Short answer: TS EN 12845+A2:2026 Clause 10.6.2.2 (EN p.59): under positive head conditions the suction pipe size shall not be less than 65 mm and a velocity of 1.8 m/s shall not be exceeded with the pump running at its maximum demand flow. Clause 10.6.2.3 (EN p.60): under suction lift conditions the size shall not be less than 80 mm and a velocity of 1.5 m/s shall not be exceeded at the maximum demand flow. In addition, on suction lift the height from the low water level to the pump axis does not exceed 3.2 m.

The suction pipe is the least forgiving part of a sprinkler pump set: the wrong diameter, the wrong slope or an inadequate NPSH margin translates directly into cavitation and loss of flow. TS EN 12845+A2:2026 covers this subject in Clause 10.6.2 and defines two different regimes: positive suction head and suction lift. Source: TS EN 12845+A2:2026, Clause 10.6, EN p.59-62.

First, the order of preference: Clause 10.6.1

Wherever possible, horizontal centrifugal pump sets are used and installed under positive suction head, that is (EN p.59):

Where this is not possible, the pump may be installed under suction lift conditions or vertical turbine pumps may be used. Suction lift and submersible pump arrangements should be avoided and used only where it is not practicable to arrange a positive suction head.

10.6.2.1 General provisions

Source: EN p.59.

Table 14: Pump pressure and flow assessment (EN p.59)

Pipework Hazard class Rated pump flow Pump inlet condition
Pre-calculated LH/OH Pressure and flow requirements from Table 6 For tanks, water supply at the low water level (see X in Figure 4)
Pre-calculated HH Pressure and "1.4 - flow" required from Table 7 For booster pumps, at the minimum town main pressure
Fully calculated All Maximum pressure and flow required for the most favourable area -

Note: in the printed text the expression in the HH row reads "Pressure and 1,4 – flow required from Table 7". Since the mark used here is a dash, it cannot be established from the printed text alone whether the factor is 1.4 times or some other operation. In design this row should be interpreted together with Table 7 and, if necessary, in consultation with the approval authority.

The numerical requirements of the two regimes

Item Positive suction head (10.6.2.2) Suction lift (10.6.2.3)
Minimum suction pipe size 65 mm 80 mm
Maximum velocity (at maximum demand flow) 1.8 m/s 1.5 m/s
Interconnection of suction pipes Only where stop valves allow one to continue operating while the other is taken out for maintenance; the connections are sized for the required flow Not permitted
Height from low water level to pump axis The pump axis not more than 2 m above the tank low water level (10.6.1) Does not exceed 3.2 m
Foot valve Where the pump axis is above the low water level (10.6.2.1) Fitted at the lowest point of the suction pipe
Priming - Each pump set has an automatic priming arrangement conforming to 10.6.2.4
Positioning within the tank - The pipe is positioned in accordance with Figure 4 and Table 12, or with Figure 5 and Table 13, as appropriate

Source: EN p.59-60.

Checking the diameter against the velocity limit

The standard gives only the two velocity limits; it gives no table of maximum flow by diameter. The following table is derived from those two limits using the relationship v = 4Q/(πd²), taking the nominal diameter as the basis of calculation. In a real project the internal diameter, which depends on the pipe wall thickness, should be used; a calculation based on the nominal diameter is for preliminary screening only.

Nominal size Maximum flow, 1.8 m/s (l/min) Maximum flow, 1.5 m/s (l/min)
DN65 358 DN65 cannot be used on suction lift
DN80 543 452
DN100 848 707
DN150 1 908 1 590
DN200 3 393 2 827
DN250 5 301 4 418
DN300 7 634 6 361

Worked check: if a maximum demand flow of 3 000 l/min is carried in DN200 under suction lift conditions, the velocity works out at 21.22 × 3 000 / 200² = 1.59 m/s and the 1.5 m/s limit of 10.6.2.3 is exceeded; DN250 is required at this flow, because in DN250 the velocity becomes 21.22 × 3 000 / 250² = 1.02 m/s. The same flow in DN200 under positive head gives 1.59 m/s and stays below the 1.8 m/s limit of 10.6.2.2. In other words, the same flow requires a different diameter depending on the suction regime.

