Short answer: TS EN 12845+A2:2026 Clause 8.1.1 (EN p.42): LH 30 minutes, OH 60 minutes, HHP 90 minutes, HHS 90 minutes. The NOTE states that for town mains, inexhaustible sources and all pre-calculated systems the duration is implicit in the other requirements of the standard.

A sprinkler water supply has three independent qualities: adequate flow and pressure (Clause 7), adequate duration (Clause 8.1.1) and uninterrupted availability (Clauses 8.1.2 and 8.1.3). This article collects the second and third of these, that is the provisions on duration, continuity and frost protection, from the standard's own text. Source: TS EN 12845+A2:2026, Clause 8.1, EN p.42 (TSE p.45).

1. Duration (Clause 8.1.1)

Clause 8.1.1 (EN p.42) first sets the general requirement: "Water supplies shall be capable of providing the required pressure/flow conditions of the system at least automatically." It then gives the durations. Where the water supply is also used for other fire fighting systems, reference is made to Clause 9.6.4; except in the cases specified for pressure tanks, each water supply shall have sufficient capacity for the following minimum durations:

Hazard class Minimum duration
LH 30 minutes
OH 60 minutes
HHP 90 minutes
HHS 90 minutes

Source: Clause 8.1.1, EN p.42 (TSE p.45).

The NOTE to the clause introduces an important exemption: "For town mains, inexhaustible sources and all pre-calculated systems, the duration is implicit in the requirements given in this standard." In other words, in a pre-calculated system the volume from Table 9 or Table 10 already includes the duration; no further multiplication is made.

2. Water volume (Clause 9.3.2)

Fully calculated systems

Clause 9.3.2.3 (EN p.48) is a single sentence: "The minimum effective water volume shall be calculated by multiplying the maximum demand flow (Qmax) by the duration specified in 8.1.1."

V_min = Q_max x t

Here Q_max is the maximum demand flow from the hydraulic calculation and t is the duration from Clause 8.1.1. The standard adds no hose reel or fire brigade allowance to this formula; there is no provision in TS EN 12845+A2 adding a hose allowance to the sprinkler design flow.

Pre-calculated LH and OH systems: Table 9

The water volumes specified in Table 9 are reserved for the use of the sprinkler system only.

Group Height h of the highest sprinkler above the lowest sprinkler Minimum water volume (m³)
LH (wet or pre-action) h ≤ 15 m 9
LH (wet or pre-action) 15 < h ≤ 30 m 10
LH (wet or pre-action) 30 < h ≤ 45 m 11
OH1 wet or pre-action h ≤ 15 m 55
OH1 wet or pre-action 15 < h ≤ 30 m 70
OH1 wet or pre-action 30 < h ≤ 45 m 80
OH1 dry/alternate; OH2 wet or pre-action h ≤ 15 m 105
OH1 dry/alternate; OH2 wet or pre-action 15 < h ≤ 30 m 125
OH1 dry/alternate; OH2 wet or pre-action 30 < h ≤ 45 m 140
OH2 dry/alternate; OH3 wet or pre-action h ≤ 15 m 135
OH2 dry/alternate; OH3 wet or pre-action 15 < h ≤ 30 m 160
OH2 dry/alternate; OH3 wet or pre-action 30 < h ≤ 45 m 185
OH3 dry/alternate; OH4 wet or pre-action h ≤ 15 m 160
OH3 dry/alternate; OH4 wet or pre-action 15 < h ≤ 30 m 185
OH3 dry/alternate; OH4 wet or pre-action 30 < h ≤ 45 m 200
OH4 dry or alternate - Use HH protection

Source: Table 9, Clause 9.3.2.2, EN p.47 (TSE p.50). NOTE: sprinklers in the sprinkler valve room are excluded.

Pre-calculated HHP and HHS systems: Table 10

Design density not exceeded (mm/min) Wet systems (m³) Dry systems (m³)
7.5 225 280
10.0 275 345
12.5 350 440
15.0 425 530
17.5 450 560
20.0 575 720
22.5 650 815
25.0 725 905
27.5 800 1 000
30.0 875 1 090

Source: Table 10, Clause 9.3.2.2, EN p.48 (TSE p.51).

