High-voltage power transformers (above 35 MVA) contain 30,000-80,000 litres of mineral oil. When a winding fault occurs, this oil can burst out and turn into a jet fire. NFPA 850 addresses exactly this scenario with oil containment (bunds), separation firewalls, water spray and K-class ester oil alternatives. The 2016 Berlin Tempelhof transformer explosion is a good reminder: the whole substation was out of service within minutes.
Transformer Oil Types
- Mineral oil: Diala-type mineral oil, flash point 145°C — the industry standard.
- Ester oil (K-class): fire point of 300°C or higher — a high fire point liquid under NFPA 850 (3.3.23.3).
- Silicone oil: flash point above 340°C; not very common in the field.
- Dry-type transformer (VPI): no oil — preferred for indoor installation.
For outdoor transformers insulated with a less flammable liquid, NFPA 850 recommends that separation from adjacent structures and transformers be set by firewalls or distance, based on the fire factors (6.1.4.6).
Separation Distances (NFPA 850 5.2)
- Building to transformer: without a firewall, the recommended line-of-sight separation is 1.5 m for under 1893 L of oil, 7.6 m for 1893-18,925 L and 15 m above 18,925 L (NFPA 850 6.1.4.3, Table 6.1.4.3). For less flammable liquid transformers the distance or firewall is set from the fire factors (6.1.4.6).
- Transformer to transformer: adjacent transformers holding 1893 L (500 gal) or more of oil are recommended to be separated by a 2-hour firewall or by the distances in the same table (NFPA 850 6.1.4.4).
- Firewall: 2-hour fire rating, extending at least 0.31 m (1 ft) above the top of the casing and conservator and at least 0.61 m (2 ft) beyond the width of the transformer and radiators, or to the edge of the containment area (NFPA 850 6.1.4.4).
Oil Containment Design
- Volume: it is recommended to size it for the spill of the largest single container plus the maximum fire hose and fixed-system discharge for at least 10 minutes (NFPA 850 6.5.1.1).
- Stone fill: in an open pit, a 30 cm layer of washed, uniformly sized stone of 3.8 cm (1.5 in) or larger between grating (or sprinkler or water spray over the pit area at 6 mm/min) is one of the recommended protections (NFPA 850 6.5.5.2).
- Drainage: provide drainage for outdoor oil-insulated transformers, or slope the ground so that oil spills flow away from structures and adjacent transformers (NFPA 850 6.5.5).
- Concrete joints: use oil-tight joint tape at penetrations.
Water Spray (Deluge)
- Design density: at least 10.2 L/min/m² (0.25 gpm/ft²) over the projected area of the rectangular prism enclosing the transformer and its appurtenances, and at least 6.1 L/min/m² (0.15 gpm/ft²) on the nonabsorbing ground surface of the exposure area (NFPA 15 7.4.4.3.1).
- Activation: Buchholz relay combined with heat detectors.
- Nozzles: medium-velocity projector type, 25-30 m throw.
- Alternatives: water mist, aerosol extinguishing or N₂ inerting solutions.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 850, NFPA 15, IEC 61936-1, IEEE 979, FM Global DS 5-4. NFPA 850 Electric Generating Plants.