The first two minutes of a fire are critical. Before sprinklers activate and before the fire department arrives, the only tool to knock down a small flame is the portable fire extinguisher. NFPA 10 details type, capacity, placement, and maintenance. A practical field guide below.

Fire Classes

  • Class A: Paper, wood, textile. Water, ABC dry chemical.
  • Class B: Flammable liquid (gasoline, solvent, oil). CO₂, BC dry, AFFF.
  • Class C: Electrical. CO₂, ABC dry; only types listed and labeled for Class C.
  • Class D: Metal (magnesium, lithium). Special dry chemical.
  • Class K: Cooking oil (kitchen). Wet chemical.

Rating System

The label (e.g., "4A:80B:C") gives per-class capacity:

  • A rating: relative Class A capacity (a 4-A unit extinguishes about twice the Class A fire of a 2-A unit)
  • B rating: relative Class B capacity (a 20-B unit extinguishes about twenty times the Class B fire of a 1-B unit)
  • C rating: Electrical safety (non-conductive)

Light hazard: minimum 2-A for a single extinguisher (Table 6.2.1.1).

Travel Distance

NFPA 10 maximum path to nearest extinguisher:

  • Class A Light Hazard: 75 ft (23 m)
  • Class A Ordinary Hazard: 75 ft (23 m)
  • Class A Extra Hazard: 75 ft (23 m)
  • Class B: 30 ft (9 m) or 50 ft (15 m) depending on hazard grade and B rating; light 5-B 9 m, 10-B 15 m; ordinary 10-B 9 m, 20-B 15 m; extra 40-B 9 m, 80-B 15 m
  • Class K: 30 ft (9 m)

Placement

  • Visible and accessible
  • Top of extinguisher ≤ 1.5 m from floor (≤ 18 kg)
  • Heavy (>18 kg): ≤ 1.07 m
  • Near exits (quick access + visibility)

Maintenance Frequency

  • Monthly visual: Pressure gauge, seal, physical damage. Non-certified staff can do it.
  • Annual service: Certified technician, external examination (internal examination too for some types).
  • 6-year service: Stored-pressure units needing a 12-year hydrostatic test are emptied and examined internally and externally.
  • Hydrostatic test: Cylinder pressure test every 5 or 12 years depending on type; units that fail are removed from service.

Common Problems in Turkey

  1. Expired units: 6- and 12-year overdue, still hanging.
  2. Gauge in red: Unnoticed for years.
  3. Behind desks: Unreachable.
  4. Only present at inspection: Moved back to storage after audit.

Conclusion

Extinguishers are cheap but life-saving. Right type, right place, proper maintenance — a big difference in the first two minutes.

Extinguisher schedule in MEP Calc

Per-building extinguisher map, monthly check reminders, 6/12-year service schedule.

View on App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

Core reference: NFPA 10 - Standard for Portable Fire Extinguishers. Original NFPA post: NFPA Today - Portable Extinguishers.