MEB operates 65,000 schools with 18 M students; an average school has 500 pupils on 3 floors. Chemistry labs, assembly halls and gyms need tailored egress. NFPA 101 mandates a monthly evacuation drill while school is in session, 2 doors for classes 50+, 1.8 m corridors, chemical labs per 8.7.4 (NFPA 45), sprinkler protection throughout, and panic hardware where doors from areas of 100 or more occupants have latches or locks.
Educational Categories
- Pre-school: Kindergarten
- Primary: 6-14 years
- Secondary: 14-18 years
- Adult education: Different rules
- Sprinklers: Educational buildings are protected throughout by supervised automatic sprinklers; the exceptions cover only non-relocatable buildings of up to 93 m2 or containing a single classroom, and certain relocatable buildings (NFPA 101-2024 14.3.5.1, 14.3.5.2)
Egress Rules
- Classroom 50+: 2 doors
- Door outward: Panic bar
- Corridor: 1.8 m min
- Travel: 61 m sprinklered, 46 m non-sprinklered (NFPA 101-2024 14.2.6)
- Drills: at least one in every month the school is in session, plus one more within the first 30 days of operation unless the school is open year-round (NFPA 101-2024 14.7.2.3)
Chemistry Lab
- Fume hood: face velocities of 0.4-0.6 m/s generally provide containment when the hood location and laboratory ventilation criteria are met (NFPA 45-2019 Annex A.7.4.7, informational)
- Solvent: Flammable cabinet
- Lab protection: laboratories using chemicals comply with 8.7.4 (NFPA 45); the building must be sprinklered throughout (NFPA 101-2024 14.3.2.4, 14.3.5.1); clean agent can only be supplementary
Gymnasium
- Assembly occupancy: Indoor gymnasiums and similar assembly spaces follow NFPA 101 Chapter 12 (NFPA 101-2024 14.1.3.3.1)
- Egress: 5 mm (0.005 m) exit width per person
Turkey Schools
- MEB total: 65,000 schools
- Students: 18 million
- Most populous province: 8000+ schools
- A school fire: evacuation reference case
- Feb 6, 2023: Earthquake evacuation

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 101, NFPA 45 lab, MEB, OSHA 1910, TS EN 14604. NFPA 101 Life Safety Code.