Most restaurant fires start at the fryer, grill, or range. Class K (vegetable-oil) fires: water doesn't extinguish, it explodes. NFPA 96 governs hoods, ducts, filters, and automatic suppression in commercial kitchens. This article summarises the field-level engineering.
What Is Class K?
Class K is cooking-oil fire:
- Water → flash steam + oil splash = explosive
- Even extinguished, oil stays hot — re-ignition
- Systems must be listed to UL 300 or equivalent, and portable extinguishers listed for Class K
Hood Design
NFPA 96 hood rules:
- Type I: Oil-bearing appliances (fryer, grill, range)
- Type II: Hot but grease-free (steam, oven) — outside NFPA 96
- Filter: UL 1046 listed baffle; easy-clean, 45° slope
Wet Chemical System
Automatic suppression:
- Fusible link or detector as required by the system listing; nozzle count and placement follow the listing and manufacturer instructions.
- Activation: fuel and heat-producing power shutoff + wet chemical discharge + alarm; the exhaust fan keeps running unless a listed ventilation component or the system design requires shutdown (NFPA 96 8.2.3.1, 10.4.1).
- At least one manual pull station in the means of egress or at a location acceptable to the AHJ (10.5.1.1).
- Post-discharge: professional recharge + hood cleaning.
Ducts and Exhaust
- Duct: carbon steel at least 1.52 mm (0.060 in.) or stainless steel at least 1.21 mm (0.048 in.) (7.5.1.1).
- Welded, leak-free joints.
- Horizontal runs: at least one 508 x 508 mm (20 x 20 in.) opening; where that is not possible, cleaning openings every 3.7 m (12 ft) (7.4.1).
- Continuous upward slope; reverse slope = grease pooling.
- Rooftop termination: at least 3 m (10 ft) horizontal clearance from adjacent buildings, property lines and air intakes (7.8.2.1).
Cleaning Schedule
NFPA 96 frequencies:
- Weekly: metal containers collecting grease drippings are inspected or emptied at least weekly (NFPA 96 11.6.16).
- Grease-buildup inspection of duct and fan by cooking type: solid fuel monthly, high volume quarterly, moderate volume semiannually, low volume annually (Table 11.4); clean when the deposit limit is exceeded
- Twice yearly: wet chemical system inspection (certified)
Common Issues in Turkey
- Wet chemical untested for 5 years: Pressure vessel may have leaked.
- No cleaning: 2 cm grease in duct — itself fuel.
- Restaurant conversion: Café turned kebab shop; hood never converted Type II → Type I.
Conclusion
Restaurant fires dominate the last decade's reports — most preventable. Running a kitchen without NFPA 96 + wet chemical + regular cleaning is Russian roulette. Conscious design and certified maintenance keep the kitchen safe 24/7.

Kitchen suppression schedule in MEP Calc
NFPA 96 cleaning program, wet chemical test reminders, and restaurant checklist.
View on App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreCore references: NFPA 96, NFPA 10 (Class K). Original NFPA post: NFPA Today - Kitchen Fires.