Large marinas with 650, 580 and 320 berths drive a billion-dollar tourism business. Yachts carry diesel and gasoline, LPG galleys and Li-ion batteries. NFPA 303 (2016 edition) calls for a Class I standpipe on piers, bulkheads and buildings where the hose-lay distance from the fire apparatus exceeds 45 m (6.3.1), an approved water supply within 30 m of the pier/land intersection or fire department connection (6.2.5), and extra (high) hazard type portable extinguishers on two sides of a fuel-dispensing area (6.1.1.1.2.1). The other figures in this article (emergency-stop spacing, extinguisher size, separation distance and similar) could not be found in the text of NFPA 303.
Marina Fire Hazards
- Fuel: Gasoline Class IA and diesel Class II together
- LPG galley: Daily propane use on board
- Li-ion: Boat battery packs up to about 100 kWh
- Electrical: 230 V shore power
- Fabrics: Awnings and mainsails, preferably flame-retardant (FR) fabric
NFPA 303 Pier Standpipes and Water Supply
- Water supply: An approved water supply within 30 m of the pier/land intersection or fire department connection (6.2.5)
- Flow: Standpipe supply piping on piers and bulkheads sized for at least 1,136 L/min (300 gpm) (6.3.5)
- Standpipe: Class I standpipe where the hose-lay distance from the fire apparatus exceeds 45 m (6.3.1)
- Hose: Hose racks, hoses and standpipe cabinets are not required on piers and bulkheads (6.3.4)
- Fire boat: Recommended for large marinas
Fueling
- Dispenser: UL 87 listed
- Emergency stop: 6 m spacing
- Extinguisher: Class B, 20 lb
- Spill kit: Adsorbent boom
- Separation: 7.5 m from the fueling point
Shore Power
- IEC 60092: Marine standard for on-board electrical installations
- Amps: 16-32-63 A
- Residual-current protection (RCD/GFCI): Mandatory in marine installations
- Connector: IP67 marina type
- Boat side: Isolation transformer (also prevents galvanic corrosion)
Marina Examples
- A large marina: 650 berths, one of the few ports accepting megayachts
- Another marina: 580 berths
- A smaller marina: 320 berths
- Another large marina: 600 berths
- A megayacht fire: a reference incident among those prompting NFPA 303 updates

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 303, NFPA 302, ISO 9650, ABYC H-25, IEC 60092. NFPA 303 Marinas and Boatyards.