Short answer: EN 12845-2:2024 Table 6 (EN p. 34) gives the shape of the design area as sprinklers x range pipe. For a 12 sprinkler design the shape is 4 x 3, that is 4 sprinklers per range pipe on 3 range pipes. The shapes given are 3 x 3 for 9 sprinklers, 5 x 3 for 15 sprinklers, 5 x 4 for 20 sprinklers, 6 x 4 for 24 sprinklers and 7 x 4 + 2 x 1 for 30 sprinklers. Clause 6.6.1.2 (EN p. 38) also states that the 9 sprinkler design area is 3 sprinklers on each of 3 adjacent range pipes and the 10 sprinkler design is 3 sprinklers on each of 3 adjacent range pipes plus 1 sprinkler on a further range pipe.

Source: EN 12845-2:2024 Clause 6 (EN p. 33-48) and TS EN 12845+A2:2026 Clauses 13.4 and 14.3 (EN p. 98-105).

ESFR design works differently from the CMDA density and area logic of EN 12845: no density is calculated, the k-factor, the number of sprinklers and the minimum operating pressure are read from a table. This article follows the order of EN 12845-2 itself.

Step 1: commodity class and storage configuration

Clause 4 (EN p. 6) requires Annex A to be applied for the determination of FH and HHS. Annex A (normative, EN p. 59) gives both the conversion table from the EN 12845:2015 classes (Table A.1) and the classification flow chart for storage commodities containing plastics (Figure A.1). The classes are HHS1-HHS5 for storage and FH1-FH5 for non storage occupancies.

Clause 6.1 (EN p. 33) sets three critical rules:

The same clause states that, unless otherwise indicated, the HHS3 protection category is used for HHS1 and HHS2, that the protection of higher categories may be used to protect lower categories, and that a k-factor design given for a particular ceiling height may also be applied to a lower ceiling height provided no other parameter changes.

Clause 6.2 (EN p. 33): ESFR and CMSA protection shall not be applied to FH3-FH5 occupancies. Where they are used for FH1 and FH2 hazards, they are designed as HHS1-HHS3 in accordance with 6.6 or 6.7, independently of the storage category.

Step 2: suitability of the building

Before moving to the design table, the limits of Clause 5.2 have to be met:

Subject Clause Requirement
Ceiling slope 5.2.1 (EN p. 12) Maximum 10 degrees (17.6 %); if exceeded, one of three options
Ceiling strength 5.2.2 (EN p. 12) Withstand a vertical upward thrust of 140 N/m²
Skylights 5.2.3 (EN p. 13) Withstand 300 °C for at least 5 min; protection if volume > 1 m³; exemption if the distance to the top is ≤ 0.3 m
Heat and smoke vents 5.2.4 (EN p. 16) Manual only; drop-out type prohibited; if automatic vents are required, one of three solutions
Horizontal air flow 5.2.6.1 (EN p. 18) Velocity at the ceiling sprinklers ≤ 1.5 m/s or automatic shutdown on early detection
Vertical air flow 5.2.6.2 (EN p. 20) Velocity between the top of the storage and the plane of the ceiling sprinklers ≤ 1.5 m/s; if exceeded, six options
Solid mezzanines 5.2.7 (EN p. 20) Quick response or ESFR sprinklers beneath them

Step 3: placement

Clause 5.1.3.2 (EN p. 8): minimum spacing 2.4 m; maximum spacing 3.7 m for ceilings ≤ 9.1 m and 3.1 m for ceilings > 9.1 m; maximum area per sprinkler 9.3 m², minimum area 6 m²; distance to a wall at most 50 % of the maximum spacing. Clause 5.1.3.5.2 and Table 2 (EN p. 9-10): the deflector at least 100 mm below the ceiling; the maximum vertical distance of the thermal element is 325 mm for ESFR K200, K240 and K400 and 425 mm for K320, K360 and K480. Clause 5.1.3.7 (EN p. 12): a clear space of at least 1 m between the deflector and the top of the storage.

Step 4: choosing the design table

Clause 6.6.1.1 (EN p. 35): Table 7 gives the design criteria for ESFR ceiling only protection and is based on the ceiling height; the designs are generally based on 12 heads. For this table, Clause 5.2.6.1 (horizontal air flow) and Clause 5.3.3.2.2 (obstructions above racks) do not apply. Table 8 belongs to rubber tyre storage and Table 9 to roll paper storage stored on end and free standing.

