Short answer: Table 19 (Clause 12.2, TSE p.73 / EN p.70): for HHP and HHS the maximum area per sprinkler is 9.0 m2, with S and D of 3.7 m maximum in standard layout and 3.7 m maximum for S and D in staggered layout as well. There is no separate, smaller value for HHS.

Source: TS EN 12845+A2:2026 (EN 12845:2015+A2:2026), Clauses 7.3.2, 12.2, 13.1, 13.3.5, 13.4.4 and Tables 7, 19, 32, 33, 34, 35.

In the high hazard class, pre-calculated design does not rest on a single pipe table as it does in LH and OH, but on a pair of tables that depends on which block of Table 7 the water supply conforms to. For the same density there are four different combinations of pipe tables and four different required pressures. This article deals with that matching and with its limits.

First the limit: when pre-calculation is not allowed

Clause 13.1 (TSE p.85 / EN p.82) says pipe sizes shall be determined by one of two methods: pre-calculated systems (13.3), where some of the sizes are taken from tables and some are calculated, and fully calculated systems (13.4), where all sizes are determined by hydraulic calculation. The designer may choose between the two; but full calculation shall always be used in two cases:

Clause 7.2.3.4 (TSE p.40 / EN p.37) says the same thing from the storage side: in-rack sprinklers and their associated ceiling sprinklers shall always be fully calculated. The note to the clause recalls the minimum pressure: the minimum pressure at any operating sprinkler is 2.0 bar (13.4.4).

The heading of Clause 13.3.5 repeats it too: "High hazard - HHP and HHS (excluding intermediate sprinklers)".

Four parameters: Clause 13.3.5.1

Clause 13.3.5.1 (TSE p.92 / EN p.89) lists in four items what determines the pipe size:

  1. the design density,
  2. the spacing of the sprinklers,
  3. the K-factor of the sprinklers used,
  4. the pressure/flow characteristic of the water supply.

And a single absolute lower limit: no pipe shall have a nominal diameter smaller than 25 mm.

The water supply: the four blocks of Table 7

Clause 7.3.2.1 (TSE p.43 / EN p.40): the water supply shall be capable of providing not less than the flow and pressure specified in Table 7 at the highest design point. Table 7 gives the pressure at the highest design point (pd) according to the area of operation per sprinkler (6, 7, 8 or 9 m²) and is divided into four blocks:

Block Pipe size tables K-factor
Table 7 (1) Tables 32 and 33 K80
Table 7 (2) Tables 32 and 34 K80
Table 7 (3) Tables 35 and 34 K80
Table 7 (4) Tables 35 and 34 K115

The maximum demand flows of Table 7 depend on the density, not on the block. Example rows (TSE p.43 / EN p.40):

Design density (mm/min) Maximum demand flow, wet/pre-action (l/min) Maximum demand flow, dry/alternate (l/min)
7.5 2 300 2 900
10.0 3 050 3 800
12.5 3 800 4 800
15.0 4 550 5 700
20.0 6 400 8 000
25.0 8 000 10 000
30.0 9 650 12 000

At the same density the required pressure falls as the block changes. For 10.0 mm/min and 9 m² per sprinkler: Table 7 (1) → 3.90 bar, Table 7 (2) → 3.00 bar, Table 7 (3) → 1.60 bar, Table 7 (4) with K115 → 0.95 bar. In other words, larger pipe tables (34, 35) and a larger K-factor let you achieve the same density with a lower supply pressure.

The note to Table 7: where there are sprinklers in the array higher than the design point, the static head from the design point up to the highest sprinklers shall be added to pd.

Matching rules and range pipe limits

Clause 13.3.5.2: Table 7 (1) with K80

In installations whose water supplies conform to Table 7 (1) and whose sprinklers have a K-factor of 80, Table 32 (range) and Table 33 (distribution) apply. No more than four sprinklers shall be connected to any range pipe. Range pipes shall not be connected to distribution pipes of a diameter greater than 150 mm.

Clause 13.3.5.3: Table 7 (2) with K80

In installations whose water supplies conform to Table 7 (2) (or are modified by 7.3.2.6) and which use K80 sprinklers, Table 32 and Table 34 are used. Again, a maximum of four sprinklers per range; range pipes shall not be connected to distribution pipes exceeding 150 mm. An additional constraint: in 4-end-side systems no distribution pipe of a diameter smaller than 65 mm shall be used.

Clause 13.3.5.4: Table 7 (3) with K80 or Table 7 (4) with K115

Table 34 and Table 35 are used. Here the number of sprinklers per range depends on the arrangement:

Range pipes shall not be connected to distribution pipes greater than 150 mm and, in 4-end-side systems, no distribution pipe smaller than 65 mm shall be used.

The pipe size tables

Table 32 - Range pipe sizes (for Table 7 (1) or (2)), TSE p.93 / EN p.90:

Range pipes Arrangement Diameter (mm) Maximum number of sprinklers fed
Ranges at the remote end of all distribution pipes 2-end-side, last two ranges 25 1
32 2
3-end-side, last three ranges 25 2
32 3
All other arrangements, last range only 25 2
32 3
40 4
All other ranges Any 25 3
32 4

Table 33 - Distribution pipe sizes downstream of the design point (for Table 7 (1)), TSE p.93 / EN p.90:

Distribution pipe Diameter (mm) Maximum number of sprinklers fed
Pipes at the ends of the installation 32 2
40 4
50 8
65 12
80 18
100 48
Between the design points and the control valve set Calculated in accordance with 13.3.5

Table 34 - Distribution pipe sizes downstream of the design point (for Table 7 (2), (3) or (4)), TSE p.94 / EN p.91:

Distribution pipe Diameter (mm) Maximum number of sprinklers fed
Pipes at the ends of the system 50 4
65 8
80 12
100 16
150 48
Between the design points and the control valve set Calculated in accordance with 13.3.5

Table 35 - Range pipe sizes (for Table 7 (3) or (4)), TSE p.95 / EN p.92:

Range pipes Arrangement Diameter (mm) Maximum number of sprinklers fed
Ranges at the remote end of all distribution pipes End-side, last three ranges 40 1
50 3
65 6
Other ranges 32 1
40 2
50 4
65 6
Ranges at the remote end of all distribution pipes 2-end-centre, last three ranges 32 1
40 2
Other ranges 32 2
All ranges 3- and 4-end-centre 32 1
40 2
50 4

The design point and everything above it

Clause 13.3.2.1 (TSE p.88 / EN p.85): the design point is located where a horizontal distribution pipe connects to a range pipe, to a riser or drop pipe connecting ranges to the distribution pipe, or to a pipe feeding a single sprinkler.

Table 26 (TSE p.89 / EN p.86) gives the position of the design point for HH: where there are more than 48 sprinklers on one distribution pipe in a room, the design point is at the junction with the distribution pipe of the range carrying the 49th sprinkler, and this applies to all range arrangements.

Clause 13.3.5.5 (TSE p.95 / EN p.92) binds everything above the design point: the pressure loss between the design points and the control valve set shall be determined by calculation. The sum of the pressure loss at the flows shown in Table 7, the pressure required at the design point and the static pressure equal to the height difference between the highest sprinkler and the control valve set shall not exceed the available pressure. Where the highest sprinkler is upstream of the design point, the section requiring the higher static head shall have its own distribution pipe. Pressure losses in the distribution pipes feeding each section of the risk may be balanced by sizing the distribution pipe appropriately.

Sprinkler layout and type

Table 19 (Clause 12.2, TSE p.73 / EN p.70) gives a single row for HHP and HHS:

Hazard class Maximum area per sprinkler (m²) Standard layout S and D (m) Staggered layout S (m) Staggered layout D (m)
HHP and HHS 9.0 3.7 3.7 3.7

There is no separate 7.5 m² value for HHS. Under Clause 12.4.1, the maximum distance to walls and partitions shall not exceed half of the maximum distance in Table 19, that is 1.85 m, nor the other values listed in the clause; the smallest of these values is selected.

Clause 12.1.2 (TSE p.73 / EN p.70): in HHP and HHS a clear space of at least 1.0 m shall be maintained below the deflector of ceiling and roof sprinklers.

Table 37a (TSE p.107 / EN p.104) binds the sprinkler type and the K-factor:

Hazard class Design density (mm/min) Sprinkler type Nominal K-factor
HHP and HHS ceiling/roof sprinklers ≤ 10 conventional, spray 80, 115 or 160
HHP and HHS ceiling/roof sprinklers > 10 conventional, spray 115 or 160
HHS in-rack intermediate sprinklers in high stacks - conventional, spray, flat spray 80 or 115

Clause 14.2.2 (TSE p.107 / EN p.104): ceiling, flush, recessed and concealed sprinklers shall not be installed in OH4, HHP or HHS areas. Clause 14.2.3: in HH installations sidewall sprinklers may be used only for the protection of corridors, cable ducts and columns.

Minimum pressure

Clause 13.4.4 (TSE p.105 / EN p.102) binds the pressure at the hydraulically most unfavourable sprinkler while all sprinklers in the area of operation are operating. The pressure required to achieve the design density applies, or the following values, whichever is the higher:

Frequently Asked Questions

What is the maximum area of coverage per sprinkler in HHP and HHS?

Table 19 (Clause 12.2, TSE p.73 / EN p.70): for HHP and HHS the maximum area per sprinkler is 9.0 m2, with S and D of 3.7 m maximum in standard layout and 3.7 m maximum for S and D in staggered layout as well. There is no separate, smaller value for HHS.

On what basis are the pipe size tables selected in pre-calculated HH design?

Clauses 13.3.5.2, 13.3.5.3 and 13.3.5.4 (TSE p.92-94 / EN p.89-91) match them to the block of Table 7 that the water supply conforms to, and to the K-factor. Table 7 (1) with K80: Tables 32 and 33. Table 7 (2) with K80: Tables 32 and 34. Table 7 (3) with K80 or Table 7 (4) with K115: Tables 34 and 35.

How many sprinklers may be connected to a range pipe in HH?

Where Tables 32 and 33 apply, no more than four sprinklers shall be connected to a range pipe (13.3.5.2). Where Tables 34 and 35 apply, a maximum of six sprinklers may be connected in end-side arrangements and a maximum of four in 2-end-centre arrangements (13.3.5.4).

What is the minimum sprinkler operating pressure in HHP and HHS?

Clause 13.4.4 (TSE p.105 / EN p.102): 0.50 bar in HHP and HHS excluding in-rack sprinklers. For in-rack sprinklers it is 1.00 bar for K115 and 2.00 bar for K80.

Can systems with in-rack intermediate level sprinklers be pre-calculated?

No. Clause 13.1 (TSE p.85 / EN p.82) requires full calculation at all times for layouts with HHS intermediate sprinklers, and Clause 7.2.3.4 also requires in-rack sprinklers and their associated ceiling sprinklers to be always fully calculated. The heading of Clause 13.3.5 likewise says excluding intermediate sprinklers.

References


SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.