A shipyard is a heavy industrial facility with a high fire risk during the construction, repair and dismantling of vessels. The same picture appears on every project: welding, grinding, painting and fuel transfer all run in the same shift. NFPA 312 (Fire Protection of Vessels During Construction, Conversion, Repair, and Lay-Up) defines the rules for dry dock fire systems, hot work permits and gas-free certificates in this chaotic environment. On site, not even a welding machine should be switched on until these three items are in place.
Dry Dock Fire System
- Temporary fire hoses: shore-fed hoses placed aboard vessels at berths or in dry dock, connected and ready for use, at least one per 62 m (200 ft) of vessel length (NFPA 312 4.12.4.1)
Hot Work Permit
- NFPA 51B: the hot work standard; not a single arc is struck without a permit
- Fire watch: a second person separate from the worker; NFPA 312 requires at least 30 minutes of watch after the work ends, NFPA 51B (2019) requires 1 hour
- Spark blanket: stops sparks falling below or onto the side deck
- Portable extinguisher: a charged, operable extinguisher suited to the possible fire must be immediately available at the work area (NFPA 51B 5.5.1.10)
- Combustible material: combustibles within 10.7 m (35 ft) of the hot work are removed; if that is impractical they are shielded by a noncombustible barrier or suitable cover (NFPA 51B 5.5.1.3; if they can be neither removed nor protected a fire watch is required: NFPA 312 4.5.2.1)
Gas-Free Certificate
Before any tanker repair begins, a marine chemist steps in:
- A marine chemist certified by the NFPA tests the tank and issues the certificate (NFPA 306)
- Oxygen: 19.5-22% (NFPA 306 7.1.1)
- Lower explosive limit (LEL): below 10%
- Toxic materials (H₂S, CO, benzene and so on): within permissible concentrations (NFPA 306 7.1.1)
The conditions on the certificate are re-inspected by the competent person within 1 day, or more often where needed (NFPA 306 8.4). "It was clean yesterday" is not accepted on site.
Onboard Fixed CO₂
- Engine room: CO₂ total flooding under the SOLAS FSS Code
- Design concentration: 40% (diesel), 50% (gas-fuelled machinery)
- Manual release: release from two separate controls is required, with an interlock against discharge on a false alarm
- Special case: LNG carriers favour IG-541 or water mist instead of CO₂

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 312, NFPA 51B, SOLAS FSS Code, OSHA 29 CFR 1915, NFPA 306 Marine Chemist. NFPA 312 Vessels Construction standard.