Short answer: Table 36 (Clause 13.4.5, TS p.106 / EN p.103): 20 mm for an LH risk; 20 mm for horizontal and upright pipe feeding a single sprinkler with a K-factor not exceeding 80 in OH and HH; 25 mm in all other cases. In addition, Clause 13.3.5.1 states that no pipe in high hazard shall be of a nominal diameter smaller than 25 mm.

In TS EN 12845+A2:2026 the pipe diameter comes out of two separate regimes: on pre-calculated systems everything downstream of the design point comes from tables and everything upstream from calculation; on fully calculated systems everything comes from hydraulic calculation. Beneath both regimes lies an unvarying floor: Table 36. Source: TS EN 12845+A2:2026, Clause 13.1, Clause 13.3, Clause 13.4.5 and Tables 27-36.

The unvarying floor: Table 36

Clause 13.4.5 (TS p.106 / EN p.103): the pipe diameter shall not be less than that shown in Table 36.

Risk Diameter
LH 20 mm
OH and HH: horizontal and upright pipe feeding a single sprinkler with a K-factor not exceeding 80 20 mm
All other cases 25 mm

Clause 13.3.5.1 (TS p.92 / EN p.89) repeats this for high hazard: no pipe shall be of a nominal diameter smaller than 25 mm.

The three rules that follow in the same clause determine the topology of the installation:

Clause 3.12 defines an arm pipe: a pipe, other than the final section of a range pipe, feeding a single sprinkler and shorter than 0.3 m.

Which system falls under which regime?

Clause 13.1 (TS p.85 / EN p.82): pipe sizes are determined by one of two methods. The designer may choose between the two, but the fully calculated method shall always be used in the following cases:

Clause 13.3.1.3: all pipes upstream of each design point are sized by calculation as specified in Clause 13.3.3.2 for Light Hazard and in Clause 13.3.4.2 for Ordinary Hazard. Clause 13.3.1.4: risers and drops connecting distribution pipes to ranges, and pipes other than arm pipes feeding a single sprinkler, are regarded as distribution pipes and sized accordingly.

LH: Table 27

Clause 13.3.3.1 and Table 27 (TS p.90 / EN p.87):

Pipes Diameter Maximum number of sprinklers
All range pipes and terminal distribution pipes 20 mm 1
25 mm 3

Clause 13.3.1.2 narrows the scope: in Light Hazard, Table 27 determines only the pipes feeding the last three or four sprinklers on each range. Clause 13.3.3.1 also states that, where hydraulic calculation shows it to be possible, 25 mm pipe may be used between the design point and the control valve set, but that where the 2 sprinkler point governs, 25 mm pipe shall not be used between the 3rd and 4th sprinklers.

OH: Table 30 and Table 31

Clause 13.3.4.1 (TS p.91 / EN p.88): range pipe diameters shall comply with Table 30 and distribution pipe diameters with Table 31.

Table 30 - OH range pipes:

Range pipes Layout Diameter Maximum sprinklers fed
Last 2 ranges at the far end of all distribution pipes 2-end-side 25 mm 1
32 mm 2
Last 3 ranges 3-end-side 25 mm 2
Last range 32 mm 3
All other layouts 25 mm 2
32 mm 3
40 mm 4
50 mm 9
All other range pipes All 25 mm 3
32 mm 4
40 mm 6
50 mm 9

Table 31 - OH distribution pipes:

Distribution pipes Layout Diameter Maximum sprinklers fed
At the ends of the installation 2-end-side 32 mm 2
40 mm 4
50 mm 8
65 mm 16
Others 32 mm 3
40 mm 6
50 mm 9
65 mm 18
Between the design points and the control valve set All Calculated in accordance with Clause 13.3.4.2

The continuation of Clause 13.3.4.1 (TS p.92 / EN p.89): where range pipes run longitudinally beneath roofs with a slope greater than 6°, the number of sprinklers on a range pipe shall not exceed six.

