Short answer: The opening of Annex A (normative) of TS EN 12845+A2:2026, EN p.124: Tables A.1, A.2 and A.3 contain lists of minimum hazard classification. They shall also be used as a guide for occupancies not specifically mentioned. They shall be read together with Clause 6.2. In other words, Annex A is normative and the value it gives is a minimum.

The first step in sprinkler design is to determine the hazard class; Clause 6.1 of TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) (EN p.30) says so explicitly: the hazard class for which the sprinkler system is to be designed shall be determined before the design work is started. Annex A (normative, EN p.124-126) gives the occupancy lists to be used in making that determination. All the lists and figures below are taken from the text of the standard.

1. The status of Annex A

The opening sentence of Annex A (EN p.124) says three things:

In other words, Annex A is normative, the value it gives is a minimum, and an occupancy falling outside the table is derived from its closest equivalent.

2. Definitions of the classes (Clause 6.2, EN p.31-32)

Storage in OH areas (Clause 6.2.3, EN p.31): materials may be stored in occupancies classified as OH, but under the following conditions: (a) the protection shall be designed to at least OH3 throughout the room; (b) the maximum storage heights shown in Table 1 shall not be exceeded; (c) the maximum storage area of a single block shall not exceed 50 m² and there shall be a clearance of at least 2.4 m around the block. Where the area is classified as OH4, or where (b) or (c) cannot be met, the storage in the area shall be treated as HHS (6.2.4.2).

Table 1 (EN p.32) - Maximum storage heights for OH3 protection (m):

Storage category Free standing or block stacking (ST1) Other configurations (ST2 - ST6)
Category I 4.0 3.5
Category II 3.0 2.6
Category III 2.1 1.7
Category IV 1.2 1.2

Footnote a: for storage heights exceeding the values in the table, HHS protection is used (6.2.4.2 and 7.2). Footnote b: ST6 storage is limited to gondola shelving of 1.2 m overall width with a solid central barrier extending from base to top; all other ST6 storage is protected in accordance with HHS protection (7.2).

3. Table A.1: Light Hazard occupancies (EN p.124)

4. Table A.2: Ordinary Hazard occupancies (EN p.124-125)

Group OH1 OH2 OH3 OH4
Glass and ceramics - - Glass works -
Chemicals Cement works Photographic film factories Dye works, soap factories, photographic laboratories, paint spraying shops using water based paints -
Engineering Sheet metal product works Metal working Electronics factories, radio equipment factories, washing machine factories, car service stations -
Food and drink - Abattoirs and meat factories, bakeries, biscuit factories, breweries, chocolate factories, confectioneries, dairies Animal feed factories, corn mills, dried vegetable and soup factories, sugar factories Distilleries
Miscellaneous Hospitals, hotels, libraries (excluding book storage), restaurants, schools (see 6.2.2), offices (see 6.2.2) Laboratories (physical), laundries, car parks, museums Broadcasting studios (small), railway stations, plant rooms, farm buildings Cinemas and theatres, concert halls, tobacco factories, film and TV production studio
Paper - - Bookbinders, cardboard factories, paper mills Waste paper processing
Shops and offices Data processing (computer room, excluding tape storage), offices (see 6.2.2) - Shops, shopping centres Exhibition halls ᵃ
Textile and clothing - Leather goods factories Carpet factories (excluding rubber and foamed plastics), cloth and clothing factories, fibreboard factories, shoe factories (excluding plastics and rubber), knitwear factories, linen factories, mattress factories (excluding foamed plastics), making-up factories, weaving mills, woollen and worsted mills Cotton mills, flax preparation plants, hemp preparation plants
Timber and wood - - Woodworking factories, furniture factories (without foamed plastics), furniture showrooms, upholstery (without foamed plastics) factories Sawmills, plywood factories

NOTE (below Table A.2, EN p.125): where there are paint spraying or similar high fire load areas within an OH1 or OH2 occupancy, these should be treated as OH3.

Footnote a: excessive clearance shall be taken into account.

