A Fluid Catalytic Cracking (FCC) unit turns heavy hydrocarbon residue into gasoline. The riser runs at 520 °C, the regenerator at 720 °C and 4–5 bar. The 2005 Texas City explosion killed 15 people. NFPA 30, API 2510 and API RP 752 cover FCC fire protection.

FCC Process

  • Feed: Vacuum gas oil (VGO) at 350 °C
  • Catalyst: Zeolite, 5–100 micron particles
  • Riser: 520 °C, 2–3 s contact time
  • Regenerator: 720 °C, coke burned off the catalyst
  • Capacity: 40,000–100,000 bpd

Riser and Catalyst Risk

  • Erosion: Catalyst wears the metal, especially at elbows
  • Feed pipe hot spot: Locally up to 750 °C, damaging the internal lining
  • Expander: Turbine driven by 720 °C flue gas
  • Slurry pump: Seal leaks are a classic fire source
  • Hot rotating equipment: Steam curtain around it

Water Spray NFPA 15

  • Vessel exposure: 10.2 L/min/m²
  • Structural steel: over the wetted area, 4.1 L/min/m² (0.10 gpm/ft²) for horizontal structural steel and 10.2 L/min/m² (0.25 gpm/ft²) for vertical steel such as columns (NFPA 15 7.4.3.1, 7.4.3.4)

Texas City 2005 Lessons

  • Incident: Vapor cloud explosion after a column overfill in the isomerization unit
  • Dead: 15, injured 180
  • Cause: Trailer siting
  • CSB report: Safety culture
  • MOC: Management of Change mandatory

Turkish Refinery FCC

  • A refinery: FCC, 40,000 bpd
  • Another refinery: Gasoline production via Unit 2
  • A new refinery: Commissioned in recent years
  • BYKHY Annex 12: Storage of flammable and combustible liquids, with minimum safety distances for above-ground (12/C) and underground (12/Ç) tanks; refineries are industrial occupancies under Article 14
  • SEVESO III: Refineries with FCC units are upper-tier establishments

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 30, NFPA 15, API 2510, API RP 752, CSB Texas City. NFPA 30 Flammable and Combustible Liquids.