A paper mill brings several different fire scenarios together in one plant: roll paper stacks up to 8 m high, dryer sections 50–100 m long, and pulping and bleaching areas under the same roof. Dry paper rolls carry a very high fire load. In these plants the NFPA 13 Ordinary Hazard Group 2 (OH2) classification applies, together with the NFPA 13 roll paper provisions and FM Global Data Sheet 8-21 for roll paper storage.

Paper Fire Load

  • Heat of combustion: generally 13.96 to 18.6 MJ/kg for ordinary combustibles (FM Global DS 8-1, 3.1.1.1)
  • Classification: Paper and pulp mills are OH2 per NFPA 13 A.4.3.3.2

ESFR for Roll Paper Storage

  • ESFR K25.2 (K360): Per NFPA 13 Table 23.6, maximum storage height 30 ft (9.1 m) for heavyweight paper only (25 ft / 7.6 m for mediumweight; not applicable to tissue), in buildings up to 45 ft (13.7 m)
  • Design: 12 sprinklers; minimum pressure 50 psi (3.4 bar) for K25.2 (K360) in a 45 ft (13.7 m) building
  • FM DS 8-21: The data sheet for roll paper storage (FM DS 8-1 is commodity classification and refers roll paper to DS 8-21)

Dryer Section

  • Sprinklers: Two lines, under the hood and above the belt
  • Broke: Combustible paper waste and a constant fire risk
  • Hood: Sprinkler layout under the arched hood ceiling is critical
  • Felt: Wool and fabric blend, highly combustible

Pulp Mill and Bleaching

  • Black liquor: Burned in the recovery boiler
  • Sprinkler density: OH2: 0.20 gpm/ft² (8.1 mm/min) over 1,500 ft² (140 m²) (NFPA 13 Table 19.2.3.1.1)

Turkish Paper Mills

  • A large mill, now closed: The largest paper mill of its time
  • A large production plant: 1.5 million tonnes a year of production capacity
  • Packaging paper plant: Mainly packaging paper lines
  • A paper mill fire: Still a reference case in the industry
  • Tissue lines: Toilet tissue and paper towel production

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 13, NFPA 664, FM DS 8-1, FM DS 8-21, FM DS 7-54, TAPPI guides. NFPA 13 Installation of Sprinkler Systems.