A shipyard is a heavy industrial facility with a high fire risk during the construction, repair and dismantling of vessels. The same picture appears on every project: welding, grinding, painting and fuel transfer all run in the same shift. NFPA 312 (Fire Protection of Vessels During Construction, Conversion, Repair, and Lay-Up) defines the rules for dry dock fire systems, hot work permits and gas-free certificates in this chaotic environment. On site, not even a welding machine should be switched on until these three items are in place.

Dry Dock Fire System

  • Temporary fire hoses: shore-fed hoses placed aboard vessels at berths or in dry dock, connected and ready for use, at least one per 62 m (200 ft) of vessel length (NFPA 312 4.12.4.1)

Hot Work Permit

  • NFPA 51B: the hot work standard; not a single arc is struck without a permit
  • Fire watch: a second person separate from the worker; NFPA 312 requires at least 30 minutes of watch after the work ends, NFPA 51B (2019) requires 1 hour
  • Spark blanket: stops sparks falling below or onto the side deck
  • Portable extinguisher: a charged, operable extinguisher suited to the possible fire must be immediately available at the work area (NFPA 51B 5.5.1.10)
  • Combustible material: combustibles within 10.7 m (35 ft) of the hot work are removed; if that is impractical they are shielded by a noncombustible barrier or suitable cover (NFPA 51B 5.5.1.3; if they can be neither removed nor protected a fire watch is required: NFPA 312 4.5.2.1)

Gas-Free Certificate

Before any tanker repair begins, a marine chemist steps in:

  • A marine chemist certified by the NFPA tests the tank and issues the certificate (NFPA 306)
  • Oxygen: 19.5-22% (NFPA 306 7.1.1)
  • Lower explosive limit (LEL): below 10%
  • Toxic materials (H₂S, CO, benzene and so on): within permissible concentrations (NFPA 306 7.1.1)

The conditions on the certificate are re-inspected by the competent person within 1 day, or more often where needed (NFPA 306 8.4). "It was clean yesterday" is not accepted on site.

Onboard Fixed CO₂

  • Engine room: CO₂ total flooding under the SOLAS FSS Code
  • Design concentration: 40% (diesel), 50% (gas-fuelled machinery)
  • Manual release: release from two separate controls is required, with an interlock against discharge on a false alarm
  • Special case: LNG carriers favour IG-541 or water mist instead of CO₂

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 312, NFPA 51B, SOLAS FSS Code, OSHA 29 CFR 1915, NFPA 306 Marine Chemist. NFPA 312 Vessels Construction standard.