Choose the standard, rack type and size, tier height and commodity; the tool gives the number and height of in-rack levels, the spacing along and across the rack, the head count and the sprinkler type with clause and figure numbers, and shows them in elevation, plan and a 3D rack model.

NFPA 13 Chapter 25CMDA · CMSA · ESFR · 25.7EN 12845 12.5FM DS 8-9 2.3.4 · 2.3.63D rack model

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

38 more calculators ↓

What are in-rack sprinklers and when are they needed?

In-rack (intermediate level) sprinklers are fitted inside the rack structure, in the flue spaces between loads, where the water from the ceiling sprinklers cannot reach the lower tiers of high-bay storage. All three standards place them at the intersections of transverse and longitudinal flues; the number of levels depends on storage height, tier height and commodity. This tool calculates the layout; the ceiling design, pipe sizes and hydraulic calculation are done separately.

EN 12845: the 3.50 m rule and clause 12.5

FM DS 8-9: IRAS(E) and IRAS(EO)

FM Global selects the horizontal arrangement with the flowcharts in Figs. 5, 5a, 6, 6a and 7. The decision depends on:

IRAS(EO) places sprinklers at every other transverse flue, 1.2–3.0 m apart; IRAS(E) at every transverse flue, 0.6–2.4 m apart. The vertical increment follows Fig. 15 by commodity: 7.5, 6.0, 4.5 or 3.0 m, with at most 3.0 m of storage above the top level. In-rack sprinklers are FM Approved, quick response, 70 °C nominal (2.3.4.3). The design comes from Table 12 and the ceiling protection table from Table 13.

NFPA 13-2025: Chapter 25 figures

NFPA 13 gives in-rack arrangements combined with CMDA ceiling sprinklers as figures by commodity and height (25.4.2).

Clearance rule: up to 7.6 m of storage, where the clearance exceeds 6.1 m for Class I–IV or 3.0 m for Group A, either the ceiling design uses a theoretical storage height or a level is added directly below the top tier. Above 7.6 m of storage, a clearance over 3.0 m makes that extra level mandatory; the tool adds it at every flue intersection.

NFPA 13: with CMSA and ESFR ceilings (25.5, 25.6)

NFPA 13: options independent of the ceiling (25.7)

For closed-top Class I–IV and Group A plastics the in-rack system is designed independently of the ceiling; the top in-rack level counts as the floor for the ceiling design (25.7.3.2.1).

NFPA 13: rubber tires (25.4.2.5)

Rubber tires on pallets, on-side or on-tread, stored over 3.7 m and up to 6.1 m are protected per Figure 25.4.2.5.1(a) and (b), in a building (ceiling) up to 9.1 m. In-rack layouts are given only with CMDA ceilings.

FM DS 8-9: special applications (2.3.6)

In the “Design route” step, the in-rack options of 2.3.6 can replace the standard 2.3.4 layout. Each comes with its own commodity, rack and ceiling conditions; where they are not met the tool says out of scope.

2.3.6.1 and 2.3.6.9 are ceiling-only protection and 2.3.6.2 sets when retail racks count as open-frame. They contain no in-rack layout, so they are not in the tool.

Counting convention: if the gap from the last sprinkler to the rack end exceeds half the spacing, the end also gets a sprinkler. Cases the figure does not dimension (e.g. the spacing along a double-row rack in NFPA) are flagged separately in the result.

Frequently Asked Questions

What is the maximum vertical distance between in-rack levels in EN 12845?

Under clause 12.5.2, floor to the lowest level and between levels at most 3.50 m or two tiers, whichever is less. The highest level may not be more than one tier below the top of storage.

Is a level needed above the top of storage?

In EN 12845 not if all ceiling sprinklers are less than 4 m above the storage; otherwise yes (12.5.2). In FM DS 8-9 at most 3.0 m of storage may remain above the top level (Fig. 15).

What is the difference between IRAS(E) and IRAS(EO) in FM DS 8-9?

IRAS(EO) puts sprinklers at every other transverse flue intersection (1.2–3.0 m), IRAS(E) at every transverse flue intersection (0.6–2.4 m). The flowcharts in Figs. 5–7 decide which is acceptable.

Where does a single in-rack level go in NFPA 13?

Where the figure does not show it, at the first tier level at or above half the storage height (25.1.8.1). For two levels, one-third and two-thirds are used (25.1.8.2).

What are the ceiling-independent in-rack options in NFPA 13 (25.7)?

Four options where the in-rack system is designed independently of the ceiling sprinklers: Option 1 (K115, with barriers, 3.7 m), 2a and 2b (ESFR K200 and K320; 9.1 and 12.2 m) and 3 (K360 extended coverage, with barriers, 9.1 m). The top in-rack level counts as the floor for the ceiling design (25.7.3.2.1).

How are in-rack sprinklers arranged for rack storage of rubber tires in NFPA 13?

For palletized tires stored over 3.7 m and up to 6.1 m (Figure 25.4.2.5.1), one level goes at the tier level at or above half the storage height, with sprinklers at most 2.4 m apart. Design 12 sprinklers × 114 L/min; ceiling 16.3 mm/min over 280 m² (9.8 mm/min with high-expansion foam); building at most 9.1 m.

What is the FM DS 8-9 alternative in-rack design (2.3.6.6)?

As an alternative to the 2.3.4 layouts, pendent quick-response storage sprinklers (at least K320; K200 where the flow is 380 L/min or less) are used in the rack 0.7–1.4 m apart. Levels at most 9.0 m apart, or 12 m for Class 1–4 and cartoned unexpanded plastics; the ceiling is designed with the top level as the floor. The number of sprinklers comes from Table 15 and the most remote flow from Table 16.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →