 8 L/min/m2 (0.2 gpm/ft2)
- Water source: Seawater pump (corrosion-resistant bronze body)
- Hydrant: One per 45 m of pier length
Fuel Dispenser
- Separation: Dispenser to building minimum 15 m
- Electrical: Class I Div 2, 5.5 m radius
- Emergency shutoff: At dispenser + remote at 7.6 m distance
- Spill control: Absorbent kit at each dispenser, foam boom for water spills
Yacht Interior Detection
For enclosed cabin boats:
- Engine room: CO2 or HFC automatic suppression
- Cabin: smoke detector (NFPA 72)
- Galley: heat detector (prevents false alarms at night)
- LPG galley: solenoid shutoff + LEL sensor
Wooden Pier Fires
Creosote-treated wood piers burn rapidly. Mitigations:
- Prefer FRP (Fiber Reinforced Plastic) or steel pier
- FR coating on wood pier (poor durability)
- Fire alarm horn at pier head
- Marina manager 911 + coast guard protocol

MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 303, NFPA 302 (Pleasure Craft), NFPA 72, USCG Marina Safety Guide. NFPA 303 Marinas standard.