Short answer: TS EN 12845+A2:2026 Table K.1 (EN p.159) gives the number of sprinklers to be tested of each available type as a function of the total number of sprinklers installed: 20 for ≤ 5 000; 40 for ≤ 10 000; 60 for ≤ 20 000; 80 for ≤ 30 000; 100 for ≤ 40 000.

Source: TS EN 12845+A2:2026, Annex K (informative) "Twenty-five year inspection" and Table K.1, EN p.159.

Annex K is one of the shortest annexes in the standard: it has no sub-clause numbers and consists of plain text and a single table. There are no clauses such as K.1, K.2, K.3 or K.4 in this annex. The annex is informative; the provisions are in the "should" form.

Scope of the annex

The opening of Annex K (EN p.159): "After 25 years the pipes and the sprinklers should be inspected."

So the annex defines two separate inspection subjects: the pipework and the sprinklers. They are dealt with together.

Inspection of the pipework

Subject Provision
Flushing The pipework should be thoroughly flushed out
Hydrostatic test It should be tested to a pressure equal to the maximum static pressure or 12 bar, whichever is the higher
Inspection The pipework should be inspected internally and externally
Range pipe sampling At least one metre length of range pipe should be inspected per 100 sprinklers
Sampling by diameter Two pipe sections of at least one metre length of each pipe diameter should be inspected
Defects All defects which might adversely affect the performance of the system should be eliminated

Source: Annex K, EN p.159.

How many installations are inspected?

System type Scope
Wet pipe systems At least one sprinkler installation per building should be checked
Where several wet control valve sets are installed in one building Only 10% need be inspected
Dry pipe systems Such a reduction is not allowed in the number of installations to be checked

Source: Annex K, EN p.159.

Table K.1: Number of sprinklers of each available type to be tested

Total number of sprinklers installed Number of sprinklers to be inspected
≤ 5 000 20
≤ 10 000 40
≤ 20 000 60
≤ 30 000 80
≤ 40 000 100

Source: Table K.1, EN p.159.

The title of the table matters: the number applies separately to each available type. Annex K does not say that separate grouping by temperature rating is required; the distinction is by type.

The text of Annex K (EN p.159): "A number of sprinklers should be removed and tested to ensure that they are fully functional. Table K.1 specifies the scope of sampling as a function of the total number of sprinklers installed."

Properties to be evaluated on the sprinklers

Annex K (EN p.159) lists six items:

The standard gives no numerical acceptance criterion for these items (for example a percentage deviation limit for the K-factor or an RTI limit for thermal sensitivity).

Where Annex K sits in the maintenance programme of the standard

Annex K is not part of the periodic service programme in Clause 20.3 (EN p.120 onwards); it is a 25 year milestone separate from it. The programme steps of Clause 20.3 are as follows:

Interval Subject Source
13 weeks maximum Quarterly routine (review of the hazard, sprinklers, pipes and hangers, water supplies and their alarms, electrical supplies, stop valves, flow alarms, spare parts) Clause 20.3.2, EN p.120-121
6 months maximum Half-yearly routine (dry alarm valves, electrical wiring of the fire service and remote centre alarms) Clause 20.3.3, EN p.121
12 months maximum Annual routine (full load flow test of the pump set, diesel failure-to-start test, tank ball valves, suction chambers and strainers) Clause 20.3.4, EN p.121-122
3 years maximum Three-yearly routine (internal examination of storage and pressure tanks; water supply stop, alarm and non-return valves) Clause 20.3.5, EN p.122
10 years maximum Ten-yearly routine (cleaning and internal examination of all storage tanks) Clause 20.3.6, EN p.122
25 years Inspection of pipes and sprinklers Annex K, EN p.159

In addition, Clause 21 (EN p.123): the sprinkler system is inspected periodically by a qualified person at least once a year (see Annex Q). The inspection report assesses whether the system complies with this standard in terms of its adequacy for maintenance, operation and the risk, and a list of deviations is drawn up.

What the standard does not say in Annex K

Field note

Field note (this is engineering interpretation, not part of the standard): in the 25 year inspection the real information comes from the internal condition of the pipes rather than from the sprinkler samples; range pipe sampling and sampling by diameter show how much corrosion and deposit build-up have changed the hydraulics of the system. For this reason, when the inspection is planned, the locations from which the sections will be taken should be decided in advance with the most unfavourable points of the installation in mind.

Frequently Asked Questions

How many sprinklers are tested under Annex K?

TS EN 12845+A2:2026 Table K.1 (EN p.159) gives the number of sprinklers to be tested of each available type as a function of the total number of sprinklers installed: 20 for ≤ 5 000; 40 for ≤ 10 000; 60 for ≤ 20 000; 80 for ≤ 30 000; 100 for ≤ 40 000.

What is done to the pipework?

Annex K (EN p.159): the pipework should be thoroughly flushed out and hydrostatically tested to a pressure equal to the maximum static pressure or 12 bar, whichever is the higher. The pipework should be inspected internally and externally; at least one metre length of range pipe should be inspected per 100 sprinklers, and two pipe sections of at least one metre length of each pipe diameter should be inspected.

How many installations in a building are inspected?

Annex K (EN p.159): in the case of wet pipe systems, at least one sprinkler installation per building should be checked. If several wet control valve sets are installed in one building, only 10% need be inspected. In the case of dry pipe systems, such a reduction of the number of installations to be checked is not allowed.

What is evaluated on the sprinklers that are removed?

Annex K (EN p.159) lists six items: a) operation; b) operation temperature; c) variation of K-factor; d) spray obstacles; e) lodgement; f) thermal sensitivity.

Is Annex K normative?

No. Annex K is informative and its text is in the 'should' form (EN p.159). The annual periodic inspection is covered by normative Clause 21 (EN p.123), which refers to informative Annex Q.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.