Table 7, minimum pendent operating pressures (bar), EN p. 36:

Commodity class Maximum ceiling (m) Maximum storage (m) K200 K240 K320 K360 K400 K480
HHS1-HHS3 7.6 6.1 3.4 2.4 1.7 1.0 - -
HHS1-HHS3 9.1 7.6 3.4 2.4 1.7 1.0 - -
HHS1-HHS3 10.7 9.1 5.2 3.6 2.4 1.4 - -
HHS1-HHS3 12.2 10.7 - 3.6 2.8 1.7 - -
HHS1-HHS3 13.7 12.2 - - 2.8 2.8 - -
HHS1-HHS3 15.2 13.3 - - - - 2.8 3.8
HHS1-HHS3 16.8 14.9 - - - - 5.5 3.8
HHS4 7.6 6.1 3.4 2.4 5.2 4.1 - -
HHS4 9.1 7.6 3.4 2.4 5.2 4.1 - -
HHS4 10.7 9.1 - - 5.2 4.1 - -
HHS4 12.2 10.7 - - 5.2 4.1 - -
HHS5 9.1 7.6 - - - 2.0 - -
HHS5 12.2 10.7 - - - 4.1 - -

Footnotes: the minimum aisle width is 1.8 m in the 15.2 m row and 2.4 m in the 16.8 m / K400 row. The HHS5 rows apply only to exposed expanded plastics and only where all the additional requirements (including the vertical barriers) are applied.

Tables 10 and 11 (designs with special requirements, EN p. 41): these tables are used together with the additional conditions of Clause 6.6.1.2 and give the number of sprinklers along with the pressure. Examples: HHS1-HHS3, ceiling 7.6 m, K200, 9 sprinklers at 2.4 bar; ceiling 12.2 m, K360, 9 sprinklers at 2.8 bar; HHS4, ceiling 9.1 m, K200, 15 sprinklers at 3.5 bar; HHS5, ceiling 12.2 m, K360, 20 sprinklers at 5.2 bar. Table 11 gives the K320, K360, K400 and K480 designs for ceiling heights of 15.2 m and 16.8 m, together with columns for the distance from the ceiling to the thermal element (325 or 425 mm) and the minimum aisle width (1.8 or 2.4 m).

The additional conditions of Clause 6.6.1.2 (EN p. 38): all requirements shall be met for the tables to be applied; Clause 5.2.6.1 always applies (it is no longer optional); where there is an obstruction above rack storage, the recommended approach of 5.3.3.2.2 is applied; the minimum design area shall be 71 m²; the 9 sprinkler design area is 3 sprinklers on each of 3 adjacent range pipes and the 10 sprinkler design is that plus 1 sprinkler on a further range pipe; and the ceiling is non-combustible and preferably unobstructed.

Step 5: duration and the shape of the design area

Table 6 (EN p. 34): for designs of 9, 10 and 12 sprinklers the duration of supply is 60 min; for 15 and 16 sprinklers 90 min; for 20, 24, 25 and 30 sprinklers 120 min. The shape of the design area is 4 × 3 for 12 sprinklers, that is 4 sprinklers per range pipe on 3 range pipes; 3 × 3 for 9 sprinklers; 5 × 3 for 15 sprinklers; 5 × 4 for 20 sprinklers.

Where the range pipes carry fewer sprinklers than the stated number, all the sprinklers are assumed to operate and the number of range pipes covered is increased to compensate. A favourable design area is not required, and pipe size reductions to limit the demand of a favourable hydraulic area are not permitted.

Step 6: hydraulic calculation

The flow formula is in EN 12845 Clause 14.3 (EN p. 104-105): Q = K√P, with Q in litres per minute and P in bar.

Example (arithmetic from the standard's values): HHS1-HHS3, ceiling 13.7 m, storage 12.2 m, K360 pendent. Table 7 gives a minimum of 2.8 bar.

The location of the design area is determined in accordance with EN 12845 Clause 13.4.2 (EN p. 99): the hydraulically most unfavourable position is found by taking account of all possible positions, together with changes in sprinkler spacing, layout, level, range pipe centres, sprinkler orifice size and pipe diameters.