For comparison: a design density of 12.5 mm/min corresponds, according to Table 7 (Clause 7.3.2.1, EN p.40), to a maximum demand flow of 3 800 l/min in a wet or pre-action system and 4 800 l/min in a dry or alternate system. With the 90 minute HHS duration, 3 800 x 90 = 342 000 litres = 342 m³; the value of 350 m³ in Table 10 remains above that.

Reduced capacity tank

Clause 9.3.2.1 (EN p.47) states that the minimum volume can be provided in two ways: a full capacity tank whose effective capacity is at least equal to the specified water capacity, or a reduced capacity tank in which the required water volume is provided jointly by the effective capacity of the tank plus an automatic infill (see Clause 9.3.4).

Clause 9.3.4 (EN p.48) sets five conditions for a reduced capacity tank:

Hazard class Minimum effective capacity (m³)
LH (wet or pre-action) 5
OH1 wet or pre-action 10
OH1 dry/alternate; OH2 wet or pre-action 20
OH2 dry/alternate; OH3 wet or pre-action 30
OH3 dry/alternate; OH4 wet or pre-action 50
HHP and HHS 70 (but in no case less than 10 % of the full capacity)

Source: Table 11, Clause 9.3.4, EN p.49 (TSE p.52).

Infill rate

Clause 9.3.3 (EN p.48): for full capacity tanks the water supply shall be capable of refilling the tank in not more than 36 hours. The outlet of the supply pipe shall be at least 2.0 m horizontally from the inlet of the suction pipe.

3. Continuity (Clause 8.1.2)

Clause 8.1.2 (EN p.42) regulates the availability of the water supply:

In addition, Clause 8.4 (EN p.44) imposes a housing prohibition: water supply equipment such as pumps, pressure tanks and gravity tanks shall not be housed in buildings or parts of premises containing hazardous processes or explosion risks. Water supplies, stop valves and control valve sets are installed so that they can be reached safely even in the event of fire. All components are secured against interference and adequately protected against freezing.

Clause 9.7 (EN p.57) regulates the isolation of the supplies from each other: a problem or maintenance on one supply shall not disturb the operation of another supply.

4. Frost protection

Frost protection appears in four separate places in the standard.

a) Supply pipe and control valve

Clause 8.1.3 (EN p.42): "The supply pipe and the control valve set shall be maintained at a minimum temperature of 4 °C."

b) Equipment rooms

Location Minimum temperature Source
Pressure tank and its housing 4 °C Clause 9.5.2, EN p.54
Electric pump set compartment 4 °C Clause 10.3.3, EN p.58
Diesel pump set compartment 10 °C Clause 10.3.3, EN p.58

Clause 9.5.2 also requires the pressure tank to be housed in one of three places: a sprinkler protected building; a separate, sprinkler protected building of Euroclass A1 or A2 construction (or the equivalent) used only to house fire protection water supplies and equipment; or an unprotected building located in a compartment with 60 minutes fire resistance and containing no combustible material. Where the pressure tank is housed in a sprinkler protected building, the area is enclosed by construction with a fire resistance of at least 30 minutes.

c) Storage tank

Clause 9.3.2.1 (EN p.47): "Where the tank is not frost resistant, the normal water level shall be raised by at least 1.0 m and ice venting shall be provided." Ready access shall be provided for closed tanks. Except for open reservoirs, tanks are fitted with a water level indicator readable from outside.

d) Pipework: three methods

Clause 11.1.2.1 (EN p.66): "Parts of the installation subject to freezing may be protected by antifreeze solution, by electrical trace heating or by subsidiary dry pipe or alternate extensions (see 11.5)."

Antifreeze solution (Clause 11.1.2.2, EN p.66):

Clause 11.1.2.2 does not specify the type of antifreeze; neither propylene glycol nor any other chemical is named.

