In geothermal plants — both flash and binary cycle — the well fluid carries dissolved H2S, CO2 and methane. H2S can be lethal even at 50–100 ppm, and it is also flammable, with a lower flammable limit (LFL) of 4%. In geothermal fields a properly designed degasser tower is now a non-negotiable requirement; for plant fire protection NFPA 850 Chapter 15 gives recommended criteria (clause 15.1).

H2S: Health and Fire Hazards

  • TLV-TWA: 1 ppm (ACGIH threshold limit value)
  • IDLH: 100 ppm — immediately dangerous to life or health
  • LFL: 4.0% by volume
  • UFL: 44% by volume
  • Autoignition temperature: 260 °C
  • Odor threshold: 0.01 ppm — but above 150 ppm the sense of smell is paralyzed, so the nose is no longer a reliable warning

Degasser (NCG Removal)

The main methods used to remove non-condensable gases (NCG) from geothermal fluid:

  • Degasser tower: NCG separation under vacuum
  • H2S absorption: Iron oxide-based (Selectox) or LO-CAT process
  • Reinjection: NCG pumped back underground
  • Stack: Stack height is set according to the residual H2S content

Gas Detection and Ventilation

  • Personal gas monitors: Worn by every operator entering the site, without exception
  • Positive-pressure control room: Air balance set to prevent H2S from entering

Wellhead Control

  • Blowout preventer (BOP): To API 6A, with NACE MR0175-compliant materials for H2S service
  • Master valve and wing valve: Both remote and manual opening/closing
  • Flowline: Corrosion-resistant duplex steel against the aggressive geothermal fluid
  • Emergency shutdown (ESD) system: Able to shut in the well within 30 seconds
  • Warning signs on site: A rotten-egg odor at low concentrations; because the sense of smell is paralyzed at high concentrations, leak detection must rely on detectors

Ventilation and gas detection with MEP Calc

MEP Calc sizes 12 ach turbine hall ventilation, H2S/LEL detector placement and degasser stack height.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 55, API 6A, NACE MR0175, OSHA 29 CFR 1910.1000. NFPA 55 Compressed Gases standard.