Source: TS EN 12845+A2:2026, Clause G.4 "Flammable liquid storage" (EN p.147), Table G.2 and Table G.3 (EN p.148), Table G.4 (EN p.149).
Clause G.4 consists of a short introductory sentence and three tables. The whole design is read from those tables; in this clause the standard gives no provision on the extinguishing method, foam, spill control or detection.
The text of Clause G.4
Clause G.4 (EN p.147) is a single sentence: "Flammable liquids shall be classified into four classes according to their flash point (FP) and boiling point (BP), as shown in Tables G.2, G.3 and G.4."
Classification
| Class | Properties (C) |
|---|---|
| 1 | FP >= 100 |
| 2 | FP < 100 |
| 3 | FP < 35 |
| 4 | FP < 21 and BP < 35 |
Source: Table G.2, EN p.148.
Note carefully: in this system Class 1 is the least flammable and Class 4 the most flammable. As the class number rises, the flash point falls and the design becomes more onerous.
Table G.2: ST1 metal drums, capacity > 20 l and <= 208 l
| Class | Properties (C) | Drum orientation | Permitted storage | Ceiling sprinkler density (mm/min) | Area of operation (m2) |
|---|---|---|---|---|---|
| 1 | FP >= 100 | On side | <= 12 drums high | 10 | 450 |
| 1 | FP >= 100 | On end | <= 6 drums high | 10 | 450 |
| 2 | FP < 100 | On side | <= 6 drums high | 25 | 450 |
| 2 | FP < 100 | On end | <= 2 drums high | 25 | 450 |
| 3 | FP < 35 | On side | <= 3 drums high | 25 | 450 |
| 3 | FP < 35 | On end | <= 1 drum high | 25 | 450 |
| 4 | FP < 21 and BP < 35 | On side or on end | 1 drum high | 25 | 450 |
Source: Table G.2, EN p.148.
In this table the storage limit is given not in metres but as a number of drums. The drum orientation (on side / on end) directly changes the permitted number.
Table G.3: ST4 palletized racks, metal drums, capacity > 20 l and <= 208 l
| Class | Properties (C) | Drum orientation | Intermediate sprinkler levels | Ceiling density (mm/min) | Area of operation (m2) |
|---|---|---|---|---|---|
| 1 | FP >= 100 | On side | Each 12th tier | 10 | 450 |
| 1 | FP >= 100 | On end | Each 6th tier | 10 | 450 |
| 2 | FP < 100 | On side | Each 6th tier | 25 | 450 |
| 2 | FP < 100 | On end | Each tier | 10 | 450 |
| 3 | FP < 35 | On side | Each 3rd tier | 25 | 450 |
| 3 | FP < 35 | On end | Each tier | 10 | 450 |
| 4 | FP < 21 and BP < 35 | On side or on end | Each tier | 25 | 450 |
NOTE (EN p.148): This table applies to drums stored at a height of one drum per tier.
Source: Table G.3, EN p.148.
The logic of Table G.3 is this: in on-end storage the intermediate sprinkler levels become more frequent while the ceiling density drops (10 mm/min for Classes 2 and 3), whereas in on-side storage the intermediate levels become sparser and the ceiling density rises to 25 mm/min.
Table G.4: ST1, ST5, ST6 metal drums, capacity <= 20 l
| Class | Properties (C) | Type of storage | Maximum permitted storage height (m) | Ceiling density (mm/min) | Area of operation (m2) |
|---|---|---|---|---|---|
| 1 | FP >= 100 | ST1 | 5.5 | 10 | 450 |
| 1 | FP >= 100 | ST5/6 | 4.6 | 7.5 | 450 |
| 2 | FP < 100 | ST1 | 4.0 | 12.5 | 450 |
| 2 | FP < 100 | ST5/6 | 4.6 | 12.5 | 450 |
| 3 | FP < 35 | ST1 | 1.5 | 12.5 | 450 |
| 4 | FP < 21 and BP < 35 | ST5/6 | 2.1 | 12.5 | 450 |
Source: Table G.4, EN p.149. (In Class 2 the density cell spans the ST1 and ST5/6 rows together.)
Table G.4 covers only ST1, ST5 and ST6 (title: metal drums with a capacity up to 20 l, EN p.149); the table has no ST1 row for Class 4 and no ST5/6 row for Class 3, and the standard regulates only the combinations listed.