Electrical trace heating (Clause 11.1.2.3, EN p.66-67):

Subsidiary dry/alternate extension (Clause 11.5, EN p.69): installed as a dry or alternate extension to a wet installation in small areas liable to frost damage within an otherwise adequately heated building; or as a dry pipe extension to a wet or alternate installation in cold stores and in high temperature ovens or furnaces. The number of sprinklers per extension shall not exceed 100, and where more than two extensions are controlled by one control valve set, the total shall not exceed 250 (Clause 11.5.2).

The limit for the wet installation itself is in Clause 11.1.1 (EN p.66): wet pipe installations are installed only in locations where there is no possibility of frost damage to the installation and where the ambient temperature will not exceed 95 °C. Dry pipe installations are installed only in locations where there is a possibility of frost damage or where the temperature exceeds 70 °C (for example drying ovens) (Clause 11.2.1, EN p.67).

5. The counterparts on the maintenance side

Interval Activity Source
Weekly All water levels are checked and recorded: elevated private reservoirs, rivers, canals, lakes, water storage tanks (including pump priming water tanks and pressure tanks) Clause 20.2.2.2 b, EN p.119
Weekly Heating systems that prevent freezing are checked for correct operation Clause 20.2.2.6, EN p.120
Annually The ball valves in water storage tanks are checked for correct operation Clause 20.3.4.4, EN p.122
3 yearly All tanks, except those designed to need no maintenance within 10 years (see 9.6.2 b), are internally inspected, emptied and cleaned if necessary, examined for corrosion, repainted and/or their corrosion protection renewed Clause 20.3.5.2, EN p.122
10 yearly At intervals of not more than 10 years, all storage tanks are cleaned and internally inspected, and the structure is treated as required Clause 20.3.6, EN p.122

Frequently Asked Questions

What are the water supply durations in EN 12845?

TS EN 12845+A2:2026 Clause 8.1.1 (EN p.42): LH 30 minutes, OH 60 minutes, HHP 90 minutes, HHS 90 minutes. The NOTE states that for town mains, inexhaustible sources and all pre-calculated systems the duration is implicit in the other requirements of the standard.

How is the tank volume determined for a fully calculated system?

Clause 9.3.2.3 (EN p.48): the minimum effective water volume is calculated by multiplying the maximum demand flow (Qmax) by the duration specified in Clause 8.1.1. For pre-calculated LH and OH systems Table 9 is used, and for pre-calculated HHP and HHS systems Table 10.

What is done if the tank is not protected against frost?

Clause 9.3.2.1 (EN p.47): where the tank is not frost resistant, the normal water level shall be raised by at least 1.0 m and ice venting shall be provided. The effective capacity of the tank is calculated as the difference between the normal water level and the lowest effective water level.

At what temperature are the supply pipe and control valve set kept?

Clause 8.1.3 (EN p.42): the supply pipe and the control valve set shall be maintained at a minimum temperature of 4 °C. Clause 9.5.2 (EN p.54) also requires at least 4 °C for the pressure tank and its housing. For the pump set compartment Clause 10.3.3 (EN p.58) requires 4 °C for electric and 10 °C for diesel.

What sprinkler count limits apply when antifreeze is used?

Clause 11.1.2.2 (EN p.66): the number of sprinklers in any section of pipe protected by antifreeze solution shall not exceed 20. Where one control valve set controls more than two antifreeze sections, the total number of sprinklers in the antifreeze sections shall not exceed 100. The freezing point of the solution shall be below the expected minimum temperature of the location, the specific gravity of the prepared solution shall be checked with a suitable hydrometer, and backflow prevention devices shall be fitted to prevent contamination of the water.

How quickly must the tank be refilled?

Clause 9.3.3 (EN p.48): for full capacity tanks the water supply shall be capable of refilling the tank in not more than 36 hours. The outlet of the supply pipe shall be at least 2.0 m horizontally from the inlet of the suction pipe.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.