Clause 13.3.4.2: the pipe diameters between the design point in the most remote area of the installation and the control valve set shall be calculated such that the total pressure loss due to friction at a flow of 1 000 l/min does not exceed 0.5 bar. Clause 13.3.4.3 states that this 0.5 bar may be increased by the static height difference in multi-storey buildings; Clause 13.3.4.4 states that where OH3/OH4 and HHP/HHS areas on the same system are connected to a common water supply, the maximum friction loss may be increased by 50 per cent of the excess pressure available, and gives an example.

Design point, Table 26 (Clause 13.3.2.3, TS p.89 / EN p.86):

Hazard class Number of sprinklers on one distribution pipe in the room Design point at the connection of the range carrying the nth sprinkler Range layout
OH > 16 17 two end-side
OH > 18 19 others
HHP and HHS > 48 49 all

HH: four tables, two pairings

In high hazard, the choice of table depends on which block of Table 7 the water supply complies with and on the sprinkler K-factor.

Clause 13.3.5.2 (TS p.92 / EN p.89): on installations where the water supply complies with Table 7 (1) and the K-factor is 80, the range and distribution pipe diameters are taken from Table 32 and Table 33. Not more than four sprinklers shall be fitted to any range pipe; range pipes shall not be connected to distribution pipes of a diameter greater than 150 mm.

Table 32 - HH range pipes (Table 7 (1) or (2)):

Range pipe Layout Diameter Maximum sprinklers fed
Ranges at the far end of all distribution pipes 2-end-side, last two ranges 25 mm 1
32 mm 2
3-end-side, last three ranges 25 mm 2
32 mm 3
All other layouts, last range only 25 mm 2
32 mm 3
40 mm 4
All other ranges Any 25 mm 3
32 mm 4

Table 32 contains only the 25, 32 and 40 mm rows; 50 mm and above do not appear in that table.

Table 33 - distribution pipes with Table 7 (1) (TS p.93 / EN p.90): at the ends of the installation, 32 mm 2, 40 mm 4, 50 mm 8, 65 mm 12, 80 mm 18, 100 mm 48 sprinklers.

Clause 13.3.5.3 (TS p.93 / EN p.90): on installations where the water supply complies with Table 7 (2) (or as modified by Clause 7.3.2.6) and the K-factor is 80, the sizes are determined from Table 32 and Table 34. Not more than four sprinklers are fitted to a range pipe; no range pipe is connected to a distribution pipe exceeding 150 mm; on 4-end-side systems, distribution pipes smaller than 65 mm are not used.

Table 34 - distribution pipes with Table 7 (2, 3 or 4) (TS p.94 / EN p.91): at the ends of the system, 50 mm 4, 65 mm 8, 80 mm 12, 100 mm 16, 150 mm 48 sprinklers.

Clause 13.3.5.4 (TS p.94 / EN p.91): on installations where the water supply satisfies the requirements of Table 7 (3) and the K-factor is 80, and on installations with a K-factor of 115 as shown in Table 7 (4), the range and distribution pipe sizes are determined from Table 34 and Table 35. Not more than six sprinklers are fitted to a range pipe in an end-side layout, and not more than four in a 2-end-centre layout.

Table 35 - HH range pipes (Table 7 (3) or (4), TS p.95 / EN p.92):

Range pipes Layout Diameter Maximum sprinklers fed
Ranges at the far end End-side, last three ranges 40 mm 1
50 mm 3
65 mm 6
Other ranges 32 mm 1
40 mm 2
50 mm 4
65 mm 6
Ranges at the far end 2-end-centre, last three ranges 32 mm 1
40 mm 2
Other ranges 32 mm 2
All ranges 3 and 4 end-centre 32 / 40 / 50 mm 1 / 2 / 4

Clause 13.3.5.5: the pressure loss between the design points and the control valve set is determined by calculation. The pressure loss occurring at the flows in Table 7, plus the pressure required at the design point, plus the static pressure equal to the height difference between the highest sprinkler and the control valve set, shall not exceed the pressure available.

