Source: TS EN 12845+A2:2026, Annex I (normative) "Transmission of alarms", I.1 and Table I.1 (EN p.155), continuation of Table I.1 and I.2 (EN p.156).
Annex I consists of two clauses: I.1 Functions to be monitored and I.2 Alarm levels. Table I.1 in between shows which clause each alarm in the standard comes from and which type it is.
It is worth starting with an important conceptual correction: A and B are alarm types, not transmission levels. The standard does not define a transmission tier such as "direct to fire brigade" or "local only".
I.1 Functions to be monitored
Clause I.1 (EN p.155):
- The alarms specified in this standard shall be connected to an alarm panel in the sprinkler control room or pump room and transmitted onwards depending on the importance of the alarm.
- Alarms shall be transmitted to a permanently attended location, on or off the premises.
- B-Type Alarms (Technical Alarms) may in addition be transmitted to a responsible person in such a way that immediate corrective action can be taken (see Clause 20.1).
- If a direct connection to the fire brigade exists, the alarm transmission procedure should be agreed with the authorities.
Table I.1: Type of alarm for transmission
| Alarm | Clause | Alarm type |
|---|---|---|
| Water flow alarm | 16.1.1 | A |
| Low pressure in town main | 9.2 | B |
| Water flow detector in pump room | 10.3.2 | A |
| Low level priming tank | 10.6.2.4 | B |
| Electric pump set: on demand | 10.8.5.1 | B |
| Electric pump set: start failure | 10.8.5.1 | B |
| Electric pump set: running | 10.8.5.1 | A |
| Electric pump set: power not available | 10.8.5.1 | B |
| Diesel pump set: automatic mode off | 10.9.2 | B |
| Diesel pump set: start failure | 10.9.2 | B |
| Diesel pump set: running | 10.9.2 | A |
| Diesel pump set: common fault | 10.9.2 | B |
| Trace heating (electrical heating trace) circuits | 11.1.2.3 | B |
| Low pressure: pre-action Type A system | 11.4.1.2 | B |
| Low pressure: dry pipe and pre-action systems | 16.2.3 | B |
Source: Table I.1, EN p.155.
Continuation of the table (EN p.156):
| Alarm | Clause | Alarm type |
|---|---|---|
| Zoned systems: open control valve | D.3.7 | B |
| Zoned systems: partially closed control valve | D.3.7 | B |
| Zoned systems: partially open subsidiary valve | D.3.7 | B |
| Zoned systems: low mains pressure | D.3.7 | B |
| Zoned systems: water flow in installation | D.3.7 | A |
| Zoned systems: water flow in zone | D.3.7 | A |
| Monitored sprinkler systems: partially closed stop valves | Annex H | B |
| Monitored sprinkler systems: liquid levels | Annex H | B |
| Monitored sprinkler systems: low pressure | Annex H | B |
| Monitored sprinkler systems: power failure | Annex H | B |
| Monitored sprinkler systems: low temperature in pump room | Annex H | B |
Source: continuation of Table I.1, EN p.156.
The way to read the table comes down to a simple rule: everything related to water flow is Type A, everything related to technical status and faults is Type B.
I.2 Alarm levels
Clause I.2 (EN p.156):
- "Signals from water flow alarms and/or alarm valves shall be shown as fire alarms (Alarm level A in Table I.1)."
- "Subject to local conditions, a signal indicating that the sprinkler pump set is running can alternatively be treated as a trouble alarm."
- "Technical faults such as a power failure, which could prevent the system operating correctly in case of fire, shall be shown as trouble alarms (Alarm level B in Table I.1)."
Other clauses related to Annex I
| Subject | Provision | Source |
|---|---|---|
| Checkability of the transmission equipment | It shall be capable of being checked for continuity of the connection and for continuity of the connection between the alarm switch and the control unit | Clause 16.3, EN p.111 |
| Direct connection to the fire brigade | The testing procedure should be agreed with the authorities in order to avoid false calls | Clause 16.3, EN p.111 |
| Electric pump indications | All monitored conditions shall be visually indicated individually in the pump room; pump running and a fault alarm shall also be audibly and visually indicated at a location permanently attended by responsible personnel | Clause 10.8.5.2, EN p.65 |
| Diesel pump indications | Pump running, start failure, common faults and automatic mode off shall be indicated both locally and at a responsibly manned location by warning lights | Clause 10.9.2, EN p.66 |
| Colour at the zoned installation panel | Green: each monitored stop valve is in its correct position; amber: a control valve set or subsidiary valve is not fully open, or the static pressure in the trunk main has fallen 0.5 bar or more below normal; red: water is flowing into the installation or into a zone | Clause D.3.7, EN p.137 |
| Silencing of alarms | Facilities shall be provided at the panel for silencing the audible alarms, but the visual indicators continue to operate until the system is restored to the normal standby condition | Clause D.3.7, EN p.137 |
Subjects not covered by Annex I
- Any alarm category called "Type C", or a local-only alarm option.
- Response time (for example 5-15 min, 10-30 min).
- Polling interval, alarm transmission time, changeover time to a standby line.
- A table of transmission line types (PSTN, IP, GSM, radio, satellite).
- "Transmission line fault" and "system test" signals. These two items do not appear in Table I.1.
- The certification standard for the alarm receiving centre. This is outside the scope of EN 12845.
Field note
Field note (engineering interpretation, not from the standard): the A/B distinction is more than a priority label, it determines how the panel and the transmission side are separated; routing Type A signals through the same channel as the Type B fault stream causes a genuine fire signal to be lost in the noise of technical faults. Using Table I.1 verbatim as the signal list for a project largely prevents this confusion.
Frequently Asked Questions
How many alarm levels does EN 12845 Annex I define?
Two. TS EN 12845+A2:2026 Clause I.2 (EN p.156): signals from water flow alarms and/or alarm valves shall be shown as fire alarms (Alarm level A in Table I.1); technical faults such as a power failure, which could prevent the system operating correctly in case of fire, shall be shown as trouble alarms (Alarm level B). There is no third level and no 'Type C'.
Where are the alarms transmitted to?
Clause I.1 (EN p.155): alarms shall be connected to an alarm panel in the sprinkler control room or pump room and be transmitted onwards depending on the importance of the alarm. Alarms shall be transmitted to a permanently attended location, on or off the premises. B-Type Alarms (Technical Alarms) may in addition be transmitted to a responsible person in such a way that immediate corrective action can be taken.
What type is the pump running signal?
Table I.1 (EN p.155) lists the 'running' signal for electric and diesel pump sets as Type A. Clause I.2 (EN p.156) allows one flexibility: subject to local conditions, a signal indicating that the sprinkler pump set is running can alternatively be treated as a trouble alarm.
Which signals does Table I.1 list?
Water flow alarm (16.1.1, A); low pressure in town main (9.2, B); water flow detector in pump room (10.3.2, A); low level priming tank (10.6.2.4, B); electric pump set (10.8.5.1: on demand B, start failure B, running A, power not available B); diesel pump set (10.9.2: automatic mode off B, start failure B, running A, common fault B); trace heating circuits (11.1.2.3, B); low pressure (pre-action Type A system 11.4.1.2 B; dry pipe and pre-action systems 16.2.3 B); zoned systems (D.3.7) and monitored sprinkler systems (Annex H).
What applies if there is a direct connection to the fire brigade?
Clause I.1 (EN p.155): if a direct connection to the fire brigade exists, the alarm transmission procedure should be agreed with the authorities. Clause 16.3 (EN p.111) further requires the transmission equipment to be capable of being checked for continuity of the connection and for continuity of the connection between the alarm switch and the control unit.
References
- TS EN 12845+A2:2026 Clause I.1 and Table I.1 (EN p.155)
- TS EN 12845+A2:2026 continuation of Table I.1 and Clause I.2 (EN p.156)
- TS EN 12845+A2:2026 Clause 16.3 (EN p.111)
- TS EN 12845+A2:2026 Clause 10.8.5.1 and 10.8.5.2 (EN p.65)
- TS EN 12845+A2:2026 Clause 10.9.2 (EN p.66)
- TS EN 12845+A2:2026 Clause D.3.7 (EN p.137)
- TS EN 12845+A2:2026 Annex H (EN p.153-154)
- TS EN 12845+A2:2026 Clause 20.1 (EN p.118)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreTS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.