10.6.2.4 Pump priming

Each pump set is provided with a separate automatic priming arrangement. The arrangement consists of the following (EN p.60):

Figure 6 shows two examples: example A with a low level switch, example B with a low level valve for pump starting.

The tank, the pump of the pump set and the suction pipework are kept continuously full of water, even if there is leakage from the foot valve referred to in 10.6.2.3. If the water level in the tank falls to 2/3 of the normal level, the pump shall start. Alternatively, an alarm is transmitted to a permanently attended location so that immediate action can be taken.

Annex I, Table I.1 (EN p.155) classifies this alarm as a type B (technical) alarm in the row "low level priming tank, Clause 10.6.2.4".

Table 15: Pump set priming tank capacity and pipe size (EN p.62)

Hazard class Minimum tank capacity (litres) Minimum priming pipe size (mm)
LH 100 25
OH, HHP and HHS 500 50

10.6.2.5 Pressure maintenance pump

A pressure maintenance pump may be installed to prevent unnecessary starting of one of the main pump sets or to maintain the system pressure above the control valve sets in the case of water supplies with fluctuating pressure, such as a town main (EN p.60).

Valves, strainers and fittings on the suction pipe

Clause 10.5 (EN p.58):

Clause 9.3.6 (EN p.51):

Clause 20.3.4.5 (EN p.122) requires, in the annual routine, that pump set suction strainers, the settling chamber and screens be inspected at least annually and cleaned where necessary.

Frequently Asked Questions

What is the velocity limit in an EN 12845 suction pipe?

TS EN 12845+A2:2026 Clause 10.6.2.2 (EN p.59): under positive head conditions the suction pipe size shall not be less than 65 mm and a velocity of 1.8 m/s shall not be exceeded with the pump running at its maximum demand flow. Clause 10.6.2.3 (EN p.60): under suction lift conditions the size shall not be less than 80 mm and a velocity of 1.5 m/s shall not be exceeded at the maximum demand flow. In addition, on suction lift the height from the low water level to the pump axis does not exceed 3.2 m.

What does EN 12845 require for NPSH?

Clause 10.6.2.1 (EN p.59): the suction pipework, including all valves and fittings, is designed in accordance with EN 17451 so that the NPSH available at the pump inlet, calculated at the maximum expected water temperature, exceeds the NPSH required by at least 1 m at the maximum pump set flow shown in Table 14.

May suction pipes be interconnected?

Conditionally yes under positive head, and no on suction lift. Clause 10.6.2.2 (EN p.60): where there is more than one pump set, the suction pipes may be interconnected only if they are provided with stop valves which allow one to continue to operate while the other is removed for maintenance; the connections are sized for the required flow. Clause 10.6.2.3 (EN p.60): on suction lift, where there is more than one pump set, the suction pipes shall not be interconnected.

What capacity shall the priming tank have?

Table 15 (Clause 10.6.2.4, EN p.62): for LH the minimum tank capacity is 100 litres and the minimum priming pipe size 25 mm; for OH, HHP and HHS, 500 litres and 50 mm. Clause 10.6.2.4 (EN p.60) requires each pump set to be provided with a separate automatic priming arrangement, the tank to be at a higher level than the pump, a sloping pipe connection to run from the tank to the delivery side of the pump, and a check valve to be fitted in that connection.

What shall the slope of the suction pipe be?

Clause 10.6.2.1 (EN p.59): the suction pipework is laid either horizontally or with a continuous slight rise towards the pump, in order to avoid the possibility of an air lock forming in the pipe. The standard gives no numerical slope percentage or ratio here.

References

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; TS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.