Aliaga, Mersin and Samsun ports host tank farms storing gasoline, diesel and jet fuel. A single tank is 50,000-100,000 m3; the Buncefield 2005 blast caused damage within a 1 km radius. NFPA 30 covers flammable liquids, API 650 tank design and dike dimensions.
NFPA 30 Classification
- Class IA: Flash <23 C, BP <38 C
- Class IB: Flash <23 C, BP >=38 C (gasoline)
- Class IC: Flash 23-38 C
- Class II: Flash 38-60 C (diesel)
- Class IIIA: Flash 60-93 C (fuel oil)
Tank Setback Distances
- Class I tank: 1.5x tank dia to neighbor
- Dike: 110 percent tank volume
- Dike wall: 1.8 m min height
- Tank-dike: Dia/2 min 3 m
- Property line: 1x dia min
Foam and Cooling
- Rim seal foam: 12.2 L/min/m2
- Full surface: 6.5 L/min/m2
- Dike foam: 6.5 L/min/m2
- Cooling water: 2.0 L/min/m2 burning tank
- Neighbour cooling: 4.1 L/min/m2 within 30 m
Lightning and Overfill
- API 2003: Lightning grounding
- Bypass ring: Upper rim bonded
- Overfill protection: 95 percent alarm, 98 percent stop
- Tank gauging: Radar + servo
- Cathodic protection: Bottom CP
Major Incidents
- Buncefield UK 2005: Overfill - 43 injured
- Caribbean BP 2009: Lightning
- Tupras Izmir: 12 Mt/y
- Alsancak port 2013: Tank fire
- CSB investigation: Large incident analysis

MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 30, NFPA 11, API 650, API 2003, FM DS 7-88. NFPA 30 Flammable and Combustible Liquids.