5. Table A.3: High Hazard Process occupancies (EN p.126)

HHP1 HHP2 HHP3 HHP4
Oilcloth and linoleum manufacture Fire lighter manufacture Cellulose nitrate manufacture Firework manufacture
Resin, lamp black and turpentine manufacture Tar distillation Car and lorry tyres -
Rubber substitute manufacture Bus, empty lorry and wagon depots Manufacture of foamed plastics with material factor m3 (see Table B.1), sponge rubber and sponge rubber goods (excluding m4, see Table B.1) -
Wood wool manufacture Candle and paraffin manufacturers - -
Match manufacturers Paper machine rooms - -
Paint spraying shops using solvents Carpet factories containing rubber and foamed plastics - -
Refrigerator factories Sawmill - -
Printing works Chipboard manufacture (see NOTE) - -
Cable factories of PP/PE/PS or similar burning characteristics (other than OH3) - - -
Paint, colour and varnish manufacture - - -
Injection moulding (plastics) of PP/PE/PS or similar burning characteristics (other than OH3) - - -
Plastics factories and plastic products (excluding foamed plastics) of PP/PE/PS or similar burning characteristics (other than OH3) - - -
Rubber goods factories, synthetic fibre factories (excluding acrylics) - - -
Rope factories - - -
Carpet factories containing non-expanded plastics - - -
Shoe factories containing plastics and rubber - - -

NOTE: additional object protection may be required.

6. From the class to the design criteria

Table 3 (Clause 7.1, EN p.36) converts the class directly into a design density and an area of operation:

Hazard class Design density (mm/min) Area of operation, wet or pre-action (m²) Area of operation, dry or alternate (m²)
LH 2.25 84 Not permitted, OH1 is used
OH1 5.0 72 90
OH2 5.0 144 180
OH3 5.0 216 270
OH4 5.0 360 Not permitted, HHP1 is used
HHP1 7.5 260 325
HHP2 10.0 260 325
HHP3 12.5 260 325
HHP4 deluge (see NOTE) - -

For HHS the design criteria come by a different route: Table 4 (roof or ceiling protection only, Clause 7.2.2, EN p.38) and Table 5 (roof or ceiling sprinklers with in-rack sprinklers, Clause 7.2.3, EN p.39). In these two tables the input variables are the storage configuration (ST1-ST6), the commodity category (I-IV) and the maximum storage height; the outputs are the density (from 7.5 mm/min to 30.0 mm/min) and the area of operation (260 m² or 300 m²).

Clause 7.2.3.2 (EN p.37): where intermediate level in-rack sprinklers are present, the design density for the roof or ceiling sprinklers shall be at least 7.5 mm/min over an area of operation of 260 m²; where goods are stored above the highest intermediate protection level, the design criteria are taken from Table 5.

7. When two classes occur together

The last sentence of Clause 6.1 (EN p.31): where there are areas in open communication with different hazard classifications, the higher design criteria shall be extended into the area of lower classification by at least two rows of sprinklers.

A similar rule applies to the categorisation of stored goods. Clause B.3.1 (EN p.129): once the material factor has been determined, the storage configuration in column 1 of Table B.1 is used to identify the most appropriate category; where Table C.1 also gives an appropriate category, the higher of the two shall be used.

8. Other clauses that affect the classification

Frequently Asked Questions

Is Annex A binding, or is it only a list of examples?

The opening of Annex A (normative) of TS EN 12845+A2:2026, EN p.124: Tables A.1, A.2 and A.3 contain lists of minimum hazard classification. They shall also be used as a guide for occupancies not specifically mentioned. They shall be read together with Clause 6.2. In other words, Annex A is normative and the value it gives is a minimum.

What is the numerical criterion for the LH class?

Clause 6.2.2, EN p.31: LH covers occupancies with low fire load and low combustibility, with no single compartment greater than 126 m² and with a fire resistance of at least 30 min. Table A.1 (EN p.124) lists the LH occupancies: schools and other educational establishments (certain areas), offices (certain areas) and prisons.

Which hazard class do museums fall into?

Table A.2, EN p.125: Museums are listed in the OH2 column, in the same column as Laboratories (physical), Laundries and Car parks.

Which class covers cinemas, theatres and concert halls?

Table A.2, EN p.125: Cinemas and theatres, Concert halls, Tobacco factories and Film and TV Production Studio are in the OH4 column.

What design density and area correspond to each hazard class?

Table 3, Clause 7.1, EN p.36: LH 2.25 mm/min and 84 m²; OH1 5.0 mm/min and 72 m²; OH2 5.0 mm/min and 144 m²; OH3 5.0 mm/min and 216 m²; OH4 5.0 mm/min and 360 m²; HHP1 7.5 mm/min, HHP2 10.0 mm/min, HHP3 12.5 mm/min, all three over 260 m². These areas are for wet or pre-action systems.

Which class applies where two different classes exist in the same building?

End of Clause 6.1, EN p.31: where there are areas in open communication with different hazard classifications, the higher design criteria shall be extended into the area of lower classification by at least two rows of sprinklers. For stored goods, Clause B.3.1 (EN p.129): where Table B.1 and Table C.1 give different categories, the higher of the two shall be used.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.