Helidecks are helicopter landing areas on offshore platforms. A Jet A fuel helicopter crash poses huge fire risk. NFPA 418 (Standard for Heliports) gives fixed foam system rules for rooftop landing pads; for offshore heliports Chapter 8 sets only general provisions on plan approval, fire-fighting access and deck pitch. Details of the Deck Integrated Firefighting System (DIFFS) and foam monitors are found in other documents (for example CAP 437, UK Civil Aviation). DIFFS became mandatory after the 2009 Cougar crash in Newfoundland.
DIFFS Deck Integrated Foam
- Design density: NFPA 418 requires 4.1 L/min/m2 (0.10 gpm/ft2) of AFFF for rooftop landing pads (5.7.1.2); for offshore helidecks the standard gives no foam density (Chapter 8)
- Deck area: 25 m D-value for S-92
- Nozzle: flush-mount recessed in deck
- Activation: under NFPA 418 the fixed discharge system on a rooftop pad is activated manually, with stations at each egress point and where the pad can be viewed from the building (5.7.2.6)
- Duration: 10 min (NFPA 418 5.7.2.3, rooftop pad fixed system)
Fixed Foam Monitor
- Number: NFPA 418 5.7.2.4: fixed nozzles around the perimeter, two or more oscillating monitors/nozzles, or in-deck nozzles
- Remote control: joystick + auto sweep
- Fluorine-free foam (F3): 2026 transition per PFAS restrictions
CAP 437 vs ICAO
- CAP 437 (UK): strict - DIFFS mandatory
- ICAO Annex 14: minimum - monitors sufficient
- NFPA 418: US - monitor + deck hybrid
- API RP 14G: US offshore - references NFPA 418
- Class H-1 to H-3: classified by overall helicopter length: H-1 < 15.2 m (50 ft), H-2 15.2-24.4 m, H-3 24.4-36.6 m (NFPA 418 Table 5.7.3.1)
Firewater Ring Main
- Seawater: firewater pump (jockey + main + diesel backup)
- Ring main: platform perimeter, two-arm feed
- Dry riser: helideck + accommodation
Helideck Drainage
- Slope: NFPA 418 gives 0.5-2 percent for rooftop pads (5.3); for offshore helidecks liquids must not collect or spill onto accommodation or working spaces (8.3)
- Fuel slop tank: collection tank - oil-water separator
- Fresh water rinse: reduces salt corrosion after seawater

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 418, CAP 437, ICAO Annex 14 Vol II, API RP 14G, API RP 2218. NFPA 418 Heliports standard.