Short answer: TS EN 12845-2:2025 Introduction, EN p.4: ESFR operates in suppression mode, that is, it is capable of significantly suppressing the heat release rate of a fire; the design is given by the k-factor, the number of operating heads and the required head pressure. CMSA operates in control mode; the design is given by the number of operating heads and the required pressure. CMDA operates in control mode in accordance with EN 12845-1 and its design is given by a minimum water application density (mm/min) over a defined area of operation.

In sprinkler design the question "which mode" is not a preference but an outcome permitted by the text of the standard. This article compares the three modes from two sources only: TS EN 12845-2:2025 (EN 12845-2:2024), for ESFR and CMSA; TS EN 12845+A2:2026 (EN 12845:2015+A2:2026), for CMDA. Every value in the comparison is given together with its clause or table number and EN page.

1. Definitions: how the standard separates the three modes

The Introduction of EN 12845-2 (EN p.4) defines the three concepts directly:

The same section adds this as well: the ESFR sprinkler concept is a technical development derived from CMSA sprinklers; ESFR and CMSA designs are less capable of coping with adverse design features and non-conformities, and it is particularly important that all the requirements of this standard are complied with without exception.

The link between the two standards is established on the EN 12845+A2 side as well: Annex N (normative, EN p.162) for CMSA systems and Annex P (normative, EN p.164) for ESFR systems state that "EN 12845-2 shall be applied together with this document" and refer to Annex A of EN 12845-2:2024 for the class conversion.

2. How the design is expressed

CMDA CMSA ESFR
How the design is given Density (mm/min) × area of operation (m²) Number of sprinklers @ minimum pressure (bar) Number of sprinklers @ minimum pressure (bar)
Main design tables Table 3 (LH/OH/HHP), Tables 4 and 5 (HHS) Tables 15-21 (general), Tables 22-25 (special products) Tables 7-9 (ceiling only), Tables 10-11 (conditional), Tables 12-14 (in-rack)
Source TS EN 12845+A2, EN p.36, 38, 39 EN 12845-2, EN p.49-58 EN 12845-2, EN p.36-47

Example values on the CMDA side (Table 3, Clause 7.1, EN p.36): LH 2.25 mm/min and 84 m²; OH1 5.0 mm/min and 72 m²; OH2 5.0 mm/min and 144 m²; OH3 5.0 mm/min and 216 m²; OH4 5.0 mm/min and 360 m²; HHP1 7.5 mm/min, HHP2 10.0 mm/min, HHP3 12.5 mm/min, all three over 260 m². For HHP4 there is a note reading "deluge, special consideration required, not within the scope of this standard".

Example values on the ESFR side (Table 7, Clause 6.6.1.1, EN p.36): HHS1-HHS3, for a 9.1 m ceiling / 7.6 m storage, K200 pendent 3.4 bar, K240 2.4 bar, K320 1.7 bar, K360 1.0 bar; the same classes for a 10.7 m ceiling / 9.1 m storage, K200 5.2 bar, K240 3.6 bar, K320 2.4 bar, K360 1.4 bar. The designs in Table 7 are generally based on the operation of 12 heads.

Example values on the CMSA side (Table 16, Clause 6.7.1, EN p.50): HHS3, for 7.6 m storage / 9.1 m ceiling, K240 upright 15 sprinklers @ 1.5 bar, K280 pendent 15 @ 1.1 bar, K360 pendent 15 @ 0.7 bar, K360 upright 12 @ 1.4 bar.

3. K factors

The k-factors for CMDA are limited by TS EN 12845+A2 Table 37a (Clause 14.2.1, EN p.104):

Hazard class Design density Nominal K-factor
LH 2.25 mm/min 57
OH 5.0 mm/min 80 or 115
HHP and HHS ceiling/roof sprinklers ≤10 mm/min 80, 115 or 160
HHP and HHS ceiling/roof sprinklers >10 mm/min 115 or 160
HHS intermediate level sprinklers in high stack storage - 80 or 115

On the EN 12845-2 side, the k-factors are read from the design tables: for ESFR, Tables 7-11 contain K200, K240, K320, K360, K400 and K480 columns (EN p.36-41); for CMSA, Tables 15-25 use K160, K240, K280, K360 and K480 (EN p.49-58).

