What the tool does
Bunding (the tank dike) that holds liquid spilled from outdoor above-ground tanks is governed in Turkey by Article 119/2 of the Regulation on the Fire Protection of Buildings (BYKHY), and on NFPA projects by NFPA 30 Section 22.11; the tool has a tab for each. The BYKHY explanation below is for the first tab. For your tank arrangement the tool finds the bund volume the regulation requires, works out the net volume your bund dimensions provide, gives the minimum bund wall height and checks the tank-to-bund distance under 119/2-ğ. The result shows a section with the bund walls, tanks and the required liquid level.
Liquid classes: what do Class I, II and III mean?
Liquids fall into three main classes by flash point; there is no "Class IV". The limits are the same in BYKHY Article 113 and NFPA 30 Section 4.2. The examples come from Table 113 of the BYKHY Guide (December 2024), which gives none for Class IIIA.
| Class | Flash point | Boiling point | Examples |
|---|---|---|---|
| IA (flammable) | Below 22.8 °C | Below 37.8 °C | Butyne, ethyl ether, ethyl chlorite |
| IB (flammable) | Below 22.8 °C | 37.8 °C or above | Acetone, petrol, ethyl alcohol |
| IC (flammable) | 22.8 °C to 37.8 °C | — | Butyl alcohol, isobutyl alcohol |
| II (combustible) | 37.8 °C to 60 °C | — | Diesel, kerosene |
| IIIA (combustible) | 60 °C to 93 °C | — | — |
| IIIB (combustible) | 93 °C or above | — | Biodiesel, antifreeze, lubricating oils |
For Class I the vapour pressure at 37.8 °C does not exceed 276 kPa. Under BYKHY, Class II and IIIA liquids heated above their flash point count as Class I (113/2). Decide from the flash point on the safety data sheet, not from the product name.
Article 119/2: required bund volume
| Case | Bund volume | Clause |
|---|---|---|
| Tanks of the same size | Volume of one tank | 119/2-a |
| Tanks of different sizes | Volume of the largest tank | 119/2-a |
| Portable tanks | 75% of the total volume, or at least the volume of the largest portable tank | 119/2-b |
| Mixed storage | Sum of the volumes under (a) and (b) | 119/2-c |
| Crude oil, carbon disulphide | Total volume | 119/2-ç |
The portable-tank clause joins its two conditions with "or at least"; the tool takes the larger of the two (safe reading). Example: portable tanks totalling 8 m³ with the largest at 2 m³ give 0.75 × 8 = 6 m³. With three 50 m³ fixed tanks in the same bund, mixed storage needs 50 + 6 = 56 m³.
How the net volume is worked out
Guide Figure 119.2 shows the bund volume as side lengths times height. In a real bund the other tanks and the foundations take up space up to the wall height and liquid cannot fill it. The regulation does not state this deduction; the tool makes it as a calculation assumption:
Vnet(h) = L × W × h − Σ π/4 × Di² × min(h, hfound + Hi) − π/4 × Dlargest² × min(h, hfound) − Vother
- The largest tank, which fills the bund, is taken as empty; only its foundation is deducted.
- Every other tank is deducted with its foundation as a solid cylinder up to the bund height.
- Tanks are vertical cylinders on foundations of the same diameter; tank volume is π/4 × D² × H.
- Supports, plinths and portable containers go into the "other volumes" field.
The minimum bund height is the height at which the net volume equals the required volume. If the tank footprints fill the bund area no such height exists, and the tool says so.
Bund and tank layout
| Rule | Requirement | Clause |
|---|---|---|
| Tank to bund | At least 3 m from bund walls lower than 4/5 of the tank height, measured from the tank shell | 119/2-ğ |
| Dividing walls | Not lower than 4/5 of the outer wall; channels open on top | 119/2-ı |
| Construction | Excavated or walled; non-combustible except the sealing membrane; liquid-tight in a fire | 119/2-g |
| Penetrations and drainage | Sealed pipes; water can be drained; closable outlet with a liquid separator | 119/2-h |
| Inside the bund | Only valves and pipes besides the tanks | 119/2-i |
The 3 m rule in 119/2-ğ is written only for bund walls lower than 4/5 of the tank height; for a higher wall the clause sets no distance. The tool works out 4/5 of each tank group's height and compares the shortest distance you enter.
How many bund zones?
