Vinyl chloride monomer (VCM, CH2=CHCl) is a flammable carcinogenic gas/liquid used in PVC manufacture. LEL 3.6%, UEL 33%, flash point −78 °C. Closed tank leaks quickly form explosive atmospheres. ATEX 2014/34/EU governs the design of VCM tanks, transfer pumps and piping; NFPA 497 lists vinyl chloride as a gas and NFPA 30 does not apply to liquefied gases. Explosion-protected (Ex) equipment and hazardous-area classification are required.
VCM Properties
- Molecular weight: 62.5 g/mol
- Boiling point: −13.4 °C (atmospheric)
- LEL: 3.6% by volume
- UEL: 33% by volume
- Autoignition: 472 °C
- IARC: Group 1 carcinogen (linked to liver angiosarcoma)
ATEX Zone Classification
- Zone 0: Tank ullage - continuous VCM vapor
- Zone 1: Tank vent outlet, pump seal, loading arm (explosive atmosphere likely in normal operation)
- Zone 2: 3 m radius around Zone 1 (only short-term, under fault or abnormal conditions)
- Equipment category: II 2G Ex db IIA T2 (VCM gas group IIA)
Explosion Pressure
VCM maximum explosion pressure: Pmax = 8.8 bar (1 atm initial).
Kst and the St classes are defined for dusts (NFPA 68, Annex B); for gas and vapor mixtures the vent area is based on gas data such as Pmax and burning velocity.
For gases, NFPA 68 sizes the vent area with the equations of Chapter 7 (for example 7.2.1a); the inputs are the enclosure internal surface area, Pred, Pmax, fundamental burning velocity, unburned gas density, the turbulence factor and the vent discharge coefficient. These inputs must be confirmed for VCM before any vent area is quoted.
Fire Protection
- Deluge water spray: 10 L/min/m² tank cooling
- Foam: Alcohol-resistant AFFF (VCM is not a polar solvent, but it can polymerize at fire temperatures, so a standard AFFF film is not sufficient)
- Gas detection: Catalytic or IR, alarm at 20% LEL, emergency shutdown (ESD) at 40% LEL
- Emergency shutdown: isolation of all transfer lines in under 30 s
- Ventilation: 12 air changes per hour, explosion-protected (Ex) fan

ATEX ventilation with MEP Calc
MEP Calc supports air-change sizing, ESD flow, explosion pressure and vent area calculations for VCM storage.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.