The flow rate comes from the same formula in all three modes: Q = K√P (TS EN 12845+A2 Clause 14.3, EN p.104-105); Q in l/min, K the constant from Table 37a, P in bar.

4. Pressures

In CMDA the design pressure is given not as a single range but as a minimum discharge pressure (Clause 13.4.4, EN p.102): the pressure at the hydraulically most unfavourable sprinkler shall not be less than the value required to achieve the density specified in 13.4.1, or than the following, whichever is the higher:

In EN 12845-2 the pressure is read directly from the design tables. The extreme values found in the tables: in CMSA the lowest is 0.5 bar (Table 17, HHS1/HHS2, K360 upright dry, 20 sprinklers, EN p.51) and the highest is 5.2 bar (Table 22 rubber tyres, K160 upright 15 sprinklers, EN p.57); in ESFR the lowest is 1.0 bar (Table 7, K360, EN p.36) and the highest is 6.9 bar (Table 10, HHS5, K200, 12 sprinklers, EN p.41). Clause 5.4 (EN p.33) also gives the minimum operating pressure for the 12 sprinkler HHS5 design directly: 2.0 bar up to a storage height of 7.6 m / ceiling 9.1 m, and 4.1 bar up to storage 10.7 m / ceiling 12.2 m.

5. Number of sprinklers, shape of the design area and duration

EN 12845-2 Table 6 (Clause 6.4, EN p.34) gives three pieces of information together:

Number of ceiling sprinklers Water supply duration (min) Shape of design area (sprinklers × range pipes)
9 60 3 × 3
10 60 3 × 2 + 4 × 1
12 60 4 × 3
15 90 5 × 3
16 90 5 × 3 + 1 × 1
20 120 5 × 4
24 120 6 × 4
25 120 6 × 4 + 1 × 1
30 120 7 × 4 + 2 × 1

NOTE 2: with CMSA in roll paper storage the duration shall be 120 min irrespective of the number of sprinklers. NOTE 3: with CMSA in rubber tyre storage the duration shall be 180 min. Table 21 (EN p.55) also contains special dry pipe designs with 36 sprinklers, and that table carries its own system duration column (90 or 120 min).

In CMDA the duration is tied not to the number of sprinklers but to the hazard class (Clause 8.1.1, EN p.42): LH 30 min, OH 60 min, HHP 90 min, HHS 90 min.

6. Layout and response characteristic

Topic CMDA (TS EN 12845+A2) ESFR (EN 12845-2) CMSA (EN 12845-2)
Maximum coverage area LH 21.0 m², OH 12.0 m², HHP and HHS 9.0 m² (Table 19, EN p.70) 9.3 m² (5.1.3.2, EN p.8) 12 m² in certain ceiling cases in STC1, 9.3 m² in all other cases (5.1.3.3, EN p.8)
Minimum coverage area Not given 6 m² (5.1.3.2) 7.5 m² (5.1.3.3)
Minimum distance between sprinklers 2 m (12.3, EN p.72) 2.4 m (5.1.3.2) 2.4 m (5.1.3.3)
Maximum spacing LH 4.6 m, OH 4.0 m, HHP/HHS 3.7 m (Table 19) 3.7 m with a ceiling ≤9.1 m; 3.1 m above 9.1 m 3.7 m; 3.1 m with combustible obstructed construction
Distance to wall The smallest suitable value in accordance with 12.4.1 (EN p.72) ≤50% of the maximum permitted spacing ≤50% of the maximum permitted spacing
Deflector below ceiling Preferably 0.075-0.15 m; where unavoidable ≤0.3 m with a combustible ceiling, ≤0.45 m with an A1/A2 ceiling (12.4.2, EN p.72) At least 100 mm; maximum 325 or 425 mm according to Table 2 (5.1.3.5.2, EN p.9-10) At least 100 mm; maximum 225-325 mm unobstructed and 325 mm obstructed according to Table 2

On the response characteristic, EN 12845-2 Clause 5.1.1 NOTE 2 (EN p.8) says only this: ESFR typically has a nominal operating temperature of 68 °C to 74 °C and is quick response; CMSA is also typically 68 °C to 74 °C, except in dry systems where it is generally 141 °C. The standard gives no numerical RTI value. On the CMDA side the classification is made by Table 38 (Clause 14.5.1, EN p.106): quick response, special response and standard 'A' response; according to the table, quick response sprinklers are not used in dry systems, and in racks only quick response sprinklers are used.

