Short answer: Not mandatory; one of two options is applied. TS EN 12845+A2:2026 Clause 7.2.2.3 (EN p.36-37): where the clearance between the storage height and the ceiling sprinkler deflector exceeds 4 m, either Option 1 is applied, that is the density is increased by 2.5 mm/min for the first metre of excess and by a further 1 mm/min for each subsequent metre, with a minimum of K115; or Option 2 is applied, that is intermediate level in-rack sprinklers are provided in accordance with 7.2.3. As a separate provision, Clause 12.5.2 requires an intermediate level to be installed above the top level of the storage unless all ceiling or roof sprinklers are less than 4 m above the storage.

In high hazard storage, intermediate level in-rack sprinklers are covered in two separate clauses of EN 12845: the layout geometry in Clause 12.5 and the hydraulic assumptions in Clause 7.2.3. An in-rack design cannot be verified without reading these two clauses together. Source: TS EN 12845+A2:2026, Clause 12.5, EN p.78-81 and Clause 7.2.3, EN p.37.

When intermediate levels are required

There are two separate triggers.

1. Excessive clearance: Clause 7.2.2.3 (EN p.36-37)

The values in Table 4 are used to determine the clearance. Where the clearance, that is the distance between the storage height and the ceiling sprinkler deflector, exceeds 4 m, one of the following options is applied:

In other words, a clearance of 4 m does not by itself make in-rack sprinklers mandatory; increasing the density is an equivalent route.

2. Exceeding the storage height limit: Clause 7.2.2.2 (EN p.36)

Table 4 gives the maximum storage height that can be protected by roof or ceiling protection alone, by category and storage type. Where the storage heights exceed this limit, intermediate level in-rack sprinklers are provided in accordance with 7.2.3.

3. The trigger from the layout rule: Clause 12.5.2 (EN p.78)

An intermediate level is installed above the top level of the storage; the exception is where all roof or ceiling sprinklers are less than 4 m above the storage.

Footnote c) to Table 2 (EN p.34) repeats the same threshold: the relevant protection method is limited to risks where the ceiling sprinklers are less than 4 m above the highest level of the goods stored; where the ceiling sprinklers are more than 4 m above, intermediate level in-rack sprinklers are used.

Clause 12.5.1: general layout and flue distances

Source: EN p.78.

Clause 12.5.2: vertical spacing

The vertical distance from the floor to the lowest intermediate level and between levels does not exceed 3.50 m or two tiers, whichever is the smaller (see Figures 13 and 14). In no case may the highest row of intermediate level sprinklers be installed lower than one tier below the top of the storage (EN p.78).

Clause 12.5.3: horizontal position

Goods category Layout Maximum horizontal distance Product of horizontal × vertical distance Page
Category I or II As far as possible within the longitudinal flue, at the intersection with every second transverse flue, staggered relative to the row above (see Figure 13) 3.75 m Shall not exceed 9.8 m² EN p.78
Category III or IV Within the longitudinal flue, at the intersection with every transverse flue (see Figure 14) 1.9 m Shall not exceed 4.9 m² EN p.80

This product condition means that the horizontal and vertical spacings cannot be chosen independently of each other. For example, if a horizontal spacing of 3.75 m is chosen for Category I goods, the vertical spacing is limited to 9.8 / 3.75 = 2.61 m; if a vertical spacing of 3.50 m is wanted, the horizontal spacing falls to 9.8 / 3.50 = 2.80 m. These two figures are the arithmetic that follows from the product of the two limits in the table.

Clause 12.3 (EN p.72) states that sprinklers shall not be installed at spacings closer than 2 m, but lists intermediate level sprinklers in racks among the exceptions to that rule (see 12.5.3).

Clause 12.5.4: number of rows per level

The number of sprinkler rows per level is determined by the total rack width. Where racks are placed back to back, the total width is calculated by adding the width of each rack and the distance between them. One row of sprinklers per level is installed for every 3.2 m of rack width. These are installed in the flue spaces wherever possible (EN p.80).

Clause 12.5.5: HHS intermediate level sprinklers in racks without shelves

For pallet rack storage and multiple row drive-through storage (see Figure 3 and type ST4 in Table 4), intermediate level sprinklers are installed as follows (EN p.80-81):

Where any shelf or structural steelwork could significantly obstruct the water distribution of a sprinkler, an additional sprinkler is provided to ensure water distribution in the area that would be obstructed.

Clause 12.5.6: solid or slatted shelf racks (ST5 and ST6)

Where intermediate level sprinklers are required, they are installed above each shelf. Where the roof or ceiling sprinklers are more than 4 m above the goods, or where water access to the goods is restricted, the top shelf is also included. The positioning is as shown in Table 21 and Figure 15. The vertical distance between rows does not exceed 3.5 m. Single rows of sprinklers are located centrally above the shelves; double rows are positioned so that each row is at the same distance from the nearest shelf edge (EN p.81).

Table 21: Position of intermediate level sprinklers in ST5 and ST6 storage (EN p.82)

Shelf width s (m) Rows of sprinklers Maximum distance between sprinklers along the rows (m) Maximum distance between rows of sprinklers (m)
ST5: s ≤ 1.0 1 2.8 -
ST6: 1.0 < s ≤ 3.0 1 2.8 -
ST6: 3.0 < s ≤ 6.0 2 2.8 2.8

The distance from the end of the shelf parallel to the range pipe lines to the nearest sprinkler is half the sprinkler spacing along the range lines or 1.4 m, whichever is the smaller (EN p.82).