Class I, II and III liquids other than crude oil and carbon disulphide may share one bund zone while the total, expressed as Class IA, does not exceed 12,500 litres (119/2-d). Article 119 gives no conversion ratio; the tool uses the storage-building ratios of 118/2 (IB/2, IC/4, II/12, IIIA/40, IIIB/80) as an assumption and warns if the limit is exceeded. For crude oil or carbon disulphide one bund zone is allowed while the stored volume stays within 15,000 m³ and the bund surface within 700 m² (119/2-e); the tool takes the surface as the bund inside area. Clauses (a) and (b) also apply where Class I, II and III liquids are stored together (119/2-f).
The bund does not replace the protection zone around the tanks: for above-ground tanks the clearance comes from Annex 12/C, for portable containers from Annex 12/D, and at least two-thirds of it lies outside the bund (119/3).
The NFPA 30 tab: Section 22.11
NFPA 30-2024 Section 22.11 governs spill control for tanks of Class I, II and IIIA liquids; Class IIIB is outside its scope. The tab works out the open-dike solution for aboveground tanks; the section is written for tanks, so the portable tank option is hidden.
| Topic | Requirement | Clause |
|---|---|---|
| Dike capacity | The greatest amount the largest tank can release, assuming a full tank | 22.11.2.2 |
| Other tanks | The volume of tanks other than the largest below the dike height is deducted | 22.11.2.2.1 |
| Property line | Outside base of the dike at least 3 m away | 22.11.2.3 |
| High dikes | Over 1.8 m: access and egress provisions; tank shell to interior toe at least 1.5 m | 22.11.2.5 |
| Class I, very high dikes | Over 3.6 m, or distance below the dike height: valves and roof reached without entering below the top of the dike | 22.11.2.5(1) |
| Subdivision | Two or more tanks: drainage channels or intermediate dikes at least 450 mm high | 22.11.2.6, .6.2 |
| Subdivision limits | Floating or weak-seam cone roofs, and crude in producing areas: single tank 1590 m³, group 2385 m³; others: single tank 380 m³, group 570 m³ | 22.11.2.6.3.1–3 |
| Large diameter | Class I, over 45 m: intermediate dikes hold 10% of the tank | 22.11.2.6.3.4 |
The clearest difference between the two bases: BYKHY does not state the deduction of the other tanks, so in the tool it is an assumption, while NFPA 30 requires it outright. The subdivision limits apply to stable liquids. NFPA 30 Annex A notes that freeboard may be added for precipitation and firefighting water (A.22.11.2.2); the tool does not add it. Remote impounding (22.11.1), closed-top diking (22.11.3) and secondary containment tanks (22.11.4) are separate solutions. In Turkey the legal requirement is BYKHY: the NFPA 30 tab does not replace it, so check the BYKHY tab too.
Common mistakes
- Relying on the gross volume: the other tanks and foundations take up space inside the bund.
- Using only 75% for portable tanks: if the largest container is bigger, that governs.
- Placing a low wall against the tank: walls lower than 4/5 of the tank height need at least 3 m.
- Draining the bund to the storm-water line: the Annex 12/C note asks for a separate channel system and 119/2-h for a closable outlet with a liquid separator.
For tank distances to boundaries and between tanks, use the Annex 12/C part of the flammable liquid class and storage tool.
Frequently Asked Questions
How is the bund volume taken for tanks of different sizes?
Under BYKHY 119/2-a the volume of the largest tank; for tanks of the same size, the volume of one tank. For crude oil and carbon disulphide the total volume is needed (119/2-ç).
What is the 75% rule for portable tanks?
The bund volume is 75% of the total volume of the portable tanks, or at least the volume of the largest portable tank (119/2-b). The tool takes the larger.
Are the other tanks in the bund deducted?
The regulation does not say; Guide Figure 119.2 shows only side lengths × height. As a stated assumption the tool deducts the volume the other tanks and the foundations take up to the bund height.
How far must a tank be from the bund wall?
At least 3 m from walls lower than 4/5 of the tank height, measured from the tank shell (119/2-ğ). For a higher wall the clause sets no distance.
What do Class I, II and III liquids mean, and is there a Class IV?
The class comes from the flash point: Class I below 37.8 °C (IA, IB, IC), Class II 37.8–60 °C, Class III 60 °C and above (IIIA, IIIB). BYKHY Article 113 and NFPA 30 Section 4.2 use the same limits; there is no Class IV.
Is the dike volume the same under NFPA 30 and BYKHY?
For fixed tanks both ask for the volume of the largest tank (22.11.2.2, 119/2-a). The differences are in the detail: NFPA 30 requires the other tanks to be deducted and sets a 1.5 m tank-to-dike distance only for dikes over 1.8 m; BYKHY asks for 3 m where the wall is below 4/5 of the tank height, and has separate volume rules for portable tanks and crude oil.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design in Three Standards
Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.
Get SprinkCalc on the App Store