Comparison of the three tables
| Item | Table G.2 | Table G.3 | Table G.4 |
|---|---|---|---|
| Container type | Metal drum > 20 l, <= 208 l | Metal drum > 20 l, <= 208 l | Metal drum <= 20 l |
| Storage configuration | ST1 | ST4 | ST1, ST5, ST6 |
| Unit of the limit | Number of drums | Number of tiers (intermediate sprinkler frequency) | Metres |
| Density range | 10 or 25 mm/min | 10 or 25 mm/min | 7.5; 10; 12.5 mm/min |
| Area of operation | 450 m2 | 450 m2 | 450 m2 |
Source: Tables G.2, G.3 (EN p.148) and Table G.4 (EN p.149).
What the three tables have in common is the 450 m2 area of operation; this is markedly larger than the 260 m2 and 300 m2 values the standard uses for HHS storage (Table 4, EN p.38).
Clause G.4 gives no provision for duration; the general provision is in Clause 8.1.1 (EN p.42): LH 30 min, OH 60 min, HHP 90 min, HHS 90 min.
What the standard does not say here
- Class designations such as IA, IB, IC, II, IIIA, IIIB and the flash point thresholds attached to them. The flammable liquid classes of EN 12845 are 1, 2, 3, 4.
- A 260 m2 area of operation. In all three tables of Clause G.4 the area is 450 m2.
- A foam (AFFF) additive, a foam-water system, a deluge valve, a proportioner or a flame detector.
- A bund or dyke capacity formula, a door threshold, or a stock volume threshold for a separate fire compartment.
- IBC storage (1000 l plastic containers). The tables cover metal drums.
- A requirement for fire monitors (water cannons) or their spacing.
Field note
Field note (not from the standard, this is engineering interpretation): in this clause the input that fixes the design is not the commercial name of the product but the measured flash and boiling point, so the FP/BP values from the safety data sheet of every stored product have to go into the project file. A change of drum orientation (on side / on end) during operation means, under Tables G.2 and G.3, a direct change of design.
Frequently Asked Questions
How does EN 12845 classify flammable liquids?
TS EN 12845+A2:2026 Clause G.4 (EN p.147): flammable liquids are divided into four classes according to their flash point (FP) and boiling point (BP). According to Table G.2 (EN p.148) Class 1: FP >= 100 C; Class 2: FP < 100 C; Class 3: FP < 35 C; Class 4: FP < 21 C and BP < 35 C.
How large is the area of operation?
In Tables G.2, G.3 and G.4 alike (EN p.148-149) the area of operation is 450 m2 for every class. The ceiling densities take the values 7.5, 10, 12.5 and 25 mm/min.
How is the stack height of metal drums limited?
Table G.2 (EN p.148), for ST1 metal drums with a capacity > 20 l and <= 208 l: Class 1 on side <= 12 drums, on end <= 6 drums; Class 2 on side <= 6, on end <= 2; Class 3 on side <= 3, on end <= 1; Class 4 on side or on end 1 drum high. The ceiling density is 10 mm/min for Class 1 and 25 mm/min for Classes 2, 3 and 4.
What is the intermediate sprinkler frequency in rack storage of drums?
Table G.3 (EN p.148, ST4): Class 1 on side each 12th tier, on end each 6th tier, density 10 mm/min; Class 2 on side each 6th tier at 25 mm/min, on end each tier at 10 mm/min; Class 3 on side each 3rd tier at 25 mm/min, on end each tier at 10 mm/min; Class 4 each tier at 25 mm/min. In all cases the area is 450 m2. NOTE: this table applies to drums stored at a height of one drum per tier.
Does EN 12845 require foam or a bund in flammable liquid storage?
Clause G.4 contains no provision on foam, deluge valves, proportioners or bunds/dykes. In Annex G a foam additive is required only in Clause G.8.5 (EN p.152) for PP/PE bins, while drainage or a bund appears only in Clause G.6 (EN p.150) at the level of a recommendation.
References
- TS EN 12845+A2:2026 Clause G.4 (EN p.147)
- TS EN 12845+A2:2026 Table G.2 and Table G.3 with the NOTE (EN p.148)
- TS EN 12845+A2:2026 Table G.4 (EN p.149)
- TS EN 12845+A2:2026 Clause G.6 (EN p.150)
- TS EN 12845+A2:2026 Clause G.8.5 (EN p.152)
- TS EN 12845+A2:2026 Table 4 (EN p.38)
- TS EN 12845+A2:2026 Clause 8.1.1 (EN p.42)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreTS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.