Clause 7.2.3: hydraulic assumptions

Subclause Provision Page
7.2.3.1 Where more than 50 intermediate level sprinklers are installed in racks, they shall not be fed from the same control valve set as the roof or ceiling sprinklers EN p.37
7.2.3.2 The design density for the roof or ceiling sprinklers shall be at least 7.5 mm/min over an area of operation of 260 m². Where goods are stored above the highest intermediate protection level, the design criteria for the roof or ceiling sprinklers are taken from Table 5 EN p.37
7.2.3.3 For the purpose of hydraulic calculation, 3 sprinklers are assumed to operate simultaneously at each in-rack sprinkler level in the hydraulically most remote position, up to a maximum of three levels. Where the rack aisles are 2.4 m or wider, only one rack is assumed to be involved; where narrower than 2.4 m but equal to or wider than 1.2 m, two racks; where narrower than 1.2 m, three racks. Note: it is not necessary to assume that more than three rows of sprinklers operate simultaneously in the vertical plane and more than three in the horizontal plane EN p.37
7.2.3.4 In-rack sprinklers and the associated ceiling sprinklers are always fully calculated (see 13.1). Note: the minimum pressure at any operating sprinkler is 2.0 bar (see 13.4.4) EN p.37

Clause 13.1 (EN p.82) repeats the same rule: full calculation is always used for arrangements with intermediate level HHS sprinklers and for gridded or looped arrangements.

Pressure: Clause 13.4.4 and the note to 7.2.3.4

Clause 13.4.4 (EN p.102) determines the pressure at the hydraulically most unfavourable sprinkler, with all sprinklers in the area of operation operating, as not less than that required to give the density specified in 13.4.1 or than the following values, whichever is the higher:

Case Minimum pressure
LH 0.70 bar
OH 0.35 bar
HHP and HHS (excluding in-rack sprinklers) 0.50 bar
K115 in-rack sprinklers 1.00 bar
K80 in-rack sprinklers 2.00 bar

The note to Clause 7.2.3.4 states that "the minimum pressure at any operating sprinkler is 2.0 bar" and refers to 13.4.4. The difference between that note and the list in 13.4.4 arises from the K80 in-rack row being 2.00 bar. In design both should be read; the higher value is binding.

Sprinkler type, sensitivity and water shield

The relationship with goods category and ESFR

The classification of stored goods into Categories I-IV is given in Annex B (methodology, EN p.127-131) and in Annex C (product list). Annex A is the list of hazard class (LH, OH, HHP) occupancies; Annex D is "Zoning of sprinkler installations".

Annex P (normative, EN p.164) gives the direction for ESFR systems: EN 12845-2 applies in conjunction with this document for ESFR sprinkler systems, and Annex A of EN 12845-2:2024 applies because of the different hazard classification systems. EN 12845-2:2024 contains only Annex A; it has no other annex. Arrangements in which ESFR ceiling sprinklers are used together with in-rack sprinklers are addressed in Clause 6.6.2 of that standard.

Frequently Asked Questions

Are intermediate level sprinklers mandatory where the ceiling sprinklers are more than 4 m above the storage?

Not mandatory; one of two options is applied. TS EN 12845+A2:2026 Clause 7.2.2.3 (EN p.36-37): where the clearance between the storage height and the ceiling sprinkler deflector exceeds 4 m, either Option 1 is applied, that is the density is increased by 2.5 mm/min for the first metre of excess and by a further 1 mm/min for each subsequent metre, with a minimum of K115; or Option 2 is applied, that is intermediate level in-rack sprinklers are provided in accordance with 7.2.3. As a separate provision, Clause 12.5.2 requires an intermediate level to be installed above the top level of the storage unless all ceiling or roof sprinklers are less than 4 m above the storage.

What vertical distance is permitted between intermediate levels?

Clause 12.5.2 (EN p.78): the vertical distance from the floor to the lowest intermediate level and between levels does not exceed 3.50 m or two tiers, whichever is the smaller. In no case may the highest row of intermediate level sprinklers be installed lower than one tier below the top of the storage.

What is the minimum pressure at in-rack sprinklers?

Clause 13.4.4 (EN p.102): the pressure at the hydraulically most unfavourable sprinkler shall be not less than that required to give the density specified in 13.4.1, or than the following values, whichever is the higher: 0.70 bar in LH; 0.35 bar in OH; 0.50 bar in HHP and HHS excluding in-rack sprinklers; 1.00 bar for K115 in-rack sprinklers; 2.00 bar for K80 in-rack sprinklers. The note to Clause 7.2.3.4 states a minimum pressure of 2.0 bar at any operating sprinkler and refers to 13.4.4; the two places must be read together.

How many racks and how many levels are assumed to operate at once in the hydraulic calculation?

Clause 7.2.3.3 (EN p.37): at each in-rack sprinkler level, 3 sprinklers are assumed to operate simultaneously in the hydraulically most remote position, up to a maximum of three levels. Where the rack aisles are 2.4 m or wider, only one rack is assumed to be involved; where the aisles are narrower than 2.4 m but equal to or wider than 1.2 m, two racks; where the aisles are narrower than 1.2 m, three racks.

Are water shields required on intermediate level sprinklers?

Clause 14.7 (EN p.106): sprinklers installed in racks or below perforated shelves, platforms, floors and the like, where water from one or more sprinklers higher up could wet the area near the bulb or fusible element, are provided with a metal water shield at least 0.075 m in diameter. Water shields on upright sprinklers are not connected directly to the deflector or to the yoke, and any bracket supports are designed to minimize obstruction to the sprinkler water distribution. The standard does not exempt the top level.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.