Turkey has 30,000 km of dual carriageway fed by 200+ asphalt plants. The rotary dryer brings aggregate to 150 °C and bitumen sits at 140-180 °C. Burners run LPG, diesel or natural gas. NFPA 87 covers fluid heaters, meaning equipment that heats a fluid indirectly (1.1); the bitumen heating system falls within it, while the rotary dryer, silo venting and deflagration venting are assessed separately.

Plant Main Units

  • Rotary dryer: 3-5 m dia x 10-15 m long
  • Burner: 10-40 MW
  • Hot aggregate silo: 150-180 °C
  • Bitumen tank: 50-200 m3, 160 °C
  • Baghouse: bag dust filter

Bitumen Hazard

  • Flash point: 218-280 °C (Class IIIB)
  • Storage temp: 160 °C
  • Ignition: at about 260 °C
  • Tank foam: NFPA 11 Annex A warns that foam on hot oil or burning asphalt tanks can cause violent frothing and slop-over, so apply with care
  • Heater coil: Hot oil safer

Rotary Dryer Risk

  • Deflagration vent: NFPA 68
  • Flame scanner: UV/IR
  • Purge: before ignition, as required by the applicable standard
  • BMS: the applicable standard depends on the plant (NFPA 85 covers boilers)

Baghouse Fire

  • Filter bag: PTFE 240 °C max
  • Aramid (Nomex): 200 °C
  • Sprinkler: dry pipe inside the baghouse
  • Spark detector: IR, at the inlet
  • Inlet gate: Quick isolation

Turkey Operators and Related Standards

  • KGM: 30,000 km asphalt network
  • Typical plants: 180-240 t/h
  • A single metropolitan area: 6 plants
  • Reference plant fire: Bitumen tank
  • Fluid heaters: NFPA 87
  • Burner management: NFPA 85
  • Deflagration venting: NFPA 68
  • Mix test methods: TS EN 12697

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 87, NFPA 85, NFPA 68, TS EN 12697, KGM (General Directorate of Highways). NFPA 87 Fluid Heaters.