Metro (subway) stations operate fire-protection equipment under harsh conditions (vibration, dust, humidity, 24/7). NFPA 130 applies to fixed guideway systems, and NFPA 25 governs ITM. The intervals below come from the relevant standards.
Weekly Inspections and Tests
- Diesel pump: 30-min no-flow test
- Jockey pump: running pressure check
- Pump room: heat adequate, ventilating louvers free to operate, piping free of leaks, controller power-on pilot light illuminated, vertical motor oil level acceptable (NFPA 25-2026 8.2.2)
- Sprinkler valve: all valves inspected weekly; monthly where locked or supervised, quarterly where electrically supervised (NFPA 25-2026 13.3.2.1)
Monthly Tests
- Electric pump: no-flow test, minimum 10 min run; weekly for pumps serving buildings beyond fire department pumping capacity, limited service controllers, vertical turbine pumps or suction from ground-level tanks, otherwise (and with a redundant pump) monthly (NFPA 25-2026 8.3.1.2, 8.3.2.3)
- Portable extinguisher: inspected monthly (at intervals not exceeding 31 days): in place, safety seals and tamper indicators intact, no obvious physical damage (NFPA 10-2018 7.2.1.2, 7.2.2)
- Emergency light: monthly functional test of at least 30 seconds (3 to 5 weeks between tests); battery-powered systems also annually for at least 1.5 hours (NFPA 101-2024 7.9.3.1.1)
Annual Tests
- Sprinkler: visual inspection from floor level (NFPA 25-2026 5.2.1.1)
- Fire alarm: functional test of system smoke detectors annually (NFPA 72-2022 Table 14.4.3.2)
- PA system: operation check of loudspeaker audible notification appliances annually (NFPA 72-2022 Table 14.4.3.2)
- Smoke control system: tested at least every 6 months for dedicated systems and at least annually for others (NFPA 92-2018 8.6.1)
- Fire and combination fire/smoke dampers: tested and inspected 1 year after acceptance, then every 4 years (every 6 years in buildings containing a hospital) (NFPA 80-2019 19.5.1)
- Hydrant: opened fully and flowed for at least 1 minute annually (NFPA 25-2026 7.3.2)
- Standpipe flow test: every 5 years on automatic standpipe systems, flowing the standpipe demand at the hydraulically most remote hose valve outlet (NFPA 25-2026 6.3.1.1)
- Hydrostatic test: every 5 years on manual standpipe systems and semiautomatic dry standpipe systems (including FDC piping), at least 200 psi (13.8 bar) for 2 hours, or maximum pressure + 50 psi where maximum exceeds 150 psi; manual wet standpipes in combined sprinkler/standpipe systems exempt; FDC piping to the check valve 150 psi (10 bar) for 2 hours every 5 years (NFPA 25-2026 6.3.2.1, 13.8.5)
- Annual pump flow test: at no-flow (churn), rated flow and 150 percent of rated flow; electric pumps run at least 10 min, diesel pumps at least 30 min before shutdown (NFPA 25-2026 8.3.3.1, 8.3.3.10)
Records
- Record-keeping: records are made of all inspections, tests and maintenance, showing the activity performed, the organization that performed it, the required frequency, the results and date, and the name and contact information of the qualified person (NFPA 25-2026 4.3.1, 4.3.2)

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 130, NFPA 25, NFPA 72, NFPA 10, NFPA 80, NFPA 92, NFPA 101, APTA-PR-E-RP-003, UIC IRS 70105. NFPA 130 Transit code.