7. Limits of applicability: who chooses the mode

The standard does not tabulate the choice of mode by stack height. Instead it sets exclusions and preconditions:

Read together, these two provisions mean that ESFR and CMSA cannot be applied in areas classified as OH4 or higher under the EN 12845:2015 classification.

On hazard classes, the classification on the CMDA side also has clear limits: Clause 6.2.2 (EN p.31) defines LH as occupancies with low fire load and low combustibility, no single compartment exceeding 126 m² and a fire resistance of at least 30 min; Clause 6.2.3 (EN p.31) permits storage in OH areas only where the room as a whole is designed to at least OH3, the maximum storage heights in Table 1 are complied with, the area of a single block does not exceed 50 m² and there is a clearance of at least 2.4 m around the block.

Field note: Although the three modes appear to be alternatives to one another, the text of the standard places them behind different doors: first the occupancy and hazard class, then the storage configuration and height, then whether the commodity appears in a table row at all. If there is no table row, there is no mode.

Frequently Asked Questions

What is the fundamental difference between CMDA, CMSA and ESFR?

TS EN 12845-2:2025 Introduction, EN p.4: ESFR operates in suppression mode, that is, it is capable of significantly suppressing the heat release rate of a fire; the design is given by the k-factor, the number of operating heads and the required head pressure. CMSA operates in control mode; the design is given by the number of operating heads and the required pressure. CMDA operates in control mode in accordance with EN 12845-1 and its design is given by a minimum water application density (mm/min) over a defined area of operation.

Which K factors are used in the three modes?

For CMDA, TS EN 12845+A2:2026 Table 37a (EN p.104): LH K57; OH K80 or K115; HHP and HHS ceiling sprinklers K80, K115 or K160 where the density is ≤10 mm/min and K115 or K160 where it is >10 mm/min; HHS intermediate level sprinklers K80 or K115. For ESFR, EN 12845-2 Tables 7-11 (EN p.36-41) give values from K200 to K480; for CMSA, Tables 15-25 (EN p.49-58) give values from K160 to K480.

How many sprinklers are assumed to operate in each mode?

EN 12845-2 Table 6 (EN p.34) lists the number of sprinklers in the ceiling design as 9, 10, 12, 15, 16, 20, 24, 25 and 30; Table 21 (EN p.55) also contains 36 sprinkler designs. For CMDA the number is not given directly; TS EN 12845+A2 Table 3 (EN p.36) gives density and area of operation, e.g. 5.0 mm/min and 216 m² for OH3.

Can ESFR and CMSA be used in every hazard class?

No. EN 12845-2 Clause 6.2 (EN p.33): ESFR and CMSA protection shall not be applied to FH3 to FH5 occupancies. Where they are used in FH1 and FH2 hazards, they are designed as HHS1 to HHS3 in accordance with 6.6 or 6.7, irrespective of the storage category. In addition, Clause 6.1 (EN p.33) states that goods such as flammable liquids and aerosols shall not be protected in accordance with this document and that EN 12845 applies instead.

How are the water supply durations determined?

For ESFR and CMSA, EN 12845-2 Table 6 (EN p.34) ties the duration to the number of sprinklers: 9-12 sprinklers 60 min, 15-16 sprinklers 90 min, 20-30 sprinklers 120 min. NOTE 2: with CMSA in roll paper storage the duration is 120 min irrespective of the number of sprinklers; NOTE 3: with CMSA in rubber tyre storage it is 180 min. For CMDA, TS EN 12845+A2 Clause 8.1.1 (EN p.42): LH 30 min, OH 60 min, HHP 90 min, HHS 90 min.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.