Titanium, magnesium and zirconium powders feed aerospace and defense production at Turkish airframe, engine and missile manufacturers (3D printing, CNC milling). Ti dust cloud can ignite at about 330 °C, and water applied to most burning combustible metals intensifies the fire. NFPA 484 combustible metals requires a dust hazard analysis, a Class D extinguishing agent and dust-explosion protection.
Metal Dust Risk
- Ti: cloud MIE about 25 mJ, cloud ignition about 330 °C (10 µm sample; NFPA 652 Table A.5.2.2(h))
- Mg: cloud MIE about 40 mJ, cloud ignition about 620 °C (<44 µm sample; NFPA 652 Table A.5.2.2(h))
- Zr: MIE 5 mJ, very sensitive
- Al: MIE 50 mJ, Kst 415 bar·m/s
- Kst: Class St3 >300 bar m/s
NFPA 484 Limits
- Notification threshold: an operation that stores or processes 2.27 kg (5 lb) or more of powder or fines notifies the local emergency response agency (NFPA 484 8.4.1)
- Separation: physical barriers segregating dust flash-fire hazard areas need at least a 1-hour fire resistance rating (NFPA 484 4.8.2.1); in dust explosion hazard areas they are designed per NFPA 68 not to fail (4.8.2.2)
- Static: Grounding, bonded
- Dust collector: wet type is required for operations that make sparks or hot particles (NFPA 484 11.2.3.6.7); dry filter-media collectors are not allowed for dusts with Kst above 150 bar·m/s or for Nb, Ta, Ti, Zr and Hf unless a dust hazard analysis supports them (11.2.4.4.1)
Class D Extinguishing
- Salt-based dry powder: sodium chloride (NaCl) based agent; used only where it is shown effective on the metal involved (NFPA 484 8.3.3.1.1)
- Dry sand: Kept in buckets at hand
- Water and incompatible agents: water, foam, halon and CO2 are not used on combustible-metal fires unless shown compatible with the metal and effective (NFPA 484 8.3.3.5); ABC and BC dry chemical extinguishers are not used either (8.3.3.6)
Wet Dust Collector
- Type: Water-wash scrubber
- Reason: Dry filter explodes
- Emergency: Spark -> isolation damper
- Sludge: H2 evolution monitor
Turkey Sector
- Airframe manufacturing: Component production
- Aero-engine manufacturing: Engine parts
- Missile manufacturing: Mg alloy
- 3D metal printing: SLM powder bed

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 484, NFPA 652, NFPA 68, ASTM E1226, IEC 61241. NFPA 484 Combustible Metals.