Very large crude and gasoline tanks in refineries mostly use floating roofs to reduce evaporation losses and the risk of a flammable vapor space. Lightning or static discharge ignites rim-seal fires. NFPA 11 defines seal area protection and full surface protection for floating-roof tanks (NFPA 11-2024, 5.3.1.1), and does not permit subsurface or semi-subsurface injection on open-top or covered floating-roof tanks (5.3.3.1). Buncefield 2005 (UK) and Jaipur 2009 (India) are the major reference accidents.

Tank Types

  • Open-top floating roof (FRT): roof rides directly on the liquid
  • Internal floating roof (IFRT): fixed outer roof plus internal floating roof
  • Fixed roof: mostly small tanks and low vapor-pressure products
  • Rim seal: primary seal (mechanical shoe or tube seal) plus secondary seal; NFPA 11 Table 5.3.5.3.1 covers each seal arrangement separately
  • Vapor retention: low for floating roofs, high for fixed roofs

Rim-Seal Fire

  • Cause: lightning, static, welding/grinding sparks
  • Area: narrow annular seal area
  • Circumference: 80 m diameter tank = 251 m
  • Foam application rate: 12.2 L/min/m² (0.3 gpm/ft²) with top-of-seal fixed discharge outlets (NFPA 11-2024 Table 5.3.5.3.1)
  • Duration: 20 min (same table); where the application rate is higher than the table minimum, the time may be reduced proportionately but not below 70% (5.3.5.3.4)
  • Maximum spacing between outlets: 12.2 m (40 ft) with a 305 mm (12 in.) foam dam, 24.4 m (80 ft) with a 600 mm (24 in.) foam dam (Table 5.3.5.3.1)

NFPA 11 Foam Types

  • AFFF (aqueous film-forming foam): fluorinated surfactants form a fluid aqueous film that suppresses hydrocarbon vapors (NFPA 11 3.3.11.2)
  • AR-AFFF (alcohol-resistant): required for polar solvents (methanol, ethanol)
  • FP (fluoroprotein): protein-based concentrate with a synthetic fluorinated surfactant additive (NFPA 11 3.3.11.5)
  • F3 (fluorine-free): the 2026 transition direction due to PFAS restrictions
  • High-expansion: for LNG fires (NFPA 11 7.3 lists only high-expansion foam for LNG) and vapor dispersion control of LNG and ammonia spills (Annex C, informative)

Full-Surface Fire

80 m diameter tank, full surface fire. NFPA 11 Section 5.3 gives seal area criteria for open-top floating-roof tanks; this full-surface example borrows the monitor criteria for fixed-roof tanks (Table 5.2.4.2.2):

  • Area: A = π × 40² = 5,027 m²
  • Application rate: 6.5 L/min/m² → 32,670 L/min
  • Duration: 65 min (Table 5.2.4.2.2: flash point below 38 °C and crude oil)
  • Wind and ambient losses: per 5.2.4.2.1.2, a minimum additional factor of 1.5 applies to monitor design; the quantities below exclude this factor
  • Foam concentrate: 3% → 980 L/min × 65 = 63.7 m³
  • Foam solution: 32,670 × 65 ≈ 2,124 m³ (about 2,060 m³ of it water)

Buncefield 2005 Lesson

  • Event: gasoline tank overfill followed by a vapor cloud explosion
  • Damage: very severe explosion, 43 injured
  • Cause: defective tank level gauge, no independent overfill protection layer
  • Lesson: independent, high-integrity high-level alarm
  • Process safety: API 2350 overfill prevention

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 11, NFPA 30, API 2350, API 650, EEMUA 159, HSE Buncefield Report. NFPA 11 Low-/Medium-/High-Expansion Foam.