Cogeneration/trigeneration plants run natural-gas turbines (heavy-duty frame and industrial units). On 50-100 MW class units, lube oil, fuel gas and high ambient temperatures create three separate fire risks. NFPA 37 (Stationary Combustion Engines and Gas Turbines) defines enclosure ventilation, CO2 protection and gas-detection rules.

Enclosure Ventilation

  • Emergency: close dampers just before CO2 release, otherwise the gas escapes
  • Purge: after discharge the agent and combustion products are removed by dilution ventilation, and the atmosphere is sampled before entry without breathing apparatus (NFPA 37, A.11.4.2.3).

CO2 Total Flooding

  • Concentration: taken from NFPA 12 Table 5.3.2.2 for the fuel involved (minimum design 34 percent for lube oil, 37 percent for natural gas).
  • Hold time: 20 min
  • Discharge: 1 min (surface fire)
  • Reserve: where uninterrupted protection is required, the reserve quantity is set by the authority having jurisdiction (NFPA 12, 4.6.1.2).
  • Alarm: pre-discharge alarm and a time delay long enough for personnel to evacuate (NFPA 12, 4.5.6.2.2).

Lube Oil System

  • Tank: 1,500-3,000 L, bearing cooling
  • Pump: AC + DC emergency pump
  • Level alarm: low-level shutdown
  • Fire detection: linear heat cable, IR3 flame detector
  • Water spray: over the lube oil tank and cooler; an NFPA 15 water spray system is the alternative

Natural Gas Regulator

  • Pressure reduction: 70 bar -> 30 bar -> 5 bar (turbine inlet)
  • ESDV: dual Emergency Shut-Down Valves
  • Gas detector: two threshold levels may be used; at the lower level ventilation is increased, at the higher level operation is shut down (NFPA 37, A.4.1.2.2.3).
  • PSV: over-pressure vent to safe location
  • Filter separator: removes liquid/solid particulates

Detection and Interlock

  • Vibration: bearing/compressor fault
  • Exhaust temp: alarm above 650°C
  • Hot gas path inspection: every 8,000 hours
  • Trip logic: the turbine is shut down as soon as CO2 activates

Gas turbine with MEP Calc

MEP Calc sizes gas turbine enclosure ventilation, CO2 total flooding and gas regulator per NFPA 37.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 37, NFPA 12, NFPA 54 Fuel Gas Code, ASME B31.3, API RP 556. NFPA 37 Combustion Engines standard.