Step 7: combining ceiling and in-rack protection

Clause 6.6.2 defines two different schemes:

Unheated areas

Clause 6.5 (EN p. 35): there is no dry installation option for this ESFR concept; where dry pendent ESFR sprinklers are used, the installation is considered a wet installation. Designs with propylene glycol are permitted provided that the k-factor is not less than 320, that the premixed antifreeze solution does not exceed 30 % glycol by volume and is manufactured specifically for sprinkler systems, and that tree type pipework is used. In the same K320 and larger systems, the glycol concentration may be raised to 40 % by volume if it can be demonstrated that water reaches a sprinkler within 60 s; after 60 s no more than 5 % glycol by volume may be present. The hydraulic calculation of the demand is based on a wet installation.

Frequently Asked Questions

What is the shape of the ESFR design area?

EN 12845-2:2024 Table 6 (EN p. 34) gives the shape of the design area as sprinklers x range pipe. For a 12 sprinkler design the shape is 4 x 3, that is 4 sprinklers per range pipe on 3 range pipes. The shapes given are 3 x 3 for 9 sprinklers, 5 x 3 for 15 sprinklers, 5 x 4 for 20 sprinklers, 6 x 4 for 24 sprinklers and 7 x 4 + 2 x 1 for 30 sprinklers. Clause 6.6.1.2 (EN p. 38) also states that the 9 sprinkler design area is 3 sprinklers on each of 3 adjacent range pipes and the 10 sprinkler design is 3 sprinklers on each of 3 adjacent range pipes plus 1 sprinkler on a further range pipe.

What is the minimum ESFR design area in square metres?

Clause 6.6.1.2 (EN p. 38): the minimum design area (number of sprinklers x spacing) shall be 71 m², the exception being where the obstructed construction requires a sprinkler in every channel. The upper bound follows from the maximum area per sprinkler: since Clause 5.1.3.2 allows at most 9.3 m² per ESFR sprinkler, a 12 sprinkler design gives at most 111.6 m².

How is the ESFR water demand calculated?

TS EN 12845+A2:2026 Clause 14.3 (EN p. 104-105): Q = K x square root of P, with Q in litres per minute and P in bar. The k-factor and the minimum operating pressure are read from Table 7, the flow per sprinkler is found with this formula, it is multiplied by the number of sprinklers in the design and converted into a volume using the duration of supply in Table 6. Example: for HHS1-HHS3 at a ceiling of 13.7 m with K360, Table 7 gives a minimum of 2.8 bar; the flow per sprinkler is 360 x square root of 2.8, about 602 L/min, about 7 229 L/min for 12 sprinklers and about 434 m³ for 60 minutes.

Which commodity classification is used for ESFR?

EN 12845-2:2024 Annex A (normative, EN p. 59) is used; the classes are HHS1-HHS5 for storage and FH1-FH5 for non storage occupancies. Annex A also gives the conversion table from the EN 12845:2015 classes (Table A.1) and the classification flow chart for storage commodities containing plastics (Figure A.1). Annex C of EN 12845 is the alphabetical list of stored products with their categories (Category I-IV) and serves the HHS1-HHS4 classification of EN 12845 itself.

Is K280 an ESFR k-factor?

No. The ESFR column of Table 2 (EN p. 10) contains K200, K240, K320, K360, K400 and K480. K280 appears only in the CMSA columns and is not found in the ESFR design tables (Table 7, Table 10, Table 11).

What is the difference between Table 7 and Tables 10 and 11?

Table 7 (EN p. 36) is the general design table and is generally based on 12 heads; for that table Clause 6.6.1.1 states that Clause 5.2.6.1 (horizontal air flow) and Clause 5.3.3.2.2 (obstructions above racks) do not apply. Tables 10 and 11 (EN p. 41) apply together with the additional special requirements of Clause 6.6.1.2: 5.2.6.1 always applies, for obstructions above racks the recommended approach of 5.3.3.2.2 is applied, and the ceiling is non-combustible and preferably unobstructed. In these tables the design number of sprinklers is given together with the pressure as 9, 10, 12, 15 or 20.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.