The mathematics of the calculation

Clause 13.2.1 (TS p.85-86 / EN p.82-83): pipe friction loss calculations shall not be less than those derived from the Hazen-Williams formula:

p = 6.05 x 10⁵ x L x Q^1.85 / (C^1.85 x d^4.87)

where p is in bar, Q in l/min, d in mm (mean internal diameter), C is a constant depending on the type and condition of the pipe, and L is the equivalent length of pipe and fittings (m). Velocity pressure loss may be neglected.

Table 22 - values of C (TS p.86 / EN p.83): cast iron 100; ductile iron 110; mild steel 120; galvanized steel 120; spun cement 130; cement lined cast iron 130; stainless steel 140; copper 140; glass fibre reinforced 140.

The exponent d^4.87 in the formula shows the effect of a change in diameter. Table 29 of the standard itself (LH, 225 l/min column) gives the numerical equivalent: 198 mbar/m at 25 mm against 52 mbar/m at 32 mm, so going up one size reduces the loss to roughly a quarter.

Clause 13.2.4 and Table 23 (TS p.87 / EN p.84) give the losses at fittings and valves as equivalent lengths; where both the direction and the diameter change at an elbow, tee or cross, the equivalent length and pressure loss are determined on the basis of the smaller diameter.

Diameter rules on the material and workmanship side

The second check on the diameter: pressure and velocity

The pipe diameter has to pass not only the table but two upper limits as well:

Field note: because all of the tables are written in terms of a "maximum number of sprinklers", a single sprinkler added to a range later in the project can push that range up one diameter; on revisions, looking at the table before the calculation saves time.

Frequently Asked Questions

What is the minimum pipe diameter in EN 12845?

Table 36 (Clause 13.4.5, TS p.106 / EN p.103): 20 mm for an LH risk; 20 mm for horizontal and upright pipe feeding a single sprinkler with a K-factor not exceeding 80 in OH and HH; 25 mm in all other cases. In addition, Clause 13.3.5.1 states that no pipe in high hazard shall be of a nominal diameter smaller than 25 mm.

May the pipe diameter increase in the direction of flow?

No. Clause 13.3.1.1 (TS p.88 / EN p.85) states that on pre-calculated systems the pipe diameters shall not increase in the direction of water flow towards any sprinkler. Clause 13.4.5 states that pipe diameters on the installation side of the control valve set may only reduce in the direction of water flow, grid and loop configurations being the exception.

Up to what diameter may upright and pendent sprinklers be connected directly?

Clause 13.4.5 (TS p.106 / EN p.103): upright sprinklers shall not be connected to any pipe of a diameter greater than 65 mm, or 50 mm where the pipe is lagged. Pendent sprinklers shall not be connected directly to any pipe of a diameter greater than 80 mm. For larger diameters, an arm pipe is fitted such that the distance from the sprinkler deflector to the side of the main pipe is not less than 1.5 times the diameter of that pipe.

How many sprinklers may be connected to a range pipe in OH?

Table 30 (TS p.91 / EN p.88): on all other range pipes, 25 mm feeds 3, 32 mm 4, 40 mm 6 and 50 mm 9 sprinklers. On the last two ranges at the far end of all distribution pipes (2-end-side layout), 25 mm feeds 1 and 32 mm 2; on the last three ranges in a 3-end-side layout, 25 mm feeds 2 and the last range in 32 mm feeds 3; in all other layouts, 25 mm feeds 2, 32 mm 3, 40 mm 4 and 50 mm 9 sprinklers.

Which tables apply where K115 sprinklers are used in HH?

Clause 13.3.5.4 (TS p.94 / EN p.91): on installations where the water supply satisfies the requirements of Table 7 (3) and the K-factor is 80, and on installations with a K-factor of 115 as shown in Table 7 (4), the range and distribution pipe sizes are determined from Table 34 and Table 35. Table 35 gives the range pipes and Table 34 the distribution pipes. Not more than six sprinklers are fitted to a range pipe in an end-side layout, and not more than four in a 2-end-centre layout.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.